An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. AcadPV10 kWp PV grid-connected system in Sofia,BG CL SENES – Sofia,BG EC Project:PV Enlargement Sofia Meeting 30 June

  2. Solar Potential: CL SENES – Sofia,BG Location: CL SENES Building LA: N 42o 42.399’ LO: E 23o 18.830’ ALT: 551 m Sofia Meeting 30 June

  3. Electrical scheme: CL SENES – Sofia,BG Sofia Meeting 30 June

  4. Expected Performance: 10 kWp PV =>13.2 MWh/ yr CL SENES – Sofia,BG Sofia Meeting 30 June EC Joint Research Centre - ISPRA, Italy

  5. Design & Construction Aim: High Visual Impact CL SENES – Sofia,BG Sofia Meeting 30 June

  6. CL SENES – Sofia,BG Design & Construction: Final Vision Sofia Meeting 30 June

  7. Solar Generator: 10 kWp installed power CL SENES – Sofia,BG Sofia Meeting 30 June

  8. CL SENES – Sofia,BG PV Inverters & DC Wiring: Grid connection Sofia Meeting 30 June

  9. Current Status:Meteo Data CL SENES – Sofia,BG Sofia Meeting 30 June

  10. Current Status: PV system Performance PV module: Readout 128 W CL SENES – Sofia,BG PVsubfield2:Readout 2666 W Sofia Meeting 30 June

  11. Software Control Menus: PV system Configuration CL SENES – Sofia,BG MPPTracking Range Sofia Meeting 30 June

  12. Main Results : 10 kWp PV array Control Electrometer Readings 1st day of operation - 37 kWh/ day 1st month of operation - 1210 kWh/ month CL SENES – Sofia,BG Typical performance: ( PV subfield 2 - 3,3 kWp) Solar Generator : SP 3100-600 Inverter: SG Voltage: 317.2 V AC Voltage: 216.7 V SG Current: 8.94 A AC Current: 12.31 A Peak Readings: P max : 3132 W , V oc : 408.0 V, V MPPT : 318.3 V Sofia Meeting 30 June

  13. Current Problems: DL100 Data logger Communication CL SENES – Sofia,BG Inverter Disconnection due to AC Grid Failure Sofia Meeting 30 June

  14. Local Grid Profile: CL SENES – Sofia,BG Sofia Meeting 30 June

  15. Future Tasks:DAS installation, Seasonal Monitoring CL SENES – Sofia,BG Sofia Meeting 30 June

  16. Conclusions: * 10 kWp PV system has been installed in BG * PV installation is connected to Low Voltage Public Grid * Excellent Performance and Trouble-free Operation * High Visual Impact CL SENES – Sofia,BG Sofia Meeting 30 June