HVAC Air Filtration Overview and Life Cycle Cost Case Study Garry Pangborn March 8, 2012 Freudenberg Filtration Technologies. The Air We Breath - Sizes of Common Particles. The Air We Breathe - Particle Size Distribution of Atmospheric Air.
E N D
HVAC Air Filtration Overview and Life Cycle Cost Case Study Garry Pangborn March 8, 2012 Freudenberg Filtration Technologies
The Air We Breathe - Particle Size Distribution of Atmospheric Air • The activities of modern society have greatly increased presence of sub-micron particles Primarily Naturally-Occurring Primarily Man-made Fine
The Air We Breathe – Health & Wellness Considerations • Every day, the typical adult in the U.S.: • Eats 3 lbs of food • Drinks 4 lbs of fluids • Breathes 35 lbs of air! • Particles are deposited into respiratory tract; the smaller the particle, the deeper it can reach • EPA estimates that people spend 90% of time indoors • Sick Building Syndrome, Building Related Illness, Pandemics • Productivity benefits of improved IAQ (Indoor Air Quality) • Increases in allergy and asthma cases nationwide • Increasing evidence that disease can spread via airborne routes (droplet nuclei)
The Air We Breathe – Dust Concentrations • What is the dust concentration in this room? • 10 to 50 μg/m3 • What is it in the extremes in the world? • Lowest recorded – Antarctica at 0.00001 μg/m3 • Highest recorded – Sandstorms at 4,000 to 6,000 μg/m3 • What is Urban Typical? • In the United States – 20 to 50 μg/m3 • In China – 300 to 500 μg/m3
Air Filtration Mechanisms Electrostatic Attraction Inertial Impaction (-) (+) Filter Fiber Brownian Diffusion Interception
Filter Efficiency - Filtration Mechanisms Working Together • Filter Efficiency is the combination of the various capture schemes • Sieving • Inertial impaction • Interception • Diffusion • Electrostatic attraction
Filtration Efficiency - What is MERV? Minimum Efficiency Reporting Value (MERV) • ASHRAE 52.2 standard • Classification system for filters based upon particle capture efficiency • Numerical designation between 1 and 16 ASHRAE 52.2 MERV Table LEED Point for MERV Level ≥13
Filter Pressure Drop and Energy • Energy consumption impact: Up to 30% of fan energy usage due to filter pressure drop Governing equation for how lower ΔP equates to lower energy usage: Q x ΔP x t Energy = η where… Q = volumetric flow rate ΔP = pressure drop t = time η = motor-fan efficiency Target operating zone.
Filter Pressure Drop and Energy Optimum Filter Change-out Timing Goal should be to change-out filters at the lowest point on this curve.
Filter Selection Criteria • Life cycle costs most important • Note difference in values between LCC and Initial Cost • Avoidance of catastrophic failures due to blowout or moisture are noteworthy • Fit and MERV naturally a key criteria • Vendor knowledge / service is valued
A Case Study in Energy and Life Cycle Cost Savings Case Study Background • Interest in energy savings and sustainability • Business and Aerospace Building, 3rd Floor • Pursued side-by-side energy consumption comparison study Business & Aerospace Bldg Single-stage 2-Stage System vs. Filter Installation • Side access housing • 4 rows of 20” tall tracks • 5 columns of filters 24” wide • Side-load gasketing • Two stages • 2” pleated pre-filter • 20”x24”x12” box filter • Single stage – no pre-filter • 20”x24”x20” pocket filter • 4 pockets per filter
A Case Study in Energy and Life Cycle Cost Savings Head-to-Head Pressure Drop Across Filter Banks Data courtesy MTSU
A Case Study in Energy and Life Cycle Cost Savings Illustration of Pressure Drop Comparison Across Filter Banks
A Case Study in Energy and Life Cycle Cost Savings Energy Monitoring • ABB variable frequency drives (VFD) • 30 HP motors • Hourly data logging of motor voltage and current for each air handler • Power data then tabulated in Excel Data Example (courtesy MTSU)
A Case Study in Energy and Life Cycle Cost Savings Energy Monitoring Results Data courtesy MTSU
A Case Study in Energy and Life Cycle Cost Savings Filter Pressure Drop Checks under Controlled Laboratory Conditions
Sustainability Impact – In Addition to Energy Reduction • Potential waste reduction on campus • Major reduction in filter usage • Pre-filters eliminated • 3x lifetime of typical box/cell filters Filter Qty: 300 20 93% potential reduction in usage over 3 yr period
Filtration Life Cycle Cost Reduction • Note importance of energy consumption • For every 0.1” w.g. reduction in P there is an energy savings of $17 per filter per year (@ $0.06 per kWh) Initial Filter Costs Operating Costs • Case Study Total Cost of Ownership Impact (over 3 years) • Energy Cost 44% • Filter Cost 54% • Labor Cost 86% • Overall 50%
Additional University Case Studies Additional Example #1 Southeast Additional Example #2 - Midwest Additional Example #3 Northeast • V-bank Type Filter (no pre-filter) • Filter dP at 30 months of service: 0.68” w.c. (new 0.28” w.c.) • Case study presented at 2010 MIAPPA summer conference: www.fm.wmich.edu/miappa/conf/s10/index.html • Pocket Filter (no pre-filter) • Filter dP after 24 months of service: 0.24” w.c. (new = 0.20” w.c.) • Pocket Filter (no pre-filter) • Filter dP after 40 months of service: 0.29” w.c. Previous Incumbent: Pre-filters: changed quarterly Final filters: changed every 12-18 months Previous Incumbent: Pre-filters: changed quarterly Final filters: changed annually Previous Incumbent: Pre-filters: changed quarterly Final filters: changed every 12-18 months
Greenguard Certification Check air filters for certification • 3rd party qualification • Assesses emissions of VOC’s (i.e. formaldehyde) • Evaluates product for mold/fungi growth Greenguard Certificate of Compliance
Trends in Air Filtration Market • Elimination of roll filters • Consolidation of 2-stage pleated filter + box filter to long-life pocket technology or V-bank filters • Higher efficiencies (LEED - MERV 13) • End-user focus on energy conservation (lower dP filters) • End-user focus on life cycle costs • End-user focus on sustainability and less waste • Growth of synthetic media filters vs. glass due to: • Lower cost • Moisture resistance • Lower VOC emissions • Ultraviolet (UV) lights used in conjunction with air filters to help keep heat transfer coils ultra clean • Nanofiber filter media • Glass fiber shedding • More puncture resistant • Installer friendly (skin contact)