An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RICH Power Supplies & GroundingThanks to Johan MorantPaolo BaessoXavier Le Gouard Electronics meeting 29/05/06

  2. Example: RICH2 module Each module is mechanically and electrically independent. Cooling plate (not shown) grounded. Plastic pipes for insulation Electronics meeting 29/05/06

  3. Power connections & grounding Maraton LV (5V) channel 1 – floating. Tested Maraton LV (5V) channel 2 – floating. Tested CAEN SY1527LC- A1511B Si bias (80V) – floating. Tested ISEG (20kV) – varistor protection. Under test Electronics meeting 29/05/06

  4. Module Power and Grounding Within module – one common ground, connected to safety earth Local ST-4913 regulators few cm from load (L0 + HPD) Regulators enabled/disabled by SPECS slave Allows possibility to enable/disable L0s/HPDs => a ‘gentle’ power-up sequence We power-up with a well-defined sequence for each module: Turn on LV supplies Turn on Si bias Enable regulators for L0/HPDs (SPECS) Enable GOLs on L0 (SPECS) Loop for all L0s in module Filtering of LV, Si bias (and HV) done locally SPECS – shield of cable connected to module ground AND SPECS master ground. No problems seen yet………. Electronics meeting 29/05/06

  5. Tests with Maraton Tested in lab with programmable load Then used in system tests & Frascati testbeams since January Electronics meeting 29/05/06

  6. Hardware 12-channel 6U prototype now in constant use in labs Not yet operated with all channels used (maximum so far is 6 out of 12 = 3 modules) Sense…… looks OK, more tests to be done Tested with proposed grounding scheme – no problems All ‘analog’ settings with potentiometers Needs water cooling – particular connectors for pipes Documentation VERY bad Electronics meeting 29/05/06

  7. Software Tests done with simple user-panel, via USB OPC server from Wiener seems to work (although installation is not obvious…..) Maraton is now networked (same as CAEN system) Now included in PVSS framework Panels/ FSM under development Electronics meeting 29/05/06

  8. Conclusions Power and grounding scheme follows LHCb recommendations Tested successfully with prototype and production modules: System tests in lab since summer 2005 Two testbeams in Frascati Tests on-going, adding final HV system Good experience with Wiener Maraton in system-tests/testbeams Electronics meeting 29/05/06