Auxiliary Power Supply System

Auxiliary Power Supply System. By CGS Gunasekara. Content. Why auxiliary supply is needed ? Equipments supplied through auxillary. Modes of operation. Demonstration of operation. Why auxiliary supply is needed ?

cyma
Download Presentation

Auxiliary Power Supply System

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Auxiliary Power Supply System By CGS Gunasekara

  2. Content • Why auxiliary supply is needed ? • Equipments supplied through auxillary. • Modes of operation. • Demonstration of operation

  3. Why auxiliary supply is needed ? To supply power to generator/turbine and other ancillary equipments for their operation.

  4. Equipments supplied by auxiliary. Common supplies • Lighting system • Annunciators & indicators, alarms • Ventilation system (supply fans, Exhaust fans) • AC system (compressures, blower fans) • Battery charging system (220 V , 48 V) • Drainage pumps • Communication system

  5. Turbine & Generator • Instrumentation (metering) • Protection relays • Bearing oil pumps • Air compressors • (to operate governor equipment • Turbine , break system) • Cooling water pumps (stator coolers, bearing oil coolers) • Bearing oil pumps • Generator Heaters

  6. General Layout Diagram

  7. Modes of operation (1) From 220 KV bus through main T/F1,2,3 and through HAD3,5, or 6 (to both ESS & Non-ess sides) (2) Generators through HAD3,5 or 6 (to both ESS & Non-ess sides) (3) DG ( only to ESS side, can not extend to Non-Ess side)

  8. *Voltage : 220 KV bus voltage 13.8 KV 11 KV400 V 3 ph

  9. *Voltage : generator voltage 13.8 KV 11 KV400 V 3 ph

  10. * Voltage : through DG T/F 400 V step up to 11 KV 400 V 3 ph