Substitution of VZ1L00xxx chokes. These are 1 phase chokes : VZ1L004M010 (10mH, 4A) VZ1L007UM50 (5mH, 7A) VZ1L018UM20 (2mH, 18A) It is possible to use 3 phases chokes below : VW3 A4 551 instead of the VZ1L004M010. VW3 A4 552 instead of the VZ1L007UM50.*
E N D
Substitution of VZ1L00xxx chokes These are 1 phase chokes : VZ1L004M010 (10mH, 4A) VZ1L007UM50 (5mH, 7A) VZ1L018UM20 (2mH, 18A) It is possible to use 3 phases chokes below : VW3 A4 551 instead of the VZ1L004M010. VW3 A4 552 instead of the VZ1L007UM50.* VW3 A4 553 instead of the VZ1L018UM20.* Customer will use only one phase of these chokes as define in diagram on next page. Rq : Like only one coil will be used we will have voltage on the 2 other coils (they will work as a transformer). We will have voltage on the unused coil equal to the voltage drop on the input coils (3 to 5% of the drive voltage supply). (*) Check remark on next page
S3 E3 S2 E2 VW3A455x S1 E1 Drive AC supply Supply Connexion for the VW3A455x used as VZ1L0xxx WARNING : E2, S2, E3, S3 of VW3A455x must not be connected Remark about VW4 A3 552 & VW4 A3 553 Like we have less inductance, we will have more input line current (~5%).