2015 Update to OBC

2015 Update to OBC. September 17, 2014. 2014 Update package. Minor changes to the code: occupancy to occupancy Regulation to regulation Missing words Updated fees for BMEC submissions. Building Code Act. Issuance of permits

vicki
Download Presentation

2015 Update to OBC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 2015 Update to OBC September 17, 2014

  2. 2014 Update package Minor changes to the code: • occupancy to occupancy • Regulation to regulation • Missing words • Updated fees for BMEC submissions

  3. Building Code Act • Issuance of permits • 8. (2)  The chief building official shall issue a permit referred to in subsection (1) unless, • (b.1) the Architects Act or the Professional Engineers Act requires that the proposed construction of the building be designed by an architect or a professional engineer or a combination of both and the proposed construction is not so designed;

  4. Voice Communication • Housekeeping change to 3.2.4.23.(10) • (10)  The voice communication system required by Sentence (7) shall meet the silencing and transmission requirements of Sentences (3) to (5). • Previously referenced (6)

  5. January 1, 2015 • Multiple changes to the code with respect to increasing Accessibility • I have included only those that impact CFAA issues

  6. Referenced Documents • NFPA 72-2013 “National Fire Alarm and Signaling Code” added • Referenced to Smoke Alarms in 3.2.4.22.(13) and 9.10.19.1.

  7. 3.2.4.19.(4) Alert and Alarm Signals • Two new additions: • (4) … visual signal devices shall be installed in addition to audible signal devices, • (e) in a washroom for public use described in Sentence 3.8.2.3.(2), (3), (4) or (6), and • (f) in the living space in a suite of residential occupancy in a Group C major occupancy apartment building.

  8. 3.2.4.22.(13) Smoke Alarms • New sentence: • 13)Smoke alarms described in Sentence (1) shall have a visual signaling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, “National Fire Alarm and Signaling Code”.

  9. 3.8.1.5 Controls • Manual pull stations in a Barrier-Free path of travel: • Accessible by a person in a wheelchair • Operate with a closed fist, max 22.2.N force • Mounted a 1200 mm above finished floor • Note: Thermostats at 1200 mm and other building controls min 900 mm / max 1100mm

  10. 9.10.19.1 Smoke Alarms • New sentence: • 2)Smoke alarms described in Sentence (1) shall have a visual signaling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, “National Fire Alarm and Signaling Code”.

  11. Other Accessibility Changes • These items may not directly impact F/A systems • For information to clarify why you may see design changes

  12. Areas Requiring Access 3.8.2.1. • Old: • Entrance storey and all floor areas accessed by an elevator, escalator or lift • New: • Entrance storey and all floor areas accessed by an elevator, escalator or lift • All office and residential buildings exceeding 3 storeys OR 600 m2

  13. Rooftop Amenity Space • External rooftop spaces are common amenity areas on new buildings. • These must be made accessible. • Rooftop spaces for building services are not included.

  14. Residential Suites 3.8.2.1. • Old • 10% of units to BF requirements • Can be located anywhere in the building • New • 15% of units to BF requirements • Proportioned to 1, 2 and 3+ bedrooms • Distributed among storeys

  15. Washrooms 3.8.2.3. • Old • BF washrooms OR stalls, only 1/floor • New • # BF washrooms based on height of building • # BF stalls as a ration of the # WC

  16. Hotels 3.8.2.4. • 10% of suites to be BF (existing) • Controls and safety devices in the suite to 3.8.1.5. (new) • Suite entrances doors to BF suites have power door operators (new)

  17. Hotels 3.8.2.4. • If the hotel has a generator for emergency power • Minimum 1 receptacle to be supplied with emergency power • The receptacle to be signed EMERGENCY POWER OUTLET

  18. Doors 3.8.3.3. • Principle entrance doors to buildings to have power door operators. • If a Vestibule occurs, both doors require power door operators • Exception for Detention occupancies and Industrial Occupancies (Previously more exceptions)

  19. Doors 3.8.3.3. • Power door operators required on: • BF washrooms • Assembly occupancies within residential buildings • Where proximity scanners are used, they must detect a person in a wheelchair

  20. 3.8.3.12 Universal Washroom • An emergency call system with audible and visual signal devices inside the Barrier-Free washroom • Must be different from the building fire alarm (both visual and audible)

  21. -

  22. -

  23. Sliding Door

  24. Doors in series

  25. Washroom Stalls

  26. Ambulatory Washroom

  27. Universal Washroom

  28. Grab Bars

  29. Accessible Urinal

  30. Fire Code Changes • Amendments to the Fire Code Retrofit requirements will also have impact on your work.

  31. Permit Requirements Fire Alarm Systems

  32. Scope of Work • Maintenance – No Permit Required • Repair – Permit Required • Upgrade – Permit Required • Replace – Permit Required • Emergency Repairs – Permit required as above

  33. Maintenance – No Permit • To keep the system functioning to original design and installation standards • Replacement of defective components with compatible components • Defective control panels may be replaced only if the exact replacement panel is available

  34. Repair - Permit • Substantial replacement of equipment that will improve the fire alarm performance • Replacement of older panels that are no longer available • New panels to accommodate newer technology

  35. Repair - Permit • Panel from a different manufacturer • New components that incorporate newer technology • Installation to CAN/ULC-S524 and Verification to CAN/ULC-S537 • Professional involvement is necessary where required by the OBC or PEO

  36. Upgrade - Permit • Involves changes to the design of the original system • Upgrading may be voluntary by the owner • Upgrading may be as a result of a Fire Code order • May include the addition of new devices, components, panels, zones

  37. Upgrade - Permit • May include upgrades necessary for compliance with barrier-free accessibility requirements • Installation to CAN/ULC-S524 and Verification to CAN/ULC-S537 • Professional involvement is necessary where required by the OBC or PEO

  38. Replace - Permit • The complete replacement of a fire alarm system • Replacement of a substantial portion of the system • Replacement may be voluntary, as a result of a building renovation program or as a result of a Fire Code order

  39. Replace - Permit • Installation to CAN/ULC-S524 and Verification to CAN/ULC-S537 • Professional involvement is necessary where required by the OBC or PEO

  40. Emergency Repairs • Fire alarm systems in occupied buildings that cease to be operational must be repaired immediately. • If the scope of work falls under Repair, Upgrade or Replace from above, a permit should be obtained and after the work is completed.

  41. Emergency Repairs • Installation to CAN/ULC-S524 and Verification to CAN/ULC-S537 • Professional involvement is necessary where required by the OBC or PEO • Note: Is notification to the Fire Department required or recommended?