1 / 27

HIDRANTNO OMREŽJE – KOLIČINA VODE POTREBNE ZA GAŠENJE

HIDRANTNO OMREŽJE – KOLIČINA VODE POTREBNE ZA GAŠENJE. VODA POTREBNA ZA GAŠENJE. STOPNJE POŽARA: 1. stopnja - začetni požar – požar je v obdobju, ko se v požarnem sektorju močno razvija in glede na vrsto in količino gorljive snovi intenzivno pridobiva na moči

cloris
Download Presentation

HIDRANTNO OMREŽJE – KOLIČINA VODE POTREBNE ZA GAŠENJE

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. HIDRANTNO OMREŽJE – KOLIČINA VODE POTREBNE ZA GAŠENJE

  2. VODA POTREBNA ZA GAŠENJE STOPNJE POŽARA: 1. stopnja - začetni požar – požar je v obdobju, ko se v požarnem sektorju močno razvija in glede na vrsto in količino gorljive snovi intenzivno pridobiva na moči 2. stopnja - požar v požarnem sektorju je popolnoma razvit vsa gorljiva snov v sektorju gori 3. stopnja - požar ima moč druge stopnje s tem, da povzroča požare v drugih sektorjih (drugih prostorih), v teh prostorih pa požari pridobivajo na svoji moči 4. stopnja - požar v prvem požarnem sektorju pojenjuje, kajti v tem prostoru zmanjkuje gorljive snovi, v sosednjih požarnih sektorjih (prostorih) pa je požar polno razvit

  3. VODA POTREBNA ZA GAŠENJE TAKTIKA GAŠENJA: • pasivna zaščita – v tem primeru gasilci polivajo z gasilnim sredstvom objekte in prostore kjer ni požara – ta taktika zahteva najmanjšo količino gasilnega sredstva, opreme in gasilcev. Ščiti se praviloma objekte, ki imajo zadosten odmik od gorečega objekta • aktivna zaščita – v tem primeru gasilci polivajo objekt ali prostor, ki gori in to z zunanje strani. S tem samo omejujejo širjenje požara na druge prostore ali objekte • napad – v tem primeru vodja intervencije ugotovi, da ima dovolj opreme, gasilnih sredstev in gasilcev, za oblikovanje napadov gašenja požara. Pri stopnji napada imamo nato več možnosti, zopet odvisno od gasilnih sredstev, opreme in števila gasilcev

  4. VODA POTREBNA ZA GAŠENJE • Osnovno gasilsko enoto sestavlja devet gasilcev. Enota ima opremo za izvedbo treh napadalnih skupin, sama črpa vodo in jo transportira do mesta požara. Enota je opremljena z gasilskim vozilom GV-1 v katerem je nameščena potrebna oprema in prostor za prevoz gasilcev. • Takšna enota lahko pogasi začetne in največ srednje požare. • V primeru večjih požarov se aktivira in združi več gasilskih enot.

  5. VODA POTREBNA ZA GAŠENJE • GASILSKO VOZILO GV – 1 • 7 do 9 gasilcev • PRENOSNA ČRPALKA 8/8: (800l/min (13l/s) pri 8 bar) • ROČNIKI: • 1 kos velikosti B, pretok 400 l/min(6.6l/s), tlak 2,5 bar • 3 kose velikosti C, pretok 200 l/min(3.3l/s), tlak 2,5 bar • 1 kose velikosti D, pretok 100 l/min(1.6l/s), tlak 2,5 bar • 1 kos ročnik za težko peno S2 , pretok 200l/min(3.3l/s), tlak 4.5 bar • 1 kos ročnik za srednjo peno M2 , pretok 200l/min(3.3l/s), tlak 2.5 bar

  6. VODA POTREBNA ZA GAŠENJE • GASILSKO VOZILO GV – 1

  7. VODA POTREBNA ZA GAŠENJE • GASILSKO VOZILO GV – 2 • 7 do 9 gasilcev • PRENOSNA ČRPALKA 8/8:(800l/min (13l/s) pri 8bar) • PREVOZNA ČRPALKA 16/8:(1600 l/min (26l/s) pri 8bar) • ROČNIKI: • 1 kos velikosti B, pretok 400 l/min(6.6l/s), tlak 2,5 bar • 4 kose velikosti C, pretok 200 l/min(3.3l/s), tlak 2,5 bar • 1 kos velikosti D, pretok 100 l/min(1.6l/s), tlak 2,5 bar • 1 kos ročnik za težko peno S4 , pretok 400 l/min(6.6l/s), tlak 4.5 bar • 1 kos ročnik za srednjo peno M4 , pretok 400 l/min(6.6l/s), tlak 2.5 bar

  8. VODA POTREBNA ZA GAŠENJE • GASILSKO VOZILO GV – 2

  9. VODA POTREBNA ZA GAŠENJE • Gasilsko vozilo s cisterno GVC 16/25 • 6 do 7 gasilcev • 2500 l vode • PREVOZNA ČRPALKA 16/8:(1600 l/min (26l/s) pri 8bar in 400l/s (6.6l/s) pri 40 bar) • ROČNIKI: • 1 kos velikosti B, pretok 400 l/min(6.6l/s), tlak 2,5 bar • 2 kosa velikosti C, pretok 200 l/min(3.3l/s), tlak 2,5 bar • 1 kos velikosti D, pretok 100 l/min(1.6l/s), tlak 2,5 bar • 1 kos revolver ročnik pretok 100l/min, tlak 40 bar • 1 kos ročnik za težko peno S4 , pretok 400 l/min(6.6l/s), tlak 4.5 bar • 1 kos ročnik za srednjo peno M4 , pretok 400 l/min(6.6l/s), tlak 2.5 bar

  10. VODA POTREBNA ZA GAŠENJE • Gasilsko vozilo s cisterno GVC 16/25

  11. VODA POTREBNA ZA GAŠENJE • Gasilsko vozilo s cisterno GVC 24/50 • 3 gasilci • 5000 l vode • PREVOZNA ČRPALKA 24/8:(2400 l/min (40l/s) pri 8bar in 600l/s (10l/s) pri 40 bar) • METALEC VODE : 1600l/min(26l/s), tlak 2,5 bar • ROČNIKI: • 1 kos velikosti B, pretok 400 l/min(6.6l/s), tlak 2,5 bar • 2 kosa velikosti C, pretok 200 l/min(3.3l/s), tlak 2,5 bar • 1 kos revolver ročnik pretok 100l/min, tlak 40 bar • 1 kos ročnik za težko peno S4 , pretok 400 l/min(6.6l/s), tlak 4.5 bar • 1 kos ročnik za težko peno S8 , pretok 800 l/min(13l/s), tlak 4.5 bar • 1 kos ročnik za srednjo peno M4 , pretok 400 l/min(6.6l/s), tlak 2.5 bar

  12. VODA POTREBNA ZA GAŠENJE • Gasilsko vozilo s cisterno GVC 24/50

  13. VODA POTREBNA ZA GAŠENJE • GASILSKA ENOTA ZA TRI NAPADE POTREBUJE : • 0d 600 l/min do 2000 l/min to je 10l/s do 33l/s PRI MAKSIMALNI OBREMENITVI PORABI VODO: • IZ VOZILA S CISTERNO 16/25 v eni do štirih minutah • IZ VOZILA S CISTERNO 24/50 v dveh do osmih minutah

  14. VODA POTREBNA ZA GAŠENJE »Gorenje« - Velenje – požar oddelka galvanska obdelava kovin - požar je gasilo 269 gasilcev s 24. vozili - hidrantno omrežje ni zadostovalo - požarno vodo so s pomočjo prenosnih črpalk črpali iz bližnjega potoka Paka - galvanska obdelava kovin je pogorela, rešili so halo s hladilno tehniko in preprečili ekološko katastrofo saj so rešili čistilno napravo ob objektu

  15. VODA POTREBNA ZA GAŠENJE • »Gorenje« - Velenje – požar oddelka galvanska obdelava kovin

  16. VODA POTREBNA ZA GAŠENJE • »Dar« - Koper – proizvodnji obrati - požar je gasilo 122 gasilcev s 29. vozili - hidrantno omrežje ni zadostovalo – deloval je samo en hidrant - požarno vodo so s črpali pomočjo prenosnih - v objektu je bilo veliko vnetljivih in lahko gorljivih snovi, med drugim tudi laki, barve in 800 litrov kurilnega olja

  17. VODA POTREBNA ZA GAŠENJE • »Dar« - Koper – proizvodnji obrati

  18. VODA POTREBNA ZA GAŠENJE • Požar v tovarni STOL v Kamniku - požar so gasilci gasili z osmimi napadi - hidrantno omrežje ni zadostovalo – vršnja poraba vode je bila 21l/s - pomanjkanje požarne vode so gasilci reševali z zapiranjem posameznih napadov - v objektu je gorel obrat servis pisarniških stolov. Obrat je pogorel vendar so gasilci rešili poslovni in ostali del tovarne

  19. VODA POTREBNA ZA GAŠENJE • Požar v tovarni STOL v Kamniku

  20. VODA POTREBNA ZA GAŠENJE • Visokogorski požar v Kamniško - Savinskih Alpah • Požar je gasilo 272 gasilcev 8 dni • Požar se je rasprostorial na nadmorski višini od1300 metro do 1800 metrov • Za pogasitev požara so gasilci porabili 157 000 litrov vode. • Vodo so črpali na nadmorski višini 590m, v izviru kamniške bistrice

  21. VODA POTREBNA ZA GAŠENJE

  22. VODA POTREBNA ZA GAŠENJE • Stanje hidrantov v podjetjih

  23. VODA POTREBNA ZA GAŠENJE • Stanje hidrantov v podjetjih

  24. VODA POTREBNA ZA GAŠENJE • Neuporabni nadzemni hidrant

  25. VODA POTREBNA ZA GAŠENJE • Primer označbe nadzemnih hidrantov

  26. VODA POTREBNA ZA GAŠENJE • Iz gornjega predavanja lahko ugotovimo: • V nobenem primeru gasilci niso imeli zadostne količine vode iz hidrantnega omrežja • Gasilci v Sloveniji smo tako organizirani in opremljeni, da do sedaj v nobenem požaru ni primanjkovalo gasilcev ali opreme • Hidrantno omrežje je v večini primerov poškodovano poškodovano, neprimerno označeno, nima predvidenega pretoka itd.

  27. VODA POTREBNA ZA GAŠENJE • Gasilci se močno zavedamo problematike izdelave vodovodnega omrežja sanitarne vode takih dimenzij, ki zadostujejo hidrantnemu omrežju – posebno v manj urbanih naseljih. • Menimo, da je v bodoče nujno potrebno razmišljanja uvajanja normativov s katerimi bi določali požarno vodo neodvisno od sanitarne vode, nikakor pa ni dopustno zaradi problematike sanitarne vode zniževati količino požarne vode. • Nujno je potrebno uvesti redne nadzore nad izvedbo obstoječih hidrantnih omrežij

More Related