An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Chapter 18 HVAC Control Systems Building Automation System Installation, Wiring, and Testing

  2. Building Automation System Installation and Wiring • Building BAS Installation requires: 1. Proper controller mounting 2. Power supply selection 3. Network configuration 4. Testing techniques

  3. BAS Installation & Wiring • All BAS controllers should be wired in accordance with the National Electric Code (NEC) • Manufacturer recommendations should followed regarding testing and diagnostic procedures.

  4. Controller Mounting • Proper mounting is necessary to prevent controller damage. • Controller mounting methods vary from manufacturer to manufacturer. • In many applications the controller can be mounted in the existing pneumatic control panels. • Many manufacturers recommend DIN rail mounts. • DIN rail is a flat mounting rail that is attached to a control panel.

  5. Controller Mounting Requirements • BAS mounting requirements vary due to the wide range of manufacturers. • Exterior mounted control panels require a panel to which can protect against weather damage. • Many BAS are equipped with an operator interface that provides maintenance personnel with the ability to view controller functions and status. • Operator interfaces require installation 60” above the finished floor. • Operator interfaces are positioned in areas away from view, to prevent tampering. • Proper sizing of control panels are mandatory. • A location should be selected carefully as to reduce the conductor runs as much as possible.

  6. Common BAS Controller Mounting • Separate BAS controller conductors and power conductors by at least 1’. • Wire BAS controller connections using copper conductors of 18-gauge to 24-gauge. • Run network field conductors and line-voltage conductors and line voltage conductors of 30 VAC or higher in separate conduits.

  7. Controller Power Supplies • The most common power supply for BAS is a 120 VAC to 24 VAC step-down transformer. • Minimum wire size for BAS controller supply is 18-gauge, stranded, copper with a ground. • BAS controller power supplies use plug in plastic connectors or spade terminations.

  8. Power Supply Sizing • In most cases the BAS controller manufacturer recommends sizing for power supplies. • Size can be determined by adding the power requirements of the components. • A 100 VA transformer is the single largest transformer used in a BAS.

  9. Building Automation Systems Most buildings about 90% have only one primary desktop PC, have only one front-end. BAS changes may be temporary or permanent. New points can be added, old points deleted, and reconfigure system based on operator access levels.

  10. Controller Power Supply Isolation • Power supply isolation from ground is necessary to prevent ground loops, which cause improper controller operation. • Ground loop is a circuit that has more than one point connected to earth ground, with a voltage potential difference between 2 ground points can be high enough to produce a circulating current in the ground system.

  11. Controller Power Supply Polarity • Correct transformer polarity is necessary because the sensors and outputs are designed to operate properly with the correct polarity. • The 2 leads are labeled 24 VAC and common and should be properly connected.

  12. Package Unit Power Supplies • Package units such as rooftops and heat pumps have a built in power supply. • These built in power supplies are often used to power BAS controllers. • Isolation of the transformer should also be checked to ensure proper grounding. • A ground connected transformer cause the controller device to become grounded which can cause damage to the controller and the operator interfaces connected to the controller.

  13. Sharing Controller Power Supplies • In some buildings larger transformers can power multiple controllers. • The use of one transformer eliminates the need for multiple small transformers. • Is often recommended when multiple controllers are located very close together. • The disadvantage of sharing a power supply between multiple controllers is if the transformer fails multiple controllers fail.

  14. Controller On-board Batteries • BAS have an onboard battery for retention of memory and clock functions. • The battery is normally disconnected during shipping to prevent discharging of the battery.

  15. Communication Network Wiring • The network wiring allows controllers and other BAS devices to communicate with each other. • The information that is transmitted across the network may include the sharing of temperatures, time scheduling information, and alarm

  16. Conductor Type • The RS-485 communication standard requires a 2-conductor shielded cable or 3-conductor twisted shielded cable. • The minimum conductor size for BAS controllers is 22-gauge. • A 20 or 18-gauge conductor is recommended over 22-gauge because the possibility of wire kinking. • Color coding is recommended to ensure that the correct conductors are terminated in the correct position on the controller. • The RS-485 communication port comes standard polarity-sensitive.

  17. Shielding and Grounding • Shielding reduces the effects of electromagnetic interference on communication network wiring. • Electromagnetic interference is are caused by the operation of large motors, compressors, high voltage wiring, and lighting loads restrictions. • Electromagnetic interference is reduced by keeping communication network wiring away from large motors, compressors, high-voltage wiring.

  18. Optoisolation • It is communication method in which controllers use photonic components to prevent communication problems. • Is communicated through hard wired runs. • The binary (0 or 1) information transmitted is converted to an optical signal that is processed by the controller. • The BAS controller is isolated from the controller is isolated from the communication network because there is no physical connection between them, reducing or eliminating communication problems.

  19. Network Configurations • Daisy chain network configuration – multiple controllers are connected in series. Chains together a multiple number of BAS controllers and avoids using wiring splices. • Multi-drop network configuration – controllers are connected to the network that runs throughout a building and spliced drops are made for each controller. • Star network configuration – communication network cables run from the center out to the controllers.

  20. Network Addressing • It is a unique number assigned to each BAS controller. • This is done using a set of dip switches • 1,2,4,8,16,32,64,& 128.

  21. Input & Output Wiring • Input wiring brings information into the BAS either analog (incremental) or digital (ON/OFF). • Output wiring are take a control signal from the controller t a controlled device. • Peripheral devices are connected to a PC and perform a specific function. • Serial device transmits one bit of information (0 or 1) at a time. • Parallel device transmits multiple bits of information (0s or 1s) at a time. • Dumb terminal is a display monitor and keyboard with no processing capabilities.