AE Senior Thesis 2009 U.S. Pharmacopeia Headquarters Consolidation Rockville, MD

AE Senior Thesis 2009 U.S. Pharmacopeia Headquarters Consolidation Rockville, MD. Analysis and Design of a Mild Reinforced One way slab with Post Tensioned Beams. Jeffrey L. Rothermel Jr. The Pennsylvania State University Department of Architectural Engineering Structural Option.

erol
Download Presentation

AE Senior Thesis 2009 U.S. Pharmacopeia Headquarters Consolidation Rockville, MD

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. AE Senior Thesis 2009 U.S. Pharmacopeia Headquarters Consolidation Rockville, MD Analysis and Design of a Mild Reinforced One way slab with Post Tensioned Beams Jeffrey L. Rothermel Jr. The Pennsylvania State University Department of Architectural Engineering Structural Option

  2. Discussion Topics • Background Information • Existing Structure • Design Goals • Project Stages and Process • Structural Design • Mechanical Ductwork Redesign AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  3. U.S. Pharmacopeia Headquarters • Owner: U.S. Pharmacopeia • Architect: Hellmuth, Obata + Kassabaum (HOK) • Structural: Cagley & Associates Inc. • MEP: R.G. Vanderweil Engineers • Construction: DPR Construction Inc. • 6 stories - 91’ • 191,000 ft2 of new office and lab space • New 19,000 ft2 conference center • Houses chemical and biological labs • $69 million AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  4. U.S. Pharmacopeia Headquarters • Showcase laboratory spaces • Large open office plans • Kitchenettes for employees at every floor • Curtain wall, metal paneling, and beige split face CMU • Conical auditorium with curtain wall skin • Enclosed outdoor plaza space AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  5. Existing Conditions • Two way mild reinforced concrete • flat slab with drop panels • 22’x22’ column grid • 14’ floor-to-floor heights (Typ.) • Reinforced concrete moment frames • Steel framed conference center • Truncated, conical concrete auditorium Photo courtesy of HOK Inc. Photo courtesy of HOK Inc. Photo courtesy of HOK Inc. AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  6. AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  7. Design Goals • Lower floor-to-floor heights from 14’ to 13’ • Increase column grid from 22’ to 44’ • Eliminate moment frames • Reduce ductwork sizes • Maintain existing ceiling height AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  8. Design Stages • Investigate 3 alternatives • Choose optimum system • Design chosen floor system • Design matching lateral system • Resize ductwork mains AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  9. Possible Solutions Taken From AISC Design Guide 14: Staggered Steel Truss Framing Staggered Steel Truss system Two way post tensioned slab One way slab with post tensioned beams AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  10. Structural Depth Design Design Process • Lay out beams • Design slab system • Design post tensioned beams • Size • Tendon quantity • Drape • Column check • Design shear walls • Shear reinforcement • Flexural reinforcement • Coupling beams AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  11. One way slab with PT beam design New Beam Layout AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  12. One way slab with PT beam design • Slab Design • One way reinforcing • 7” slab typ. • 7-1/2” slab at 250 psf loading • #5 bars T&B • #5@ 24” for shrinkage and temperature parallel to beams AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  13. One way slab with PT beam design Designed with RAM Concept per ACI 318-02 • Spans extended to 44’ • Shallow wide beams • Existing column size kept (24”x24”) • F’c = 6000 psi • Class T Transitional • T-Beam properties • #6 Bottom at ρmin= 0.004 • #5 Top with no minimum reinforcement • 0.6f’ci compression limit (18.4.1(a)) • 7.5√f’c ≤ft ≤ 12√f’c tensile stress limit (18.3.3) AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  14. One way slab with PT beam design Design Process Size the beams Add tendons Check stresses Adjust profile Schedule AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  15. One way slab with PT beam design • Interior beams typically 48”x14” • Edge beams typically 30”,32”x14” • 40-60 tendons interior typically • 30-40 tendons in edge typically AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  16. One way slab with PT beam design • Transfer Girders • 16-30” deep at transfers • 48-56” wide at transfers • Same depth as existing transfers • 20-50% more post tensioning AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  17. One way slab with PT beam design Load Balancing • Balance % of dead load • Target balance 60-90% • Target met in most beams • A few beams overbalanced • Some underbalanced AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  18. One way slab with PT beam design • Existing Column Properties • Checked using PCA Column • Moments from RAM Concept at column • Interior columns sufficient • Exterior columns require increased rebar • Required for increased moment • 8#9 12#9 AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  19. Shear Wall Design Existing reinforced concrete moment frames AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  20. Shear Wall Design AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  21. Shear Wall Design Load Determination • Method 2 per ASCE 7-05 • 4 wind cases investigated • Seismic loads using Equivalent Lateral Force Method • 18” trial thickness • 1.6W vs. 1.0E Taken From ASCE 7-05 AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  22. Shear Wall Design • Shear reinforcement as required per Sec. 11.9 • Each wall/segment designed for shear and flexure separately • Minimum shear reinforcing used • None needed for shear strength • #4s H,V @18” Typ. • Moment controlled reinforcing designs • #8s Vert. for flexure AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  23. Shear Wall Design • Deflections in SAP • 8” Membrane • Self mass included • 24” mesh • Full I values for all members • F’c = 3000 psi • Wind limitation H/400 • Seismic limitation 0.02hxn AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  24. Shear Wall Design • Coupled shear wall design • SAP • Member self weight included • 8” Membrane • Coupling beams extend into wall face • 2’ Rigid end offset • 48” deep beams • Coupling beams as deep beams • per Sec. 21.9.7 • Designed per Sec. 10.7 • Shear reinforcement per Sec. 11.7 AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  25. Mechanical Ductwork design • Design Goals • Keep loss under .25” WC/100’ • Keep fpm flow under 2500 in mains over occupied spaces • Reduce height and increase width AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  26. Mechanical Ductwork Redesign First Floor AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  27. Mechanical Ductwork Redesign • Vertical mains shrunk 8-20” per side • Maximum horizontal run that travels under beams is 20” • Minimum ceiling height is 8’10” • Average ceiling height can be +10’6” AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  28. Some Quick Costs • Savings on façade and ductwork • More expense on structure AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  29. Project Summary • Post tensioned beam system provides optimal performance • Wide shallow beams incorporate desired attributes into floors • 48”x14” for most interior beams and 30”x14” for most exterior • 8” shear walls designed for moment • Mechanical ductwork redesigned to obtain project goals • Savings on façade and mechanical ducts, more cost in structure • All goals reasonably attained AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option

  30. Questions/Comments AE Senior Thesis 2009|U.S. Pharmacopeia Headquarters|Jeffrey L. Rothermel Jr.|Structural Option