1 / 5

SIMATIC ET 200M Systemredundancy

SIMATIC ET 200M Systemredundancy. R edundancy with PROFINET. Ring struktur with standard-CPU (MRP). Standard-CPU (IO Controller). DP/ MPI. DP. PN. Sync. PN. PN. Sync. ET 200M. ET 200M. ET 200M. ET 200M. ET 200M. ET 200M. IM153-4 PN IO Standard. Possible Configurations.

vivien
Download Presentation

SIMATIC ET 200M Systemredundancy

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SIMATIC ET 200MSystemredundancy

  2. Redundancy with PROFINET Ring struktur with standard-CPU (MRP) Standard-CPU (IO Controller) DP/MPI DP PN Sync PN PN Sync ET 200M ET 200M ET 200M ET 200M ET 200M ET 200M IM153-4 PN IO Standard Possible Configurations System redundancy with S7-400H S7-400H DP/MPI DP/MPI DP DP PN PN Sync Sync PN PN PN Sync Sync IM 153-4 PN IO High Feature

  3. Redundancy with PROFINET Control of possible errors 3 1 1 2 2 Wire break of the ring Power off / failure of a single station CPU failure Switch over time appr. 30ms  autom. synchronisation at CPU change Wire break of the ring Power off / failure of a single station Switch over time appr. 200ms

  4. High-available automation system SIMATIC S7-400H with PROFINET I/O System Redundancy (SR) Goals Automatic switchover in the event of a fault • Event-controlled synchronization of both stations makes for fast and bumpless switchover • Redundant CPU picks up processing at the interruption point without loss of information and alarms. • All components can be replaced during running operation (hot swapping). • When replacing a CPU, it is automatically loaded with the latest programs and data. Overview Innovations Redundant Periphery Periphery Open ring architecture § Overview § PROFINET I/O SR-Support through H-CPUs and ET 200M Sync wiring § PROFIBUS I/O Data synchronization High-available communication Guarantee of functionality in the case of an error in a CPU or a ring node or a bus error CPU 41x-5H CPU 41x-5H Failure of an IO device (ET 200M) is limited to the damaged ring node Safety & High availibility Switch Switch Switch PROFINET Cable break between two devices does not affect functionality of the system Applications Failure of a CPU does not affect functionalityof the redundant system References Automatic synchronization after replacement of faulty component ET 200M ET 200M ET 200M E 200M

  5. SIMATIC ET 200M