Heat Exchange Design and Optimization Project Presented: May 6 th , 2010

Heat Exchange Design and Optimization Project Presented: May 6 th , 2010 Professor: Mr. Toksoy Group Members: Nathan Dart Andrew Kinney Paul Thompson Joe Sullivan Christian Watness. Problem Statement:. Using a heat exchange reduce a liquid chemical by 20⁰C via city water.

tulia
Download Presentation

Heat Exchange Design and Optimization Project Presented: May 6 th , 2010

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Heat Exchange Design and Optimization Project Presented: May 6th, 2010 Professor: Mr. Toksoy Group Members: Nathan Dart Andrew Kinney Paul Thompson Joe Sullivan Christian Watness

  2. Problem Statement: Using a heat exchange reduce a liquid chemical by 20⁰C via city water. • Design Criteria/Assumptions: • Mass flow rate = 220,000 kg/hr • Material properties of this chemical product can be approximated as water • Cooling of the chemical product will be achieved by using treated city water • City water is available at 20 ⁰C • Exit temperature of city water from the heat exchanger is a function of the selected mass flow rate

  3. Design Optimization Goals: • Chemical must be cooled from 45⁰C to 25 ⁰C. • Length of heat exchanger must not exceed 7 meters. • Diameter of shell must not exceed 2 meters. • Minimize heat exchanger weight. • Minimize heat exchanger pressure drop.

  4. Initial Parameters: Funnel Effect • Shell Material • Shell Thickness • City Water Flow Rate • Counter or Parallel Flow • Shell ID • Baffles – Yes or No • Baffle Spacing • Tube OD • City Water Flow • Tube Length • Tube Thickness • Tube Layout & Angle • Tube Material • Tube Pitch • Shell Mass Flow Rate

  5. Main Effects Plot: Weight

  6. Main Effects Plot: ΔP Shell

  7. Main Effects Plot: ΔP Tube

  8. Main Effects Plot: Q Calculated

  9. Pareto Chart: Weight

  10. Standardized Effects: Weight

  11. Pareto Chart: ΔP Shell

  12. Pareto Chart: ΔP Tube

  13. Pareto Chart: Q Calculated

  14. Standardized Effects : Q Calculated

  15. Standardized Effects : Q Calculated

  16. Optimized Results: HE Pressure Drop ====================================== Shell Side Delta-P = 12330.12 Pa Shell Side Delta-P = 12.33 kPa Tube Side Delta-P = 2412.77 Pa Tube Side Delta-P = 2.41 kPa ====================================== Shell Side Pump Power = 0.31 kW Tube Side Pump Power = 0.11 kW Heat Exchanger Weight ====================================== Shell Weight = 96.79 kg Tube Weight = 887.29 kg Shell Fluid Weight = 1363.08 kg Tube Fluid Weight = 873.20 kg Total HE Weight = 3220.36 kg Heat Exchanger Inlet & Outlet Temperatures (Celsius) ========================================== Inlet Outlet Delta Bulk Wall Tube 45.00 25.00 20.00 35.00 30.55 Shell 20.00 32.22 -12.22 26.11 Overall Heat Transfer Coefficient ====================================== U (Tube Outside Area) = 815.25 W/m2.C Heat Transfer Rate ====================================== Desired Heat Transfer Rate = 5106263.80 W Calculated Heat Transfer Rate = 5105087.64 W Difference = 1176.16 W Desired-to-Calculated Ratio = 1.00

  17. Material Selection Reasoning: • Cost of Shell (96.79 kg = 213.385 lbs)… • Stainless Steal • 1.04/lb = $221.92 Total • Aluminum • .84/lb = $179.24 Total • Cost of Tubes (N = 8,142)… • Aluminum • $1,117,489.50$ • Stainless Steal • $1,384,615.20 Therefore, Aluminum was chosen for the tube material due to its low weight. In addition, Stainless steal was chosen as the shell material to provide a longer shell life.

  18. Referenced: • Toksoy, John. ME 414 Thermal-Fluid Systems Design. Department of Mechanical Engineering, IUPUI, Indianapolis, IN, Spring 2010. • OnlineMetals.com. (n.d.). Retrieved May 6, 2010, from htttp://www.onlinemetals.com/basket.cfm

  19. Questions ?