1 / 10

Gas Control System with PLC for PNU-RICH2

1. Gas Control System with PLC for PNU-RICH2. 27. April. 2010 C.W. Son*, J.G. YI, K.E. Choi , K.S. Oh, J.H. Song, J.S. Eum In-Kwon Yoo Department of Physics, Pusan National University Heavy Ion Physics Experiment LAB. 2. Contents. Motivation & I ntroduction of PNU-RICH2

darcie
Download Presentation

Gas Control System with PLC for PNU-RICH2

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 1 Gas Control System with PLC for PNU-RICH2 27. April. 2010 C.W. Son*, J.G. YI,K.E. Choi, K.S. Oh, J.H. Song, J.S. Eum In-Kwon Yoo Department of Physics, Pusan National University Heavy Ion Physics Experiment LAB

  2. 2 Contents • Motivation & Introduction of PNU-RICH2 • Control System Tool (PVSS) • Gas Control System with PLC and sensors for HIPEx • Test result • Conclusion

  3. 3 Motivation & Introduction of PNU-RICH2

  4. 4 Control System Tool (PVSSII) PVSS II : SCADA (Supervisory Control And Data Acquisition) tool adapted by CERN - Archiving, Alarm Generation & Handling, A Graphical Editor, A Scripting Language (CTRL), A Graphical Parameterization tool, Drivers

  5. 5 Gas Control System with PLC and sensors for HIPEx Counting House Gas flow rate control -> MFC Gas flow direction control -> Electric valve Gas monitoring -> Pressure -> Humidity and Temperature Online control and monitoring at counting house by ethernet Beam Line Ethernet

  6. 6 Gas Control System with PLC and sensors for HIPEx Specification DC15V Programmable Logic Controller • On/Off Valve • Normal Close(NC) • 0.3 ~ 10kgf/cm2 • Mass Flow Controller • 0 ~ 10SLPM Flow Range (N2) • Accuracy : ±1% FS • 0 ~ 5VDC In/Out Signal Circuit breaker Relay DC24V • Pressure Transmitter • 0 ~ 5Kgf/cm2 Range • Accuracy : ±0.3 FS • 4 ~ 20mA Out Signal Current Loop Supply I/O Terminal • Temperature & Humidity Sensor • -20 ~ 80℃ Range for Temperature • 0 ~ 100% Range for Humidity • Accuracy : ±0.3℃, ±1.8% • 4 ~ 20mA Out Signal

  7. 7 Gas Control System with PLC and sensors for HIPEx System Control & Monitroing Menu Temperature Humidity Alarm Monitoring

  8. 8 Gas Control System with PLC and sensors for HIPEx • Interlock System • Valve1 • Valve2 • Auto Control & Alarm System • Pipe pressure monitoring • -> Greater than 3atm, Valve1 can open • RICH pressure monitoring • -> Greater than 1.3atm, Valve3 close & Valve4 open (High pressure alarm) • Low Pressure • -> Less than 0.8atm, Valve3 open & Valve4 close (Low pressure alarm)

  9. Test result 9

  10. 10 Conclusion • PLC and PVSSII is working • Gas System problem • - Gas is leaking • - When low pressure, gas is not flow in vessel