UNIVERSITY OF MINNESOTADept. of Environmental Health and Safetywww.dehs.umn.edu Hazard Analysis Process for Adding Amines to Steam System C. Moody, A. Streifel, and M. Nagel
Background • Peak campus steam demand - 450,000 lb/hr • Hospital demand – 20,000 lb/hr • Corrosion of boilers, coils, pumps, traps and piping • Increased maintenance and energy costs – $1M per year
Causes of corrosion • Corrosion caused by formation of carbonic acid • CO2 + H2O H+ + HCO3- (carbonic acid) • Major sources of CO2 • Dissolved gas in make-up water • Thermal breakdown of NaHCO3 and Na2CO3 • Oxygen enhances corrosion
Amine addition • Add neutralizing amines to keep pH range at 8.5 - 9.2 • Morpholine condenses soon after release to protect close-in piping • Cyclohexylamine protects far reaches of condensate piping
Health Effects • Eye irritation • Irritation of upper respiratory tract • Dermatitis and sensitization from skin contact
Amine Type OSHA PEL (ppm) FDA limit in steam (ppm) Odor Threshold (ppm) Morpholine 20 10 0.14 Cyclohexyl-amine 10 10 0.90 Health standards
NIOSH Health Hazard Evaluations • 1982 – Museum study • Diethylaminoethanol (DEAE) produced eye irritation and dermatitis • Air samples - 0.01 ppm • 1988 - Electrical components factory • Nausea, dizziness, throat irritation • DEAE and cyclohexylamine added at 4x normal strength • 1989- Nurses in humidified nursery & newborn ICU – Eye and upper respiratory irritation • Cyclohexylamine and morpholine
NIOSH Evaluation -1993 VA Medical and Research Center • Morpholine and cyclohexylamine • Fatigue, allergy symptoms, eye and upper respiratory irritation • Air, surface and steam samples • Air samples not exceeding minimum detectable concentrations • Detectable concentrations in surface samples • Measured concentrations in condensed steam samples • Recommended no amines for humidification
Potential campus exposures • Humidification of sensitive patient areas • Medical device sterilization • Irritation for students and staff when added in excessive amounts to steam • Food preparation
Control Options for Hospital • Clean steam generators • Direct steam humidification with monitoring and control
Team approach to evaluate proposal • Facilities Management Department • Contract steam plant operator • Department of Environmental Health and Safety
Options for amine addition • Inject amine based on: • pH of condensate return • Steam demand • Grab samples versus real-time monitoring • Metered injection
Proposal • Inject amine based on steam demand • Use computer to calculate injection rate • Use chemical metering pump • Install analyzer to continuously monitor downstream concentration • Use analyzer signal to prevent overfeed of amine
Failure analysis • Conduct “What If” analysis based on description of monitoring/control system • Review possible failures • Evaluate control features • Make additional recommendations for monitoring and control
Recommendations • Certify amine concentration • Request written permission of the University to change amine concentration • Route alarm conditions to central monitoring point • Take independent steam samples
Results • Real time analyzer • Amine concentrations 1.0 - 2.5 ppm • No complaints of irritation or odor
Benefits and Conclusions • Safety and health assurance • Patients, employees and students • Cost effectiveness • Alternative to clean steam generators • Reduce maintenance and energy costs • Process hazard analysis useful
Craig MoodyCraig Moody, CIHDepartment of Environmental Health and SafetyUniversity of Minnesotamoody002@umn.edu612-626-4399