An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 5.1.6 Selecting Dispenser Transfer Hose(s), Hose End Valves, Hose Safety Devices, and Adapters Selection of proper dispenser transfer hoses, end valves and adapters relies on a thorough understanding of the functional requirements for the propane dispenser; that is, an analysis of the types of containers serviced by its operation. In this module you will learn to: • Select filling adapters based on the dispenser application (types of containers serviced) and hose-end valves to meet NFPA 58 code requirements • Apply NFPA 58 code requirements for selecting dispenser transfer hose(s)

  2. NFPA 58 2004 Courtesy Sherwood Products Selecting filling adapters based on the dispenser application (types of containers serviced) and hose-end valves to meet NFPA 58 code requirements 6.22.3.10 A listed quick-acting shutoff valve shall be installed at the discharge end of the transfer hose. Figure 1. Quick-Acting Hose-End Valve (Cylinder Filling)

  3. Figure 2. POL Filling Adapter Courtesy Engineered Controls International, Inc (REGO) Figure 3. Motor Fuel Cylinder Disconnect Coupling Filing Adapter Figure 4. Type-1 and OPD Filling Adapter

  4. Figure 5. Female POL to Hansen Quick Disconnect Valve Filling Adapter Figure 6. Female POL to Liquid Withdrawal Valve Filling Adapter

  5. Courtesy Fisher Controls Figure 7. 1¾-inch ACME Minimum Loss Hose-End Valve Courtesy Engineered Controls International, Inc (REGO)Figure 8. 1¾-inch ACME Minimum Loss Hose-End Valve

  6. NFPA 58 2004 Applying NFPA 58 code requirements to selecting dispenser transfer hose(s) and hose protection devices Vehicle fuel dispenser requirements 6.22.3.5 An excess-flow check valve or a differential back pressure valve shall be installed in or on the dispenser at the point at which the dispenser hose is connected to the liquid piping. 6.22.4.2 A listed emergency breakaway device complying with UL 567, Standard Pipe Connectors for Flammable and Combustible Liquids and LP-Gas, and designed to retain liquid on both sides of the breakaway point, or other devices affording equivalent protection approved by the authority having jurisdiction, shall be installed.

  7. Courtesy Clean Fueling Technologies Figure 9a. Dispenser Base Piping or Hose Emergency Breakaway

  8. Courtesy Engineered Controls International, Inc (REGO) Figure 9b. Dispenser Hose Emergency Breakaway

  9. NFPA 58 2004 5.8.6.4 Hose, hose connections, and flexible connectors used for conveying LP-Gas liquid or vapor at pressures in excess of 5 psig, and as provided in Section 6.17 regardless of the pressure, shall comply with 5.8.6.4(A) through 5.8.6.4(D). • Hose shall be designed for a working pressure of 350 psig with a safety factor of 5 to 1 and shall be continuously marked with LP-GAS, PROPANE, 350 PSI WORKING PRESSURE, and with the manufacturer’s name or trademark. • Hose assemblies, after the application of couplings, shall have a design capability of not less than 700 psig. • If a pressure test is performed, such assemblies shall be pressure tested at 120 percent of the maximum working pressure (350 psig minimum) of the hose. • Hose assemblies shall be leak tested at time of installation at not less than the operating pressure of the system in which they are installed.

  10. NFPA 58 2004 6.22.4.1 Hoses shall comply with the following: • Hose length shall not exceed 18 feet unless approved by the authority having jurisdiction. • All hoses shall be listed. • When not in use, hoses shall be secured to protect them from damage. 6.8.7.2 Flexible connectors and hose used as flexible connectors shall not exceed 36 inches in length where used with liquid or vapor piping on portable or stationary tanks. 6.11 Hydrostatic Relief Valve Installation. A hydrostatic relief valve or a device providing pressure-relieving protection shall be installed in each section of piping and hose in which liquid LP-Gas can be isolated between shutoff valves so as to relieve the pressure that could develop from the trapped liquid to a safe atmosphere or product-retaining section..

  11. Figure 10. Hydrostatic Relief Valve with Weather Cap Protecting Pipe and Connected Hose