An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EN 54-16 Compliant Installation of Voice Alarm Systems

  2. When does EN54-16 Apply? • Construction Products Directive CPD CPD: EN54 is mandatory for fire detection and alarm systems in all EU member states • 2008: issue of two new parts of EN54 • Part 16: voice alarm systems • End of co-existence period*: March 2011 • Part 24: loudspeakers for voice alarm systems • End of co-existence period*: April 2011 * End of co-existence period: conflicting national standards must be withdrawn

  3. When does EN54-16 Apply? • System depending • EN 54-16 must be applied • When the voice alarm system is controlled by the fire detection system • Application not necessary • When the voice alarm system is a stand-alone system (triggered manually) or • controlled by others that fire detection systems • When must voice alarm be applied? • National requirements

  4. Approved VA Systems • Certification • The voice alarm system must be certified on EN54-16 by a notified body • Notified bodies can be found on the EU Web sites • Certificate of the notified body contains • Certificate number • Approved system components • Approved options

  5. Approved VA Systems • Indication of Approval • Certificate number • at least on one main part of the VA system • in the accompanied documents • Applicable options • in the accompanied documents

  6. EN 54-16 Compliant Design Access Levels Mandatory Function Mandatory Indications

  7. Access Levels • Access Level 1 • Public areas or • Areas with unrestricted access for persons having a general responsibility for safety supervision • E.g. in a technical room • Manual controls shall be accessible without special procedures • E.g. not by opening a door

  8. Access Levels • Access Level 2 • Access restricted by special procedures • Access by • mechanical key (locked technical room) • code of at least 3 sequential operations • access cards • Access for Persons • with specific responsibility for safety and • Authorised and trained on operating

  9. Mandatory Indications • Must be in Access Level 1 always • VA condition, especially EMERGENCY • Indication on a remote microphone by programmed fault receipt (acknowledge) button (SX: on SM) • General Fault • Indication on a remote microphone by programmed fault receipt (acknowledge) button (SX: on SM) • System Fault • Indication on a remote microphone by programmed fault receipt (acknowledge) button (SX: on SM)

  10. Mandatory Indications • Must be in Access Level 1 always • Fuse Rupture • Indication on a remote microphone by programmed fault receipt (acknowledge) button for all amps • Fault in Signal Path between System components • Only for SX-2000: indication by programmed fault receipt (acknowledge) button • Earth Leakage • For outgoing wires (e.g. speaker lines, microphones) • Only necessary if not implemented in other fault

  11. Mandatory Functions • Must be in Access Level 1 always • Lamp Test (Button) • To test the mandatory indications • Fault Acknowledge (Button) • In TOA VA systems always combined with fault indications

  12. Options • Mandatory Indications • Faults in VA Zones • One fault indicator per VA zone • Fault in the connection to the fire detection system • A separate indicator must be provided

  13. Options • Access Level • Manual Silencing 2 • Manual Reset of the VA condition 2 • VA condition output n.a. • VA manual control 2 • Emergency microphones 2 • Redundant power amplifiers n.a. • Audible warning of VA condition 1, 2 • VA manual control 2 • Phased evacuation 2

  14. Options • Available on TOA VA Systems • Manual Silencing SX, VX • Button on emergency microphone • VX: acivating dummy text (silence) • SX: stopping emergency pattern or sequence • Manual Reset of the VA condition SX, VX, VM • Emergency reset button • VA condition output SX, VX, VM • Control output • VA manual control SX, VX, VM • Manual assignment of emergency messages to emergency zones

  15. Options • Available on TOA VA Systems • Emergency microphones VX, VX, VM • Fireman microphone, emergency microphone (VX, SX) • Redundant power amplifiers SX, VX, VM • Standby amplifiers • Audible warning of VA condition VM • Buzzer tone when emergency was activated • Phased evacuation SX • When phases can be controlled manually or by fire detection system