1 / 40

Application Guidelines for FMC

NEMA RV 3 Application & Installation Guidelines For Flexible & Liquid Tight Flexible Metal Conduits. Application Guidelines for FMC. Construction of FMC Grounding and Bonding Uses Permitted and Not Permitted. Construction for FMC. Constructed in accordance with NEC

duyen
Download Presentation

Application Guidelines for FMC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NEMA RV 3Application & Installation Guidelines For Flexible & Liquid Tight Flexible Metal Conduits www.nema.org

  2. Application Guidelines for FMC • Construction of FMC • Grounding and Bonding • Uses Permitted and Not Permitted www.nema.org

  3. Construction for FMC • Constructed in accordance with NEC • Complies with safety requirements of UL1 • Interlocked corrosion resistant steel or Aluminum strip www.nema.org

  4. Picture Example for FMC www.nema.org

  5. Diagram Example for FMC Cross-section view illustrating interlocking construction www.nema.org

  6. Grounding and Bonding for FMC • Permitted for bonding • When installed with listed fittings and; • Flexibility is not required after installation and; • When installed according to NEC Articles 348 and 250 and; • Protected by overcurrent device rated 20 Amperes or less. • Limited to 6’ lengths when used for bonding (see NEC 250.118 (5)) • Grounding conductor required if FMC • installed for flexible equipment or • when used in lengths greater than 6’. • Grounding and bonding continued in slide 7… www.nema.org

  7. Product Marking for FMC • Manufacturer’s designation • UL Logo • Conduit type • Reduced wall (RW) • Extra reduced wall (XRW) • Material type • Aluminum (AL) • Steel (No Mark Required) www.nema.org

  8. FMC Marking Example www.nema.org

  9. Uses Permitted for FMC • Exposed and concealed locations – NEC 348.10 • Dry locations only • Branch circuits and feeders • Ducts or plenums for environmental air • 300.22(B) limits to 4’ length • 300.22(C) no length limit • Under raised floors for computer rooms • Lighting whips and motor leads • These uses are not all inclusive, but serve as guidelines www.nema.org

  10. Uses Not Permitted for FMC • NEC 348.12 • Wet locations • 2008 NEC removed exceptions • Hoistways except as permitted in 620.21(A)(1) • Storage battery rooms www.nema.org

  11. Uses Not Permitted – cont. for FMC • Hazardous locations except 501.10(B) and 504.20 • Where conductors are exposed to deteriorating material • Underground or in concrete • Where subject to physical damage www.nema.org

  12. Reference ArticlesReference UL 1 and NEC • NEMA RV 3 1.4.1 – National Electric Code • NEMA RV 3 1.4.2 – Related NEC Articles • NEMA RV 3 1.4.3 – UL Standards • Guide information page: http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm • White book “Guide Information for Electrical Equipment” www.nema.org

  13. Application Guidelines for LFMC • Construction of LFMC • Grounding and Bonding • Marking • Uses Permitted and Not Permitted www.nema.org

  14. Construction for LFMC • In accordance with NEC • Complies with safety requirements of UL360 • Interlocked zinc-coated corrosion resistant steel • Trades sizes are 3/8” through 4” • Sizes 3/8” – 1 ¼” have bonding strip enclosed by convolution www.nema.org

  15. Construction – cont. for LFMC • Jacket material is liquid-tight, non metallic • Jacket specifications governed by UL 360 • Fittings for LFMC are constructed to UL 514B www.nema.org

  16. Picture example for LFMC Cut-away view of Liquidtight Flexible Metal Conduit to illustrate construction www.nema.org

  17. Diagram Example for LFMC Cross-section view illustrating interlocking construction www.nema.org

  18. Grounding and Bonding for LFMC • LFMC trade sizes 3/8” – 1 ¼” permitted for equipment bonding: • When installed with listed fittings and; • Flexibility is not required after installation and; • When installed according to NEC Articles 350 and 250 and; • Only in 6’ lengths or less • Sizes 3/8” – 4” may be installed in unlimited lengths provided: • A separate grounding conductor is installed • And installed according to NEC Articles 350 and 250 www.nema.org

  19. Surface Print for LFMC • Manufacturer’s name or location • Trade size • Temperature rating • Burial rating (when applicable) • Flame rating (when applicable) • Current rating (for equipment bonding according to NEC article 250) www.nema.org

  20. Uses Permitted for LFMC • Exposed and concealed locations as follows: • When flexibility or protection from liquids, vapors or solids are required • As permitted by 501.10(B), 502.10, 503.1 and 504.20 • Other hazardous classified locations per 553.7(B) • Direct burial where listed & marked for that purpose • If LFMC is marked direct burial it is also suitable for use in concrete or in poured concrete • The following are references throughout the NEC code: www.nema.org

  21. Uses Permitted –cont. for LFMC • Outside branch circuits and feeders • Under raised floors for computer rooms • Lighting whips and motor leads • These uses are not all inclusive, but serve as guidelines • References throughout the NEC Code: www.nema.org

  22. Uses Not Permitted for LFMC • Where subject to physical damage • Where operating conditions cause temperatures to exceed material ratings • See NEC 350.12 for prohibited uses www.nema.org

  23. Reference Articles for LFMC • NEMA RV 3 2.4.1 – National Electric Code • NEMA RV 3 2.4.2 – Related NEC Articles • NEMA RV 3 2.4.3 – UL Standards • Guide information page: http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm • White book “Guide Information for Electrical Equipment” www.nema.org

  24. Installation Guidelines • Installation Considerations • Securing & Supporting FMC & LFMC • Terminating FMC www.nema.org

  25. Installation Considerations for FMC & LFMC • Minimum centerline bend radius • Table 2 chapter 9 NEC • “Other bends” column • Maximum # of bends between pull points • Not to exceed (4) - 90 degree bends • Or a total of 360 degrees (any direction) www.nema.org

  26. Offset Table 2 3/4" Trade Size 0.75 Overall Length of Conduit for Given Offset and Lateral Distance "B" (in.) "R" Offset Distance (in.) Lateral Dist. 1.0 1.5 2 2.5 3.0 4.0 5.0 6.0 8.0 10.0 7 7.6 8 8.3 8.7 9 9.2 9.5 9.8 10 10.2 10.4 10.6 11.0 11 11.1 11.3 11.5 11.8 12 12.1 12.2 12.4 12.7 13.0 13 13.1 13.2 13.4 13.6 13.8 14.4 14 14.1 14.2 14.3 14.5 14.7 15.3 15 15.1 15.2 15.3 15.5 15.6 16.1 16.7 20 20.0 20.1 20.2 20.3 20.4 20.7 21.2 21.7 22.9 24.4 25 25.0 25.1 25.1 25.2 25.3 25.6 25.9 26.2 27.2 28.3 30 30.0 30.1 30.1 30.2 30.2 30.4 30.7 31.0 31.7 32.7 Lateral Offsets • Use tables for length • Lateral offset • Example below www.nema.org

  27. Vertical Loop • Vertical loop w/offset • L=(8xTS)+(1.57xA) +T/2+F • L = Overall length • TS = Trade size • A = Horizontal dist between fittings • T = Travel distance • F = Offset • This accounts for suggested tangent length www.nema.org

  28. Fittings should be tightened properly Section 3.3, tables 1 and 2 of NEMA guidelines for proper torquing values Closely follow manufacturer's instructions Installation Considerations – cont. for FMC & LFMC www.nema.org

  29. Securing & Supporting FMC & LFMC • According to NEC 348.30 & 350.30 • Both must be supported and secured every 4.5’ or less • Must be secured within 12” of each termination • These support requirements are waived if needed for flexibility or for luminaries www.nema.org

  30. Securing & Supporting – cont. for FMC & LFMC • Both may be unsupported when: • Conduit is fished between access points through concealed spaces in finished buildings or structures and supporting is impractical • Flexibility is required • 3’ maximum for LFMC • 3’ maximum for FMC ½” through 1¼” • 4’ maximum for FMC 1½” through 2” • 5’ maximum for FMC 2½” and larger • Used on luminaries; 6’ maximum • Run through non-vertical framing members with distances not exceeding 4½’ www.nema.org

  31. Terminating FMC • Fitting Selection requires knowing: • Trade size or metric designator • Type of FMC, (standard, reduced or extra-reduced wall) • Type of metal (steel or aluminum) www.nema.org

  32. Conduit Preparation for FMC & LFMC • Square the cut end of the metal conduit • Insert conduit flush with fitting end stop • Ensure seating of clamp on conduit before torquing • Be careful torquing the securement screw • Always follow the manufacturer's instructions • Follow recommendations from NEMA FB 2.20, “Selection and Installation guidelines for Fittings for use with Flexible Conduit and Cable” www.nema.org

  33. Cutting Conduit for FMC • Rotary armor cutters • Hacksaw • Cut one convolution at a 60 degree angle • Diagonal wire cutters • Brake the conduit or twist open • Then cut with the cutters www.nema.org

  34. Cutting Conduit for LFMC • Hacksaw • Blade should have 32 teeth per inch • Band saw with ½” X .025 Blade with 24 teeth per inch at 350 ft/min www.nema.org

  35. Fitting Attachment for FMC • Always make sure the conduit is inserted completely to the smooth end stop • When using a clamp type fitting, be sure the fitting seats between the convolutions • Hand tighten the fitting screws and slightly rotate the conduit in the fitting • If there are two screws, tighten alternately to provide even pressure. • Table 1 in NEMA RV 3 shows standard torque values for FMC fittings www.nema.org

  36. Terminating for LFMC • Fitting Selection requires knowing: • Trade size or metric designator • The environment of installation • Conduit preparation • Square the end of the conduit • Fully insert conduit to end stop • Ensure jacketing is not cut or ripped • Always follow the manufacturers instructions • Follow recommendations from NEMA FB 2.20, “Selection and Installation guidelines for Fittings for use with Flexible Conduit and Cable” www.nema.org

  37. Fitting Attachment for LFMC • Squared end must be fully inserted into ferrule • Assembly methods vary for LFMC fittings, follow manufacturer's instructions • Table 2 in NEMA RV 3 show standard torque values for LFMC fittings www.nema.org

  38. Unthreaded Entries • Hand tighten the threaded portion of fitting to secured box using a locknut • Assemble nut, gland and ferrule onto conduit • After securely tightening the gland nut to the threaded body, finish tightening the locknut ¼ turn www.nema.org

  39. Fitting Example www.nema.org

  40. Verification of Installation • Conduit shall be properly terminated at boxes • Conduit shall be properly secured and supported • Conduit shall not show evidence of damage or physical abuse www.nema.org

More Related