An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CB Series Fast Recharge Enhanced Performance Optimized Battery Life • Proteggono le batterie • Ne esaltano le prestazioni • Ne preservano la durata nel tempo The New Battery Charging Philosophy I Carica Batterie cambiano filosofia www.adelsystem.com battery care

  2. Mission Protect and Enhance your investment over time Complete battery management

  3. The CB series is a new range of battery chargers based on two strategic know-how elements: Switching technology Adel system has a 20 year experience in design of advanced stabilized switching technology power supplies. A battery charger based on this technology is much more efficient and much smaller and lighter than traditional linear technology battery chargers. Micro-processor and Battery Care Unlike most other state-of-the-art battery chargers, the CB series is equipped with a micro-processor which controls the charging process and enables several monitoring functions. The firmware implements the extended Adel battery care know-how, result of many years of experience in this field Technology

  4. Available Models • Input: 110 – 230 Vac • Out: 12 Vdc • CB123ALC • CB123A • CB126A • CB1210A • Input: 110 – 230 Vac • Out: 24 Vdc • CB243A-LC • CB243A • CB245A-C • CB2410A • CB2410AC

  5. Setting of charging current • Setting is possible in the range 20% - 100% of rated current • Not available on LC versions

  6. Visual Signals • Clear indication of operation status via LED signaling “Battery Fault” Led Two function Led : • Type of Charge • CB System Auto Diagnostic

  7. Battery Contact Signals • CB chargers indicate battery status and faults also via changeover contacts with galvanic isolation. Battery fault NO–NC Output Changeover Contacts • Not available on LC versions

  8. Three charging levels CB battery chargers features three charging levels. • Boost (also known as fast charging) • Trickle (also known as float or maintenance charging) • Recovery The active charging mode is displayed by anLED on the front panel Boost Trickle Recovery

  9. V batt I max V batt LED display of charging mode Boost (fast) 2 flashes per sec. Trickle 1 flash per sec. Recovery 5 flashes per sec. Mode switching occurs automatically

  10. Battery V batt Recovery charging • CB can recharge batteries even when their voltage is close to zero. It allows recharge and complete recovery of flat batteries. Typical charging curve for recovery of batteries with voltage close to zero

  11. Protections • The output is protected against short circuit and overload • Protection against deep battery discharge • Protection against reverse polarity connection

  12. Battery Diagnostic checks • Check for elements in short circuit • During trickle charge the quality (resistance) on the battery connection is checked every 20 sec • Appropriate voltage check, to prevent connection of wrong battery types • End of charging check • Check for accidental disconnection of the battery cables • Reverse polarity check

  13. BatteryDiagnostic • An LED flashing sequence code allows to discriminate among various possible faults. 1 flash = Reverse polarity, wrong battery voltage 2 flashes= Disconnected battery. 3 flashes= Battery element in short circuit 5 flashes= Battery to be replaced.

  14. Battery Battery life test • The smart features overviewing battery charge status and life test diagnostics ensure high efficiency and risk-free operation • A pulse stimulation is sent to the battery by a specific circuitry. The electric signal received back in response is analysed by evaluation algorithms able to discriminate cable disconnected, sulphated battery conditions or cells in short circuit. Pulse stimulation and assessment of battery status Cell in short circuit

  15. Ready for charging most battery types … Jumper for Battery Type Selection

  16. … Ready for charging most battery types Jumper positions / VPC: • Open Lead Acid: Trickle 2.23V Boost 2.40V • Sealed Lead Acid (1): Trickle 2.25 Boost 2.40V • Sealed Lead Acid (2): Trickle 2.27 Boost 2.40V • Gel: Trickle 2.30V Boost 2.40V • Optional: Ni/Cd