1 / 21

NFPA-12 Edition 2005

What “IMPACT” will the changes to NFPA-12 have on the design and installation of a CO 2 system?. NFPA-12 Edition 2005. NFPA-12 Edition 2005. Reasons for changes Continuing effort to improve/enhance product features and system designs for “life safety” on both: Existing Installations

Audrey
Download Presentation

NFPA-12 Edition 2005

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. What “IMPACT” will the changes to NFPA-12 have on the design and installation of a CO2 system? NFPA-12 Edition 2005

  2. NFPA-12 Edition 2005 • Reasons for changes Continuing effort to improve/enhance product features and system designs for “life safety” on both: • Existing Installations • New Systems

  3. NFPA-12 Edition 2005 • Who does this affect? • Manufacturers • Designers • Installers • Service • End-users/Owners

  4. NFPA-12 Edition 2005 • Application /systems affected: • Total Flood CO2 systems applied to Normally Occupied Spaces • Total Flood CO2 systems applied to Occupiable Spaces • Local Application Systems

  5. Definitions per NFPA-12 Edition 2005 • 3.2.4 Normally Occupied Area. An area or space where, under normal circumstances, persons are present. • 3.2.5 Normally Unoccupied Area (occupiable). An area or space not normally occupied by people but could be entered occasionally be brief periods. • 3.2.8 Unoccupiable Area. An area or space which cannot be occupied due to dimensional or other physical constraints.

  6. Existing Systems 1.3.1 Retroactivity. All (NO, Occupiable., Local if exposing personnel) existing systems shall be upgraded to meet the requirements for . . . • Safety signs in paragraph 4.2.2 • Lockout valves in paragraph 4.2.3.6 & 4.2.3.6.1 • Pneumatic time delays & pre-discharge alarms in paragraph 4.4.5.7 1.3.2 These upgrades shall be completed by June, 2006

  7. Safety Signs 4.2.2.1 Warning signs should be affixed in a conspicuous location . . . • In every protected space • At every entrance to protected spaces • In spaces near the protected spaces where it is determined carbon dioxide could migrate creating a hazard to personnel . . .

  8. Safety Signs The safety sign • Format • Color • letter style of signal words • message panel letting • lettering size • safety symbols shall be in accordance with ANSI Z535.

  9. WARNING Carbon dioxide gas discharge into nearby space can collect here. When alarm operates vacate immediately. Carbon dioxide gas may cause injury or death.

  10. Personnel Safety – NFPA 12 continued… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES VACATEIMMEDIATELY Typical Warning signs shall be affixed in conspicuous locations:

  11. Typical Warning signs… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES DO NOT ENTER UNTIL VENTILATED

  12. Typical Warning signs… WARNING CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH WHEN ALARM OPERATES OR WINTERGREEN SCENT IS DETECTED, DO NOT ENTER UNTIL VENTILATED

  13. Typical Warning signs… CAUTION CARBON DIOXIDE GAS DISCHARGE INTO NEARBY SPACE CAN COLLECT HERE. WHEN ALARM OPERATES VACATE IMMEDIATELY. CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH

  14. Typical Warning signs… CAUTION CARBON DIOXIDE GAS MAY CAUSE INJURY OR DEATH VENTILATE THIS AREA BEFORE ENTERING. A HIGH CARBON DIOXIDE GAS CONCENTRATION CAN OCCUR IN THIS AREA AND CAUSE SUFFOCATION

  15. Typical Warning signs… WARNING ACTUATION OF THIS DEVICE WILL CAUSE CARBON DIOXIDE TO DISCHARGE. BEFORE ACTUATING, BE SURE PERSONNEL ARE CLEAR OF AREA

  16. Safety Signs Exception: Existing installations where facilities have written caution / warning sign procedures in place to provide: • information and directions to personnel • have a training programs established to educate personnel about signage then said sign procedures can be used in place of ANSI Z535.

  17. Stop/Maintenance (“lock-out”) Valve NFPA 12 Paragraph 1-6.1.7 To prevent accidental or deliberate discharge, a “lockout” shall be provided when persons not familiar with the systems and their operation are present in a protected space. NFPA 12 Paragraph 1-8.4 Supervision of automatic systems and manual lock-out valves shall be provided unless specifically waived by the A.H.J. Items Required to Comply with NFPA 12 Edition 2000 No Lockout With Lockout

  18. Changes Required to Comply with NFPA 12 Edition 2005 Typ. Arrangement w/ Mech Time Delay & Siren

  19. New Systems 4.1.3 Carbon dioxide total flood extinguishing systems shall not be used in normally occupied enclosures if other fire extinguishing agents can be used to provide an equivalent level of fire protection to carbon dioxide. When CO2 is determined to be the most suitable agent of choice the designer / installershall provide documentation . . . to verify that CO2 is the most suitable fire suppression agent available.

  20. Examples where CO2 should not be used • Control Rooms • Computer Rooms • Data Centers • IT Equipment Rooms / Centers • Telecommunication Rooms • Laboratory Rooms • Libraries • Museums

  21. NFPA 12: Marine Systems • 2 separate valves shall be provided for releasing CO2 into any protected space. 1 valve shall control discharge from the CO2 storage. The 2nd valve shall control CO2 discharge into the protected space(s). • A separate manually operated control shall be provided to operate each valve… A set of controls shall be located outside at least one of the main means of egress from each protected space. • Audible predischarge alarms and a minimum 20 second time delay shall be provided that depend on no source of power other than CO2.

More Related