An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Commissioning the System

  2. Commissioning • Use Service form 1A • Proof of performance • Speeds up Tech support • Reduces recalls

  3. Balancing Orifices • Works with all plenums • 15, 35, 50% • Easy to re-balance system

  4. Airflow Checks • U tube or Slope Gauge – best way • Delta T in cooling 25-28 deg. • Electric Heat Delta T check • Motor Amperage

  5. Static Pressure Affects on Fan Performance

  6. Electric Heat Airflow • Convert KW to BTU (3413 X KW = BTU) • DeRate for 208 (.8) • Cfm’s x1.08 x’s Temp. Diff. = BTU • Compare to unit data

  7. Winterizing Cooling Only Units • Winter supply shut-offs • Seal the return • Winterize condensate • Shut off breaker