0 likes | 8 Views
Success Report Energy Saving FRP Fan for Shinwa Cooling Tower PTSC
E N D
SUCCESS REPORT Fan Diameter Size 2100 mm. Energy Saving FRP Fan for Shinwa Cooling Tower
AGENDA Background Before Changing Background Before Changing Energy Saving Fan Specification Energy Saving Fan Specification Process (Removing The Old Fan) Process (Removing The Old Fan) Process (Installing New Energy Saving Fan) Process (Installing New Energy Saving Fan) Testing Testing Results Results Project Reference Project Reference 1. 1. 2. 2. 3. 3. 4. 4. 5. 5. 6. 6. 7. 7. Sample Footer Text Sample Footer Text 2
BACKGROUND BEFORE CHANGING Fan Material : Aluminum Alloy Cast Boss Material : Aluminum Alloy Cast Cooling Tower Model : SNC-U 320BSSD Place (Site) : AJ Plast Fan Motor Size : 7.5 kW. Electrical System : 380 V/ 3Phases / 50Hz Fan Detail : 4 Blades and Diameter 2100 mm. Customer Target : Reduce Electrical System at least 15% • • • • • • • • Energy Saving FRP Fan for Shinwa Cooling Tower 3
ENERGY SAVING FAN SPECIFICATION Fan Material : FRP. Boss Material : Aluminum Cast Cooling Tower Model : SNC-U 320BSSD Place (Site) : AJ Plast Fan Motor Size : 7.5 kW. Electrical System : 380 V/ 3Phases / 50Hz Fan Detail : 6 Blades and Diameter 2100 mm. • • • • • • • Energy Saving FRP Fan for Shinwa Cooling Tower
PROCESS (REMOVING THE OLD FAN) Energy Saving FRP Fan for Shinwa Cooling Tower 5
TESTING Energy Saving FRP Fan for Shinwa Cooling Tower Sample Footer Text Sample Footer Text 7
TESTING STAFF นายเจตนาจิตรา วิศวกร นายแสงสุรีวงค์โม้ หัวหน้าช่างเทคนิค นายวัลลภจันทร ช่างเทคนิค นายวิโชติวิจิตรวงษ์ ช่างเทคนิค Sample Footer Text Sample Footer Text 8
TEST RESULTS Result Before After R (A.) 13.83 7.10 S (A) 14.57 8.00 T (A) 12.93 7.68
TEST RESULT (BEFORE) (AFTER) Energy Saving FRP Fan for Shinwa Cooling Tower
TEST RESULT Target Reduce Electric Current Reduce Electric Current at least 15% at least 15% Real Result Reduce Electric Current Reduce Electric Current at least at least 30 30 - - 40 40% % Energy Saving FRP Fan for Shinwa Cooling Tower 11
PROJECT REFERENCE - AJ Plast - Thai Glico - Suzuki Motor - Elleair International Energy Saving FRP Fan for Shinwa Cooling Tower 12
Energy Saving FRP Fan for Shinwa Cooling Tower THANK YOU PRECISION TOOLING SERVICE CO., LTD. PRECISION TOOLING SERVICE CO., LTD. Email : info@ptsc.co.th www.ptsc.co.th 13