IR transmitter : OLCT IR. OLCT IR: onshore and offshore installations. You encounter some of the most severe constraints and infrared technology is very often the only solution. OLCT IR.
E N D
OLCT IR: onshore and offshore installations • You encounter some of the most severe constraints and infrared technology is very often the only solution.
OLCT IR • The extra-tough OLCT IR transmitter detector with infrared sensor for top performance provides top-end gas flammable detection reliability : • insensible to poisoning ( silicon vapours, hydrogen sulphide, chlorinated products …) • resistant to aggressive substances • long-life, highly-resistant sensor • low maintenance and non-intrusive calibration...
OLCT IR • The transmitter OLCT IR is designed for detection of flammable gas : • hydrocarbons , • methane,propane/butane as standard • and others on request… • Note : functional in inert gas atmosphere .
OLCT IR : concept • OLCT IR concept is based on measurement of infrared radiation passing through a volume of gas. • Working IR pulsed source • Reference IR pulsed source.
OLCT IR • Since most gases have unique absorption spectra, they can easily be identified by proper selection of an infrared wave-length at which absorption is measured • l ’OLCT IR = two standard versions : • OLCT IR CH4 • OLCT IR HC. Reference wave-length
Recommanded versions CH4 version HC version ALCENES: ethylene,propylene,1-butene,1-3butadienne… AROMATICS: benzene,toluene,0-Xylene (m- ; p- ),Styrene... ALCANES:butane,propane,hexane,ethane, pentane ... ALCOHOLS:ethanol,methanol, propanol... CETONES:acetone,2-Butanone,cyclohexanone... ETHERS: ethylacetate, methyl methacrylate, ethyl acrylate... ESSENCES: supers,gasoil,gazole,kerozene,essence of terebenthine... SOLVANTS:White spirit...
« CH4 » = recommandedversion according to these examples : • ALCENES • AROMATICS
« HC » = recommanded version according to these examples : • ALCANES • ALCOHOLS • CETONES • ESTHERS • ESSENCES • SOLVANTS ...
OLCT IR compared with cataltytic cells : major advantages • High gas concentration does not saturate the transmitted signal • insensitive to poisoning • low dispersion of response to various gases • presence of oxygen is not required • humidity ( without condensation) has no influence on accuracy • the gas flow rate has no influence on accuracy .
Other ADVANTAGES Proven high reliability and long-term stability no calibration(1) and low maintenance required during equipment lifetime (10 to 15 years) Automatic self test Immunity to poisonning from H2S, silicone and other agents (1) OLCT IR has a continous self-test function
Proven leading-edge technology • « low maintenance » efficiency: electronics of the OLCT IR guarantee extreme accuracy and constant stability ... • The answer to spurious alarms: an ability to ignore external substances that trigger false alarms ... • non -intrusive calibration (magnetic switch)
OLCT IR : maintenance • The OLCT IR has been designed to requiere a minimum of maintenance : • it ’s only necessary to inspect visually that the weather protection is not clogged in heavily contaminated areas • and be sure that the optical surfaces are clean*. * use an equal-part mixture of isopropyl alcohol and water.
Two configurations for adapting to your site : Housing « E » = standalone version , fitted with a terminal compartment and a cable gland. Housing « M25 » = free-fitting version , fitted with a threading and 3-wire output for electrical connections.
DIMENSIONS WEIGHT: 2,3 to 3,1 kgs
INSTALLATION : indications • The location of each detector should preferably be determined at the system design stage : • where gas leakage is most likely to occur • It should be considered whether the gas in question is heavier or lighter than air ? • The detector can be used with the weather protection (réf : 6124976) • The detector should not be mounted where it could be exposed to water drenching
INSTALLATION : orientation • L’OLCT IR must be mounted so that the flow direction indicator must point upwards.
INSTALLATION : information • Housing “ E ” must be mounted so that the longitudinal axis of OLCT IR is horizontal. • This will prevent accumulation of water and dust on the optics • for this purpose, mounting bracket is avaible : réf : 6132380.
Accessories Calibration sample flow housing. Leather test nozzle: allows the functional test by injecting a calibration gas .
Accessories Weather protection kit : Mounting bracket:
Accessories « mosquito » Filter • Weather protection
Accessories • Interface-module allows a direct transmetter 4-20mA linking to a channel initially connected with a catalytic gas detector (analog signal in mv): • and that, without other modifications of installation (cable…), wiring and electronics (control unit) !
TECHNICAL CARACTERISTICS • Detection range: 0-100 % LEL • response time : T50 < 10 secondes with calibration cap • power supply: 16 à 30VCC, 3 active wires • max. resistance per wire capt./control unit = • 16 ohms ( 500 m with 1,5 mm2) and with 21 VCC of power • 4-20 mA signal : max. impedance = 300 ohms • average power consumption = 8W (max 12W) • IP66 • Housing material: stainless steel 316L • Operating temperature: from -30°C to + 55°C • Storage temperature : from 0 to +30°C .
Main applications: • Offshore Platforms, • petrochemical plants, • Chemical industries, • Reffineries, • Marine, • Waste disposal plants …