1 / 10

PID Temperature Controller

PID Temperature Controller. Allen Bradley 1771-TCM Brian Van Eyk. Background. Applications Plastic injection molding Powder paint There is a need for quick and accurate temperature control Two solutions Sensor with simple logic controller Smart I/O controller. Allen Bradley 1771-TCM.

arlen
Download Presentation

PID Temperature Controller

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PID Temperature Controller Allen Bradley 1771-TCM Brian Van Eyk

  2. Background • Applications • Plastic injection molding • Powder paint • There is a need for quick and accurate temperature control • Two solutions • Sensor with simple logic controller • Smart I/O controller

  3. Allen Bradley 1771-TCM • Uses PID controller • 8 independent control loops • Heating or cooling control • Auto-Tuning software • Speeds up design • Accurate gains • Analog or digital control • Standard PLC-5 rack mount

  4. Control Loops • Thermocouples used for feedback • Open loop detection • Disable unit or output constant value • Data collected in the TCM is given to the PLC • PLC controls actuator

  5. PID Auto-Tuning • Auto-Tune calculates PID gains • Gains are stored in TCM module • Gains must be read into PLC data table • TCM can be set to slow, medium or fast response time • TCM memory is volatile • TCM must have gains sent to it or auto-tune whenever power to the module is lost

  6. PID Fine-Tuning Fine tuning can be done manually • Too much overshoot • Decrease P and I • Increase D • Too slow • Increase P and I • Decrease D

  7. Analog vs. Digital Control • TCM module has two possible outputs: • Analog control allows PLC to set the temperature of the heating / cooling device • Digital control gives the PLC the duty cycle for the actuator

  8. Alarms • Alarms can be set • High and low temperature alarm values • High and low deviations • Can use with dead band or without • Alarm is sent to the PLC • The PLC programmer can do what they want with the alarm

  9. Mounting • Termination panel mounted separately • Standard DIN style • Mount in panel near thermocouples • Two cables from termination panel to TCM • Provides more accurate temperature readings

  10. Questions • Cost - $3,150

More Related