1 / 18

Chapter 4

Wiring Enclosures & Support (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004). Chapter 4. Protection of cables against Electromechanical & Mechanical Stresses.

yagil
Download Presentation

Chapter 4

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Wiring Enclosures & Support(Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004) Chapter 4 Electrical Installation II

  2. Protection of cables against Electromechanical & Mechanical Stresses • Electromechanical forces may be caused by fault currents • Mechanical forces may be caused by accidental drilling of holes on a wall, the conduits own weight, etc. Electrical Installation II

  3. Conduits • Rigid Steel Conduits • Excellent mechanical protection • Good protection against fire • Can be used as circuit protective conductor (cpc) • Resistant to ultra-violet radiation from sunlight • BS4568-1 classifies conduits by: • Light gauge and heavy gauge (CoP permits only heavy gauge conduits) • Classes 1, 2, 3 & 4 Electrical Installation II

  4. Conduits • Rigid Insulating Conduits / PVC conduits • Ambient temperature is a major consideration • Overall cost saving • Separate circuit protective conductor must be used • Weight reduction compared with steel conduits Electrical Installation II

  5. Conduits • Flexible Conduit (Metallic / PVC) • Used in applications involving constant movement, e.g. connection to a pump • Separate circuit protective conductor must be used • Where exposed to damp situation, it should have metallic pattern with PVC oversheath and IP rating not less than IP54 (Table 4.16) Electrical Installation II

  6. Conduit • Supports: • Horizontally surface-mounted • Vertically surface-mounted • For rigid steel conduit, refer to Table 4.5 • For rigid insulating conduit, refer to Table 4.7 Electrical Installation II

  7. Conduit • Cable capacity - Selection principle: Conduit Factor ≥ ∑ (Cable Factors) • Refer to Tables 4.1 to 4.4 • Solid and stranded cables • Short run (3m and no bend) and long run (>3m or with bends) • Adaptable boxes to be installed at least every 10m straight run. • Example: • How many 2.5 mm2 1-C PVC cables can be accommodated in a 20 mm conduit 10m long incorporating 2 bends? Electrical Installation II

  8. Conduit • Solution: From Table 4.4, conduit factor for a 20mm conduit, 10m long incorporating 2 bends is 141. Let the max. no. of cables that can be drawn in be x, and from Table 4.3, cable factor for 2.5mm2 1/C PVC cable is 30, then 30x ≤ 141  x ≤ 4.7 Therefore, we select x = 4 Electrical Installation II

  9. Trunkings • Construction • Steel trunking (screw-on-lid) Electrical Installation II

  10. Trunkings • PVC (or insulating) trunking (clip-on-lid) Electrical Installation II

  11. Trunkings • There are other trunking systems also of PVC steel construction, e.g. 2- and 3- compartment trunkings (telephone and / or data + power):- • Raised floor trunkings (flush with raised floor panels) • Underfloor trunkings (flush with floor screed) • Skirting trunkings Electrical Installation II

  12. Trunkings • Classification • The higher the Class, the better the mechanical protection, e.g. Class 3 steel trunking  heavy protection on both inside and outside of trunking Electrical Installation II

  13. Trunkings • Can Be Used as Circuit Protective Conductor (cpc) • Steel trunkings may be used as cpc, whereas for PVC trunkings, separate cpc must be used. Electrical Installation II

  14. Trunkings • Bends and supports • Support requirements for steel trunking and insulating trunking refer to Tables 4.13 and 4.15 Electrical Installation II

  15. Trunkings • Cable Capacity - Selection principle: Trunking Factor ≥ ∑ (Cable Factors) • Refer to Tables 4.10, 4.11 and4.12 • For sizes and types of cable and sizes of trunking other than those given in the table, the no. of cables drawn into a trunking should be ≤ 45% • Space factor is the percentage occupancy of space inside the trunking • Example • What is the max. number of 10 mm2 1-C PVC cables that can be accommodated in a 100mm x 50mm trunking?What if a space factor of 0.45 is applied? Electrical Installation II

  16. Cable Supports • Cable Clips • For surface-mounted PVC-insulated PVC-sheathed non-armoured cables  10 mm.sq. Electrical Installation II

  17. Cable Supports • Cable Cleats / Saddles • As above but for > 10 mm.sq. cables and all armoured cables. Electrical Installation II

  18. Cable Supports • Cable Trays and Ladders • Suitable for almost any mounting method but for heavier cables than those accommodated in a trunking. • The mechanical strength of cable ladders is better than cable trays. Electrical Installation II

More Related