1 / 15

COMBINED NATURAL GAS POWER PLANT

COMBINED NATURAL GAS POWER PLANT. POWER PLANT LAYOUT. OFFERING TO SELL ;. - 6 ALSTOM Power Plant U.K. construction TYPHOON model gas turbines ( 5.08 MW ) - 1 ALSTOM Power s.r.o. construction ST3- C.V56 steam turbine ( Nom ; 15.25 MW , Max: 16.3 MW )

albina
Download Presentation

COMBINED NATURAL GAS POWER PLANT

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. COMBINED NATURAL GAS POWER PLANT

  2. POWER PLANT LAYOUT

  3. OFFERING TO SELL ; - 6 ALSTOM Power Plant U.K. construction TYPHOON model gas turbines ( 5.08 MW ) - 1 ALSTOM Power s.r.o. construction ST3- C.V56 steam turbine ( Nom ; 15.25 MW , Max: 16.3 MW ) - Build in 2003 and has been active since - Maintenance of the turbines are carried out by Siemens - 2 Boilers (heat recover steam generators) - 7 ALSTOM power transformers - Two bus-bar systems (34,5 kV) - Air filtering system for effective performance in polluted enviroments - The facility works with 43% efficency and has a total capacity of 45 MWh.

  4. GAS TURBINES (6)

  5. Technical Data of the Turbines (6) • SGT-100-1S single-shaft turbine for Power Generation • Power output 5.25 MW(e) • Fuel: Natural gas / liquid fuel / dual fuel and other fuels capability on request • Automatic changeover from primary to secondary fuel at any load • Frequency: 50/60Hz • Electrical efficiency: 30.5% • Heat rate: 11,815kJ/kW-hr (11,199Btu/kW-hr) • Turbine speed: 17,384rpm • Compressor pressure ratio: 14.6:1

  6. STEAM TURBINE (1)

  7. Technical Data of the Steam Turbine (1)TURBINE : ALSTOM Brno/ Czech RepuplicTYPE : ST3-C , V56A ATP2 (Condensing)TURBOSE OUTPUT: (at generator terminals )Rated:15,25 MWmaximal:16,3 MWSpeeds :5952 rpmLive steamPressure : 45 BarTemperature: 440 C Flow : 52,2 t/hLP admissio steamPressure : 6 BarTemperature :243 C Flow :12,6 t/h

  8. Heat Recover Steam Generators/Boilers (2)

  9. TECHNICAL DATA FOR BOILERS

  10. TRANSFORMERS - To increase the output voltages of generators from 11 kV to 34.5 kV, 7 ALSTOM power transformers are used. - Gas turbine's power transformers are 11 / 34.5 kV and 6550 kVA the - The steam turbine transformer is 11/34.5kV and 20,400 kVA power. - In addition, for internal need we have 4 transformers. 2 of them are 0.4 kV / 1000 KVA, the other 2 are 0.4 kV / 1600 KVA power.

  11. COOLING TOWERS

  12. AIR FILTERING SYSTEM

  13. LIQUID FUEL SYSTEM Gas turbines and natural gas alternative-fuel units, can operate with diesel and naphtha fuels. Fuel transitions can take place without interruption. If there is a drop in gas pressure, the liquid fuel passage is provided automatically.

  14. PROCESS FLOW OF THE POWER PLANT

  15. TURBINES WORKING AND MAINTANENCE SCHEDULE Total working hours: Working hours of all systems related to turbinesNet working hours : Working hours of turbines onlyB-type maintenance: Extensive maintenance of all systems related to turbinesA-type maintenance: Second degree maintenance of all systems related to turbines

More Related