The New SafEye Xenon 800 IR Open-Path Gas Detector. Open Path Gas Detection . Fast detection of a wide range of hydrocarbons Measures gas cloud concentration over many meters Proven, reliable gas detection technology . Applications. Indoor and outdoor installations for:
E N D
Open Path Gas Detection • Fast detection of a wide range of hydrocarbons • Measures gas cloud concentration over many meters • Proven, reliable gas detection technology
Applications Indoor and outdoor installations for: • Offshore oil & gas exploration and production • Fence line emission monitoring at industrial sites • Petrochemical storage areas • LNG/LPG storage, pumping, and filling • Pipelines • Paint booths and paint production • Bus terminals [natural gas powered vehicles]
LEL Meter Concept 1 LEL meter = a cloud of 5% methane (100% LEL) gas that is one meter across.
LEL Meter Concept 1 LEL meter = a cloud of 0.25% methane (5% LEL) gas that is twenty meters across.
New Features • Advanced Xenon Flash source • Improved operation with up to 90% signal reduction • Improved, low-profile stainless steel housings w/swivel mounts • Heated detector and source optics
New Features • Explosion-proof enclosure • Data port (I.S. approved) • Heated optics • Small (robust) footprint swivel mount
Swivel Mount Unit thumb screws for easy alignment mounting plate
Intrinsically Safe Hand-Held Kit General Purpose Hand-Held Kit carrying case shoulder strap intrinsically safe PDA PDA charger IR module general purpose PDA
New Features • 3mA: “maintenance call” – early warning of preventative maintenance • Programmable configuration and diagnostics via hand-held unit • 3 year system warranty, 10-year lamp warranty
Product Features • High sensitivity and fast response to hydrocarbon gases • Detection range up to 120 meters • Simple installation, alignment and functional check • One-person commissioning
Product Features Alignment Kit filter to check functionality telescope Allen wrenches
Product Features • Gases detected: simultaneous detection of flammable gases C1-C8 • Models available specifically for LPG, methane, natural gas and ethylene
Product Features • Dual-spectrum reference sensor, triple optics detector • Immune to industrial environments including solar radiation • Continuous operation in extreme environmental conditions • Operational integrity with up to 90% reduction in signal • No interconnecting cable between source and detector
Specification • Sensitivity Range: 0 - 5 LEL. m (optional 0-2 LEL. m) • Displacement/Misalignment tolerance to fault : 1 • Response time < 3 seconds • Temperature Range: -40 C to + 55º C
Specification • Warranty: 3 years for the complete system 10 years for Xenon Flash Lamp • Explosion proof:Class I, Div. I, Groups A-D, Class I, Div. 2, Groups A-D • Approvals: U.S., Canada, Europe, Australia • IP Rating:IP66 and IP67 • Environmental:meets MIL-STD-810C for humidity, salt, fog, vibration, mechanical shock, high/low temp
Electrical Specification • Power supply: 24 VDC nominal (18 - 32 VDC) • Power consumption: • Detector: 150mA @ 24 VDC • Source: 100mA @ 24 VDC(detector/source 300mA peak includes heated optics) • Electrical connection: 2 x M25 x 1.5mm or 2 x ¾“ – 14 NPT
4- 20 mA Output Signals • 4mA: Zero • 3mA: Maintenance call: early warning of preventative maintenance • 2mA: Obscuration/misalignment/beam block • 1mA: Zero calibration mode • 0mA: Fault
Maintenance Call Maintenance Call provides a 3mA output as a pre-warning maintenance signal. The SafEye Xenon 800 Detector continues to function in this mode. 3mA output indicates: • Low signal • Dirty window • Misalignment • Detector parameter at limit value
Communication Features • RS-485 Modbus RTU communication • Data communication with a host computer or universal controller • Central monitoring from a network of up to 247 addresses • Can network 32 SafEye 800 Detector units (without repeaters)
SafEye Xenon 800 Detector HAND-HELD DIAGNOSTIC KIT
Hand-Held Unit Features • A diagnostic/calibration/interrogation tool that allows one-person commissioning and maintenance • Intrinsically safe connection provides easy and economical interface • Quick and easy analysis of system status
Hand-Held Unit Features • On-site configuration of SafEye 800 Detector parameters • Verify detector parameters during installation • Recommended maintenance action to optimize the detector’s performance.
SafEye Xenon 800 DetectorHAND-HELD UNIT Detector operation: • Detector status • Change setup • Current gas reading • Detector serial number • Address (if networked) • Many other diagnostic features
SafEye Xenon 800 DetectorHAND-HELD UNIT • Detector setup: • Select one of 4 standard gas calibrations • Select full-scale range: 0-5 or 0-2 LEL.m • Select accessory relay activation at warning alarm level • Select alarm relay latching option • Detector address setting
SafEye Xenon 800 DetectorHAND-HELD UNIT • Detector maintenance: • Verify the detector installation range • Recommended corrective actions • Intensity of signal and gain • Signal-to-noise ratio • Signal-to-reference ratio • LEL. M reading using an IR filter
SafEye Xenon 800 DetectorHAND-HELD UNIT Specification • Intrinsically safe (general purpose version) certified: Class I, Div. I, Groups A-D • Extremely rugged: dust/waterproof rated to IP65
The New SafEye Xenon 800Open Path Gas Detection System The IR open-path detector for all environments & applications