Scale Model InertingTesting with 1/4 Scale Boeing 747 SP Fuel Tank . July 17-18, 2001 International Aircraft Systems Fire Protection Working Group Wilson, NC. Background. Inconsistent Comparisons of Test Data Created Questions of NEA Required to Inert an Aircraft Center Wing Tank

candy
Download Presentation

July 17-18, 2001 International Aircraft Systems Fire Protection Working Group Wilson, NC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Scale Model InertingTesting with 1/4 Scale Boeing 747 SP Fuel Tank July 17-18, 2001International Aircraft Systems FireProtection Working GroupWilson, NC AAR-422 Fire Safety R&D

  2. Background • Inconsistent Comparisons of Test Data Created Questions of NEA Required to Inert an Aircraft Center Wing Tank • Focus of the Testing is to Better Determine the Best Method to Inert a Compartmentalized Fuel Tank • Study Equal NEA Distribution and Localized NEA Deposit • Study Cross-Vented and Single Vent Configurations • Develop Methods to Make Fair Comparisons. AAR-422 Fire Safety R&D

  3. Test Article • Quarter Scale Model of Boeing 747 SP CWT was Built from Plywood By Scaling Drawings from Shepherd Report • 24% length Scale (1.2% Volume) • Scaled all Bay-Bay Penetrations • “Variable Manifold” Allows for Depositing NEA in Any and All Bays of the Tank at Different Rates to Support Inerting Times as Low as 10 Minutes • Oxygen Sensor in Each Bay and in One Vent Channel AAR-422 Fire Safety R&D

  4. Scale Model Bay Convention Dry Bay 1 2 3 4 5 6 AAR-422 Fire Safety R&D

  5. Preliminary Balanced Data • Inerted Tank Several Times with NEA 95% and NEA 98% with the Goal of Balancing the Flow into Inert Each Bay “Equally” for Standard Cross-Venting Configuration • Acquired Data with a Stop Watch (1 reading per minute) • Developed a Volumetric Average to Make Comparisons with Other Inerting Runs • Results As Expected and Consistent with Previous Testing but New Numbers Point Toward a VTE of 1.6 for 95% NEA • VTE Very Sensitive to O2 Concentration at 8% for 95% NEA AAR-422 Fire Safety R&D

  6. Preliminary Balanced Inerting Data AAR-422 Fire Safety R&D

  7. Preliminary Balanced Weighted Average Data AAR-422 Fire Safety R&D

  8. Preliminary Unbalanced Data • Inerted Tank Several Times with NEA 95% with the Goal of Minimizing the Volume Required to Inert the Tank with Standard Cross-Venting Configuration • Acquired Data with a Stop Watch (1 reading per minute) • Used the Volumetric Average Developed to Make Fair Comparisons with Other Inerting Runs • Results Illustrated Very Little Improvement in VTE Required, but Allowed for Simpler Manifold Designs • Smart Design as Good or Better then Well Balanced Manifold AAR-422 Fire Safety R&D

  9. Preliminary Unbalanced Inerting Data AAR-422 Fire Safety R&D

  10. Preliminary Unbalanced Weighted Average Data AAR-422 Fire Safety R&D

  11. NEA Minimization Data • Inerted Tank Several Times with NEA 95% to Minimizing the NEA Volume Required to Inert the Tank with Half Vent System Blocked (No Cross Venting) • Acquired Data with Computer Data Acquisition System at a Rate of 1 Sample per Second (Approximate) • First did Balanced Run to Give Baseline; Used the Volumetric Average Developed to Make Fair Comparisons with Other Inerting Methods • Results Illustrated Modest Improvement with Simplest Deposit Scheme AAR-422 Fire Safety R&D

  12. NEA Minimization Data - Best Data AAR-422 Fire Safety R&D

  13. Unbalanced Weighted Average Data AAR-422 Fire Safety R&D

  14. Summary • Model Results Consistent with Existing Knowledge Base But VTE Slightly Higher in These Experiments • This is Believed to be due to Better Measurement Techniques Developed • Depositing in an Efficient Manner Can Greatly Simplify Manifold Design and Even Improve Inerting Efficiency • Still Need to Verify Results in Full-Scale Test Article AAR-422 Fire Safety R&D