ATMOSFERSKA PRAŽNJENJA U NADZEMNE VODOVE

ATMOSFERSKA PRAŽNJENJA U NADZEMNE VODOVE. Nadzemni vodovi se dele u tri grupe. Vodovi sa čelično-rešetkastim ili armirano-betonskim stubovima bez zaštitnog užeta, Vodovi sa čelično-rešetkastim ili armirano-betonskim stubovima sa zaštitnim užetom,

fulton-odom
Download Presentation

ATMOSFERSKA PRAŽNJENJA U NADZEMNE VODOVE

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ATMOSFERSKA PRAŽNJENJA U NADZEMNE VODOVE

  2. Nadzemni vodovi se dele u tri grupe • Vodovi sa čelično-rešetkastim ili armirano-betonskim stubovima bez zaštitnog užeta, • Vodovi sa čelično-rešetkastim ili armirano-betonskim stubovima sa zaštitnim užetom, • Vodovi sa drvenim stubovima bez zaštitnog užeta.

  3. Vrste pražnjenja u vodove • Direktno pražnjenje u fazni provodnik, • Pražnjenje u vrh stuba ili u zaštitno uže koje izaziva preskok preko izolacije ka faznom provodniku (povratni preskok), • Pražnjenje u okolinu voda koje izaziva indukovane prenapone na faznim provodnicima.

  4. Preskok na izolatoru sa zaštitnom armaturom

  5. Uloga zaštitne armature • Tačno definiše nivo preskočnog napona, • Omogućava ravnomerniju raspodelu potencijala duž izolatorskog lanca, • U slučaju preskoka udaljuje električni luk od površine izolatora, sprečavajući na taj način njegovo termičko uništenje

  6. Pražnjenje u fazu

  7. Pražnjenje u zaštitno uže

  8. Iz=Ig/2-Is Ig /2 Is UL=L(dis/dt) Ur=Ruz Is Povratni preskok pri udaru u zaštitno uže Ig Uk=RuzIs+L(dis/dt)

  9. Iz=0.1Ig Iz=0.1Ig Is=0,8Ig Povratni preskok pri udaru u vrh stuba Ruz

  10. Oblik struje pražnjenja I(kA) Im Tč t(ms) 0

  11. Model Ekvivalentna šema Lst Lst Ig(t) Ruz Ruz Vremenski oblik napona-šema sa koncentrisanim parametrima

  12. Analitički oblik napona Za slučaj talasa kosog čela

  13. Napon na fazi Napon na konzoli Tc Vremenska promena napona u(t) Tp t( s)

  14. Uticaj trenutne vrednosti radnog napona na ukupan napon koji napreže izolaciju

  15. Primer povratnog preskoka u 35kV mreži • Struja groma Ig=60 kA • Struja kroz stub Is=0.8 Ig= 48 kA • Vreme čela Tč=2 ms • Induktivnost stuba lst=0.5mH/m • Visina stuba H=15 m • Ukupna induktivnost Lst= lstH=7.5 mH • Otpornost uzemljenja Ruz=5 W • Uk= 5  48 + 7,5  48/2=240+180=420 kV Uk=420 kV> 170 kV za 35 kV sistem

  16. C kapacitet izolatora i C Kapacitet drveta d R Otpor drveta d C i C R d d Ekvivalentna šema Pražnjenje u vod na drvenim stubovima Skica voda

  17. Ukupan napon na izolatoru i stubu pre preskoka Napon na drvenom stubu posle preskoka Preskok na izolatoru Proboj drvenog stuba Napon na drvenom stubu pre preskoka Pad napona na luku Vremenska promena napona pri pražnjenju u drveni stub

  18. Skica pražnjenja pored voda v h Y x

  19. Procena visine prenapona h b • Gde je: • K -empirijska konstanta k=3060 usvajamo 30 • Im-amplituda struje • h - visina provodnika • b- udaljenost mesta udara od provodnika

  20. Primer procene • Visina faznog provodnika 10 m • Udaljenost mesta udara 50 m • Ampituda struje groma 100 kA • Empirijski koeficijenat 30 • Mreža nazivnog napona 10 kV, podnosivi udarni napon 75 kV • Izračunati prenapon

  21. Greška u proceni indukovanih prenapona • Dominantan uticaj ima strmina struje groma, a manji uticaj amplituda

  22. Atraktivna zona voda Ae Stub Atraktivna zona stuba Procena broja preskoka na 100km u toku 1 god n100km,god = ng Ae 100 P(x) ng-gustina pražnjenja po km2

  23. Pražnjenje mimo zaštitnog užeta a

  24. PP PMU PMU PP Detektor načina pražnjenja

  25. Poslednji skok skokovitog lidera Rud=k Ia Udarno rastojanje Rud

  26. Udarno rastojanje a = R KI ud K=6-10 a=0,65-0,8

  27. Pražnjenje u uže Pražnjenje u fazu Atraktivna površina faze Rud Elektrogeometrijski model 1 Rud1=k I1a

  28. Pražnjenje u uže Atraktivna površina faze Rud Elektrogeometrijski model 2 Rud2=k I2a I2>I1 Rud2>Rud1

  29. Atraktivna površina faze Rud Elektrogeometrijski model hipoteza o usmeravanju skokovitog lidera P= / P=verovatnoća pražnjenja mimo užeta 

  30. Mogućnosti preskoka usled pražnjenja mimo užeta • Podnosivi napon izolacije Uiz • Napon na fazi usled struje groma Ig • Uiz>Uf uslov da ne dođe do preskoka • Granična struja mimo užeta

  31. Primer • Rud=7.5 Ig0.8 • Nazivni napon 110 kV • Podnosivi napon Uiz=550 kV • Karakteristična impedansa faze Zf=400 W • Granična struja Ig=4550/400 kA=5,5 kA • Udarno rastojanje Rud=7.53.9=29.25 m • Sa dobijenim udarnim rastojanjem i dimenzijama stuba proveri se uslov pražnjenja mimo užeta

  32. Grafičko određivanje uslova pražnjenja mimo užeta 29,25 Hz=15m, hf=10m