CIDEL Argentina 2010 Session 1 New Aspects for Neutral Grounding of Generators Considering Intermittent Faults Georg Koeppl, Dieter Braun Koeppl Power Experts ABB. Introduction:
E N D
CIDEL Argentina 2010 Session 1 New Aspects for Neutral Grounding of Generators Considering Intermittent Faults Georg Koeppl, Dieter Braun Koeppl Power Experts ABB
Introduction: Most electrical faults are arcing faults (flash-over of an insulation), mostly they are treated as steady state, permanent faults however. Justified, if there is practically no chance of fault arc extinction (high currents with high arc-channel ionisation). Not justified for small currents (single-phase faults in systems with isolated or high impedance grounded systems).
Single-phase fault tests in an 8kV-cable system with isolated neutral [1] Voltages l-g Load currents 10ms Current at fault location
Consequences of these tests: • Single-phase faults with arc channel in solid insulation systems behave like a re-striking switch: • An arc is initiated with a high transient (discharge- and recharge-) current far higher than the 50Hz steady state fault current. • This transient current may be extinguished at a current zero. • Then the recovery voltage (50Hz) rises to a certain magnitude where again a re-strike takes place. • This sequence may be repeated often and almost regularly. • The fault damage caused by the high transient currents is far higher than could be expected on the basis of the small 50Hz fault current.
Transient fault currents Discharge current: Recharge current: (50Hz fault current: 4.7A)
Generator + Step-up Transformer Typical Data: 20kV, 150MVA, 50Hz, Ctotal = 0.305mF/phase, Rf = 10W Resonant grounding via Petersen coil: T = 2Lcoil / Rcoil = 2Q / w 0.12s >> 0.01s
Steady state fault:High-resistance grounding of generator neutral Energy in fault resistance (10W): 140J + 9.4J/cycle 610W
Intermittent fault:High-resistancegrounding of generator neutral Energy in fault resistance (10W): 140J + 220J/cycle 11‘140W
Intermittent fault:Resonant grounding of generator neutral Energy in fault resistance (10W): 140J + 11J/cycle 690W
Conclusions: • Single phase faults in stator windings are in most cases intermittent faults. • The corresponding transient fault currents are by a factor of 60 higher than the small steady state fault current and hence responsible for damages in stator iron and winding. • High resistance grounding (most usual) or resonant grounding of the generator neutral have practically no influence on height and shape of those transient currents. • With high resistance grounding the recovery voltage after fault arc extinction re-appears very quickly, leading to a high cadence of re-strikes and extinctions (2 per cycle) and a high amount of energy absorbed in the fault resistance.
Conclusions (continued): • With resonant grounding the interval between extinction and re-strike is substantially prolonged due to a slowly rising recovery voltage. Energy absorption in the fault resistance is thus reduced by a factor of 20. • Earth fault protection relays are normally suited for high resistance grounding as well as for resonant grounding (different setting of course). • Resonant grounding of generator neutrals consequently is to be preferred to high resistance grounding.