1. Product Introduction9390 40-160 kVA
2. Eaton 9390 Presentation Index Snapshot
Specifications
Design & Characteristics
Paralleling
Battery solutions
Eaton Technologies
HotSync
ABM
ESS
Efficiency
Accesories
4. Eaton 9390 40-160kVA Rating: 40; 60;80;100;120; 160kVA
Input: 3ph; 380/400/415V Nominal; 50/60Hz
Output: 3ph; 380/400/415V; 50/60hz
Connectivity: Wide options with X-slots
High power performance:
Efficiency 94% at nominal load
Output power factor 0.9
Input ITHD < 5%
Graphical LCD
Technology
PWM controlled IGBT technology
Transformerless
State-of-art design
Compact, lightweight, space-saving
Can operate as frequency converter
Can operate as power conditioner (no battery)
Combine this slide with #5Combine this slide with #5
5. Eaton 9390 40-160kVA 9390 range
40 kVA
60 kVA
80 kVA
100 kVA
120 kVA
160 kVA
6. EATON 9390 40-160kVA 40; 60; 80kVA 380/400/415V 100; 120; 160kVA 380/400/415V
7. Serviceability 100% Front Access
Unit can be backed up against wall or into a corner
Mean time to repair (MTTR) less than 30 minutes (worldwide)
Power modules are field replaceable units
Fan tray is a field replaceable unit
Power module component repair in remote countries
Mean time before failure (MTBF) calculated to be:
>150 thousand hours in RT mode w/bypass
Comprehensive service plans
9. 9390 Input Specification No. of phases: 3 phases + Neutral
Rectifier rated input voltage:
380 /400 / 440 VAC Nominal
Tolerance
+10 -15% at 100% nominal load (zero battery discharge at low end)
-30%... +20% of nominal maximum input voltage window
Frq: 45-65Hz; 50 or 60Hz ą3Hz (nominal)
Bypass input voltage
380 /400 / 440 VAC Nominal -15%... +10%
Input power factor: 0.99
Input current THD: 3-5%
Lets work on this slide Better way to show it!! Elina did it in a rush.. Without thinking it.. Too much.. Lets work on this slide Better way to show it!! Elina did it in a rush.. Without thinking it.. Too much..
10. 9390 Output Specification No. of phases: 3 phases (+Neutral)
inverter rated output voltage
220; 230; 240VAC ą3VRMS
Rated output frq: 50 or 60Hz (configurable)
Variation: ą3Hz (default); configurable!
Slew rate: 1Hz/s (default); configurable!
Voltage THD <3% (linear load); 5% reference non-linear load
Crest factor: 3
Nominal power factor 0.9
Range: 0.7 lagging
0.9 leading
Short circuit capability (@inverter):
240A 300ms (80kVA) / 480A 300ms (160kVA)
11. 9390 DC Circuit Specification Typical DC-link Voltage 620VDC
Battery Specification:
40 Block VRLA 12V batteries per string
Maximum total battery voltage 569VDC
Battery cut-off voltage 1.75/1.67VPC
Typical runtimes with 0.8 output PF
13. Design Characteristics
14. Typical System Main Circuit: 9390 80kVA w MBS
15. EATON 9390 Dimensions
16. EATON 9390 Mechanical Design Transformerless design :
Compact, lightweight, space-saving
Front to top cooling
Cool air is draw in via the front door, warm air is exhausted out the top of the unit
Fan tray assembly blows cool intake air up through the power modules
17. Cabling EATON 9390 40-80kVA
18. Cabling EATON 9390 120-160kVA
19. Reliable Upgradability through Eaton Paralleling Technologies - HotSyncŽ EATON HotSyncŽ
Paralleling Technology
Enables synchronization without communication line between the UPS
Eliminates single point of failure Work in this one!Work in this one!
20. HotSyncŽ Paralleling Technology EATON Powerware Hot SyncŽ - Increasing Availability
Accurate parallel UPS load share without communication
Available to Powerware 3-ph UPS at power range 8kVA ?
21. 9390 Battery Solutions Powerful battery converter technology allows flexible extent runtimes without need for external chargers
External battery cabinet solutions
Line and match!!
Battery Specification:
40 Block VRLA 12V batteries per string
Maximum total battery voltage 569VDC
Battery cut-off voltage 1.75/1.67VPC
ReWork.. Main message: our desing is highly configurableReWork.. Main message: our desing is highly configurable
22. Battery Management Advanced Battery Management
Advanced charging algorithms to significantly extend battery life compared to traditional charging method
Automatic and periodic self tests for battery circuitry
Temperature compensated charging available (option)
Explain more the second bullet point!!Explain more the second bullet point!!
23. User Interface Add in more detail with is displayed. E.g., metering, event history log, add the # of languages we have.Add in more detail with is displayed. E.g., metering, event history log, add the # of languages we have.
24. User Access and Communications
25. User Access and Communication
27. 9390 Accessories External battery cabinets and rack systems
System parallel modules (SPM)
Sync Control
External (manual) bypass switches
Software and communications options
28. External Battery Cabinet (Large)
29. EBC Dimensions
30. Battery breaker box (
250 A )
31. SPM Cabinet 4* 40-80 kVA 1023540 SPM9390-80-4
32. Tie Cabinet 3* 100-120 & 3* 160 kVA 1024506 9390 Tie Cabinet 3x160 kVA
1024687 9390 Tie Cabinet 3x120 kVA
33. SyncControl 100-160 kVA 1024635 Powerware 9390-100-U-4X1 (Sync Control SUPPORT)
1024636 Powerware 9390-120-N-4X1 (Sync Control SUPPORT)
1023298 Powerware 9390-120-U-4X1 (Sync Control SUPPORT)
1023299 Powerware 9390-160-N-4X1 (Sync Control SUPPORT)
34. Distribution systems: IT International standard IEC 60364:
I : no point is connected with earth (isolation), except perhaps via a high impedance.
T : direct connection with earth, independent of any other earth connection in the supply system
In Europe:
400 Volts 50 Hz
380 Volts 50 Hz
415 Volts 50 Hz
35. 9390 40-160 kVA IT -model