1 / 24

GROUND-MED PROJECT Data Acquisition Hardware and Software Anibal T. De Almeida

GROUND-MED PROJECT Data Acquisition Hardware and Software Anibal T. De Almeida Andre Quintino Duarte Coimbra, 25 February 2010. Global Data Acquisition. Septemes les Vallons, France. Sensors. DAQ. FTP. Oradea, Romania. Sensors. DAQ. FTP. FTP Server. Coimbra, Portugal. Sensors.

gari
Download Presentation

GROUND-MED PROJECT Data Acquisition Hardware and Software Anibal T. De Almeida

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. GROUND-MED PROJECT Data Acquisition Hardware and Software Anibal T. De Almeida Andre Quintino Duarte Coimbra, 25 February 2010

  2. Global Data Acquisition Septemes les Vallons, France Sensors DAQ FTP Oradea, Romania Sensors DAQ FTP FTP Server Coimbra, Portugal Sensors DAQ FTP Benedikt, Slovenia Sensors DAQ FTP Valencia, Spain Sensors DAQ FTP Barcelona, Spain DAQ FTP Sensors Padova, Italy Sensors DAQ FTP Athens, Greece DAQ FTP Sensors

  3. Single Data Aquisition Sensors: - Flow - Temperature - Electrical Power - Thermal Power - Solar Radiation Data Management System FTP File DAQ

  4. DAQ schematic

  5. NI cRIO-9074 • Processor: 400 MHz RT • Internal Storage: 256MB • DRAM: 128 MB • Ethernet Port(s): 2 • Operating Temperature: -20 to 55 C • Number of Slots: 8 • NI 9144 expansion chassis to expand I/O module selection beyond 8 slots

  6. 4-Port RS485 Serial Module Overview The NI 9871 C Series serial module adds four RS485/RS422 serial ports. • Maximum baud rates 3.6864 Mbps; • Maximum cable length 1.2 km. • Electric Power (Carlo Gavazzi); • Thermal Power (Brunata).

  7. NI 9219 - 24-Bit Universal Analog Input • 250 Vrms channel-to-channel isolation • Built-in quarter, half, and full-bridge support • Built-in voltage and current excitation • Thermocouple, RTD, resistance, voltage, and current measurements • CJC per channel for accurate thermocouple measurement • 100 S/s/ch simultaneous inputs (50S/s/ch for Thermocouple) • LI-COR Pyranometer

  8. NI 9217 – 4-Channel 24-Bit RTD Analog Input • 250 Vrms channel-to-channel isolation • Built-in current excitation • RTD measurements • High-resolution mode 0.003 ºC • Indoor JUMO PT100; • Outdoor JUMO PT100.

  9. Mandatory Variables I

  10. Mandatory Variables II

  11. Other Variables I

  12. Other Variables II

  13. Ambient and Room Temperature Sensors Jumo RTD Indoor / outdoor temperature sensor(PT100) - for temperatures from -30 to +80°C (200°C) - for use in HVAC - IP20 to IP65 protection - for 2-wire, 3-wire or 4-wire connections - fitted transmitter option 4 – 20mA or 0 – 10V

  14. LI-COR - Solar Radiation Sensor About 200 € Li-COR LI200SZ - silicon photovoltaic detector -Current output, which is directly proportional to solar radiation -Calibrated against an Eppley Precision Spectral Pyranometer (PSP) under natural daylight conditions in units of watts per square meter (W m-2) -Under most conditions of natural daylight, the error is < 5% (2). -Output - Typically 90 µA per 1000 W m-2

  15. Carlo Gavazzi - Energy Meter Type EM21 72D Main Outputs: Currents (A); Voltages (V); Apparent power (VA); Active power (W); Reactive power (var). Communication through a RS485 communication port Compressor, Circulators, Fan Coils, HP Controls (?)

  16. Brunata - Thermal Energy Meter Overview • Flow meter; • Two Liquid Temperature meters; • RS-485 Communication • Max. Flow16.5 m/h (HGP 15); • Max. Liquid Temperature 120 ºC (HGP 15). 3

  17. Thermal Energy Consumption Tin_ci (C) Tout_ci (C) Q (m3.s-1) Q (W) Q.t (Wh) Brunata HGQ Energy Meters

  18. Brunata – Flow Sensor Technology Michael Faraday’s physical law about induction Water is the conductor This principle allows for measuring range better than 1000:1

  19. Brunata – Components of a Heat Meter Flow sensor 2 temperature sensors Calculator with display

  20. Brunata – Calculation of Heat Energy E – Energy consumed in a period of time; V – Water volume passing through the meter in same period; – Average temperature difference between flow and return in the system; k – Correction factor for heat enthalpy and the volume mass at the temperature measured.

  21. Software

  22. Software

  23. Output file The data acquired by all these devices will be processed every minute into a string buffer and after 10 minutes the last 10 buffered strings will be updated into a FTP file trough the Internet. To create this string, the application will also read the cRIO-9074 board date and time to complete all the required parameters.

  24. Output file Data String (1 minute) 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; Data Buffer (10 minutes) 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; 06/12/2010 0:01;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;0;no;yes;no; FTP (Old File) FTP (New File)

More Related