Presentation On INERGEN

Presentation On INERGEN. Romeetech Engineering & Services Introducing Inergen Bijan Kumar Mani Managing Partner Romeetech Engineering & Services. The fire needs Fuel, Heat and Oxygen. Remove or lower one of those and the fire is extinguished.

eddy
Download Presentation

Presentation On INERGEN

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Presentation On INERGEN Romeetech Engineering & Services Introducing Inergen Bijan Kumar Mani Managing Partner Romeetech Engineering & Services - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  2. The fire needs Fuel, Heatand Oxygen. • Remove or lower one of those and the fire is extinguished. • The fire goes out if the oxygen level is below 15% Oxygen Fire triangle Fuel Heat - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  3. How does Inergen work? - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  4. Unlike any other suppression agent like, Water, DCP, Foam, or gases like CO2, FM200, ,Nitrogen, Argonite or Halon 1301 INERGEN will: Extinguish the fire andinhibit re-ignition, with norisk to people or damage to equipment and no impact on the environment Why Inergen? - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  5. Wouldn’t it be fantastic to extinguish fire with the air that we breathe? This is really possible! - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  6. Safe for People • NO adverse effects on people. • Contains a small amount of CO2 to stimulate the uptake of oxygen • Does not create a fog ensuring that escape routes are always visible • Safe for Property • Harmless on physical assets like equipment furniture etc. • Leaves no residue to clean up and does not produce any toxic by-products Inergen - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  7. Inergen Safe for the Planet Inergen is as safe as the air we breathe! Safe for your Pocket Inergen will never be banned Central cylinder banking to protect multiple areas Naturally existing gases makes maintenance and refills easy 10 year Evergreen warranty takes all your problems away - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  8. Inergen Manufactured by Mother Nature - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  9. Inergen Comparatively Less Spaces & Less Maintenance Cost Than Other INERGEN System 300 Bar Cylinders with Accessories From Fire eater , Denmark Supplied with UL listed Manifolds UL Listed Products - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  10. Advantage Of 300 Bar Cylinder Inergen It is only 300 Bar cylinder store pressure and the system pressure is same as other pressure rating like 200 Bar & 150 Bar. No of cylinder reduce to 2/3rd as compared to 200 Bar and just ½ as compared to 150 Bar. 300/200/150 Bar all cylinders are UL Listed and Certified which ensure the best safety aspect of the products. Civil construction cost reduces drastically . Spaces saving. Initial investment are much less since the no of cylinder is less. Accessories are also less. Maintenance cost for refill and others spare parts are less. Easy remote monitoring round the clock to ensure correct functionality all the time. - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  11. New Inergen Atmosphere • NITROGEN 68% Lowers oxygen level below 15% • ARGON 16% The INERGENatmosphere has a density similar to normal air – with a long retention time of 20 to 30 minutes • CO2 4% Increases human respiration rate and oxygen transfer to brain – protects human life • OXYGEN 12 - 12.5% Fires are extinguished below 15% Safe for people - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  12. Test atmospheres O2 21% O2 10% • Medically supervised tests carried out with human beings • Test atmospheres: Air 21% oxygen Hypoxia 10% oxygen Inergen 10% O2 + 4% CO2 • Source: University of Pennsylvania U.S. Research Program – Test Results - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  13. Blood oxygenation O2 21% O2 10% • Inergenmaintains brain oxygen at normal levels due to the CO2 content. • Lowering the Oxygen level using any other Inert gas does not. Safe for people - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  14. Pulse rate • Inergendoes not affect the heart rate in low oxygen atmospheres • Critical for people with heart disease. 100 90 80 70 60 50 Safe for people O2 10% O2 21% - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  15. Word and number tests 30 20 O2 21% 10 O2 10% 0 • Inergenmaintains mental performance in low oxygen atmospheres • Good for an emergency situation! Safe for people - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  16. NO Thermal Shock • Generates NO Toxic Breakdown Products - HF (Hydrogen Fluoride Gas) • Long “Holding” Time • Generates no residue Safe for property - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  17. THERMAL SHOCK Electronics can be adversely affected by sudden temperature changes Change from temperature 20oC to: Safe for property - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  18. Typical Results INERGEN® Concentration (%) HALON Concentration (%) 60 56 52 48 44 40 36 32 28 24 20 16 12 8 4 0 INERGEN® Concentration 6 4 3 2 1 INERGEN® Retention Threshold HALON Retention Threshold HALON Concentration 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Safe for property Time (Minutes) - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  19. Ozone Depletion Potential (ODP) = 0 • Global Warming Potential (GWP) = 0 • Atmospheric Lifetime = 0 • Composed entirely ofgases present in the air webreathe Safe for the planet - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  20. One cylinder requires 0.07m2(1 square foot) of storage space • Cylinders can be stored up to 100m from the protected room • Central Storage and selector valves can be used for multi-hazard protection Central Storage safe for your pocket - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  21. Cylinders can be Stored 150 meters away There is always a convenient place to locate the storage bank - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  22. 5 CYL 10 CYL 15 CYL Cost Saving – Central Cylinder Bank System Single Cylinder Bank Room 1 Room 2 Room 3 Selector Valves - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  23. Cost Saving – Central Cylinder Bank System Single Cylinder Bank 5 CYL 10 CYL 15 CYL Room 1 Room 2 Room 3 Selector Valves - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  24. Automatic Remote Cylinder Condition Monitoring • INERGEN Gas Based System Is Nothing But Safety Measurement Used For Fire Prevention In The Event Of Fire. • What Happens If Some Or All Cylinders Are Exhausted Due To Leaking Or Low Pressure. • To Ensure Correct System In Place Throughout - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  25. Automatic Remote Monitoring Automatic Remote Cylinder Condition Monitoring The manoswitch (combined pressure gauge and pressure switch) used by Fire Eater features a single pole change over switch making it possible to monitor for normal and low pressure as well as short circuitry and open circuit. The manoswitches are designed to be connected in a daisy chain, where low pressure on one manoswitch will indicate low pressure on the monitoring panel. The dual-resistor terminator (part of this kit) has to be placed on the last manoswitch in the daisy chain. In the normal position (pressure above the set point) the resistance of the circuitry is high (3K3/5K6), when pressure falls below the set point the resistance of the circuitry falls to low (680/470 ohm). - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  26. Machinery Spaces • Laboratories • Control Rooms • Telecommunication Facilities Where Inergen is Used Worldwide - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  27. Electrical Switch Rooms • Museums and Archives • Computer Rooms • Normally occupied areas • Operation and Command Centers Where Inergen is Used Worldwide - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  28. Safe for People NO adverse effects on people. Contains a small amount of CO2 to stimulate the uptake of oxygen Does not create a fog ensuring that escape routes are always visible Safe for Property Harmless on physical assets like equipment furniture etc. Leaves no residue to clean up and does not produce any toxic by-products Safe for the Planet Inergen is as safe as the air we breathe! Easy on your Pocket Inergen will never be banned Central cylinder banking to protect multiple areas Naturally existing gases makes maintenance and refills easy 10 year Evergreen warranty takes all your problems away Inergen, The logical choice - Perfectly Safe for People, Property, the Planet…. and your Pocket!

  29. END ------ Your Safety Is Our Commitment -------- - Perfectly Safe for People, Property, the Planet…. and your Pocket!