130 likes | 586 Views
SIMATIC ET 200M Systemredundancy. R edundancy with PROFINET. Ring struktur with standard-CPU (MRP). Standard-CPU (IO Controller). DP/ MPI. DP. PN. Sync. PN. PN. Sync. ET 200M. ET 200M. ET 200M. ET 200M. ET 200M. ET 200M. IM153-4 PN IO Standard. Possible Configurations.
E N D
Redundancy with PROFINET Ring struktur with standard-CPU (MRP) Standard-CPU (IO Controller) DP/MPI DP PN Sync PN PN Sync ET 200M ET 200M ET 200M ET 200M ET 200M ET 200M IM153-4 PN IO Standard Possible Configurations System redundancy with S7-400H S7-400H DP/MPI DP/MPI DP DP PN PN Sync Sync PN PN PN Sync Sync IM 153-4 PN IO High Feature
Redundancy with PROFINET Control of possible errors 3 1 1 2 2 Wire break of the ring Power off / failure of a single station CPU failure Switch over time appr. 30ms autom. synchronisation at CPU change Wire break of the ring Power off / failure of a single station Switch over time appr. 200ms
High-available automation system SIMATIC S7-400H with PROFINET I/O System Redundancy (SR) Goals Automatic switchover in the event of a fault • Event-controlled synchronization of both stations makes for fast and bumpless switchover • Redundant CPU picks up processing at the interruption point without loss of information and alarms. • All components can be replaced during running operation (hot swapping). • When replacing a CPU, it is automatically loaded with the latest programs and data. Overview Innovations Redundant Periphery Periphery Open ring architecture § Overview § PROFINET I/O SR-Support through H-CPUs and ET 200M Sync wiring § PROFIBUS I/O Data synchronization High-available communication Guarantee of functionality in the case of an error in a CPU or a ring node or a bus error CPU 41x-5H CPU 41x-5H Failure of an IO device (ET 200M) is limited to the damaged ring node Safety & High availibility Switch Switch Switch PROFINET Cable break between two devices does not affect functionality of the system Applications Failure of a CPU does not affect functionalityof the redundant system References Automatic synchronization after replacement of faulty component ET 200M ET 200M ET 200M E 200M