An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Local Law 87/09Energy Audits & Retro-commissioning

  2. Energy Audits & Retro-commissioning of Base Building Systems in Covered Buildings What is Local Law 87/09?

  3. Implementation & Enforcement • NYC Department of Buildings is responsible for implementation and enforcement • Filing Fees for: Initial EER Submission/Deferral : $375 Extension Request : $155 Amendment : $145 Registering as an Approved Agent: $200 each (EA and Retro-Cx) • Failure to comply with LL87/09 subjects properties to fines of $3,000 the first year and $5,000 for each additional year

  4. What is a Covered Building? Check the Covered Buildings List and Department of Finance Tax Bills to determine if a property needs to comply • A single building on a lot over 50,000 square feet • 2 or more buildings on the same tax lot that together are more than 100,000 square feet • 2 or more buildings held in condo ownership that together are more than 100,000 square feet Sample list of Properties Covered by LL87/09

  5. What are Base Building Systems? • HVAC (Heating, Ventilation and Air Conditioning) • Electrical and Lighting • Domestic Hot Water • Building Envelope • Conveying Systems

  6. Exemptions, Exceptions, Deferrals, Extensions Exemptions: Energy Efficiency Report (EER): • Building owners do not have to file if the building is classified as Class 1 pursuant to subdivision 1802 of the real property tax law of the state of New York (1, 2, or 3 family dwellings that are not condominiums or 1, 2, or 3 family condos of 3 stories or less – status should be indicated on your tax bill from the Department of Finance)

  7. Exemptions, Exceptions, Deferrals, Extensions Exceptions: Conducting an Energy Audit: • Building owners need not conduct an energy audit if: • The building has received an EPA Energy Star label for at least 2 of the 3 years preceding the filing of the building’s Energy Efficiency Report (EER)* • The building has received LEED Certification within 4 years prior to the filing of the building’s EER* • The building is a SIMPLE BUILDING and 6/7 of the items listed in the law are satisfied (This only applies to the building’s first EER filing.)* Simple Building: No central cooling or chilled water system *Certified by an RDP

  8. Exemptions, Exceptions, Deferrals, Extensions Conducting Retro-commissioning: • Building owners do not have to conduct retro-commissioning if: • The building has received LEED Certification within 2 years prior to the filing of the building’s EER AND • The building has earned the LEED point for Existing Building Commissioning investigation and analysis AND • The building has earned the LEED point for Existing Building Commissioning implementation

  9. Exemptions, Exceptions, Deferrals, Extensions Deferral of filing an EER: • Building owners can defer filing until the next filing year for a building (ten years) if: • The building is less than ten years old, AND/OR • The building has substantially changed its base building systems AND • The building can demonstrate that it meets the energy code as in effect • for new buildings constructed on or after July 1, 2010 OR • as in effect at the time the building was built/altered, whichever is later

  10. To Demonstrate Energy CodeCompliance DOB website • Codes & Reference • Energy Code Guidelines • Energy Analysis How To Guide

  11. Exemptions, Exceptions, Deferrals, Extensions Extension of time to file an EER: • Building owners must file by Oct 1st of their reporting year • Financial Hardship (one year – may be renewed annually) • Property taxes in arrears within 2 years prior to filing of EER on the DOF’s annual New York City tax lien sale list • Exempt from real property taxes pursuant to sections 420-a, 420-b, 446 or 462 of the real property tax law • Had outstanding balances under the Department of Housing Preservation and Development’s Emergency Repair Program that resulted in the property’s inclusion, within 2 years prior to filing of EER, on the DOF’s annual New York city tax lien sale list • Has an active or effective commitment letter from a governmental agency that provides for the financing of the rehabilitation, within a period of 5 years or less, for the purposes of affordable housing for low or moderate income families • Good Faith Effort (one year – may only be granted twice) • One Example: Hurricane Sandy wiped out base building systems, so unable to complete LL87 work

  12. Who can do this work? • NYS Registered Design Professionals (PE or RA) can act as the Auditor and/or Retro-cx Agent if they have the required certification(s) OR they can supervise a team that has an individual with the required certification(s) • For retro-cx, a certified Refrigerating System Operating Engineer or a licensed High Pressure Boiler Operator can be substituted for the RDP • Non-Registered Design Professionals (not a PE or an RA) can act as the Auditor and/or Retro-cx Agent if they have the required certification(s) AND they have registered with the Department of Buildings The energy auditor or retro-cx agent performing or supervising may not be on the staff of the building being audited/retro-commissioned

  13. Energy Auditor Certifications(RDPs or those on RDP team) • NYSERDA approved Flex-Tech consultant • CEM or CEA– Certified Energy Manager/Auditor (AEE) • HPBD – High Performance Building Design Professional (ASHRAE) • BEAP – Building Energy Assessment Professional (ASHRAE) • MFBA – Multifamily Building Analyst (BPI) – for multifamily audits only!

  14. Retro-cx Agent Certifications(RDPs or those on RDP team) • CCP-Certified Commissioning Professional (BCA) • CBCP-Certified Building Commissioning Professional (AEE) • EBCP-Existing Building Commissioning Professional (AEE) • CPMP-Commissioning Process Management Professional (ASHRAE) • ACPAP-Accredited Commissioning Process Authority Professional (Univ. of Wisconsin)

  15. Required Certification(s) for Non-RDPs Who Register with the Department • To perform energy audits: • CEM/CEA from AEE • HPBD from ASHRAE • BEAP from ASHRAE • MFBA from BPI (for multifamily audits only) • To perform retro-commissioning: • CCP from BCA • CBCP from AEE • EBCP from AEE • CPMP from ASHRAE

  16. What is an EER? An Energy Efficiency Report (EER) is the report required to be filed pursuant to section 28-308.4. An EER includes: • EERC1 (Professional Certification: Energy Auditor and Owner Statements) form • Energy Audit Workbook • EERC2 (Professional Certification: Retro-commissioning Agent and Owner Statements) form • Retro-commissioning Workbook

  17. What is the process for submitting an EER? Building owners need to submit by 12/31 of the building’s filing year • The filing year is the calendar year that coincides with the last digit of the building’s tax block number • Hire a professional to conduct energy audit and retro-commissioning activities Allow enough time for a service provider to complete the work • Complete the EA Professional Certification Form (EERC1) and EA Reporting Workbook and the Retro-cx Professional Certification Form (EERC2) and the Retro-cx Reporting Workbook • Submit the four parts of the EER via email to LL87@buildings.nyc.gov

  18. Submission Process (cont.) • DOB Sustainability Auditors will perform an initial review of the submission for completeness and will issue preliminary comments • An email request for payment will also be sent • Mail in payment (as described in the email) and respond with a resubmittal to any of the comments • For help, consult: • Service Notice • How to File an Energy Efficiency Report Guide • Example Tools (EA & Retro-cx) • Randomly-selected properties will have comprehensive reviews of the actual audit and retro-commissioning full reports (10 days to provide the reports)

  19. LL87/09 Webpage http://www.nyc.gov/html/dob/html/sustainability/energy-audit.shtml Main Source of Information from DOB

  20. QUESTIONS? LL87Questions@buildings.nyc.gov

  21. Greener, Greater Buildings Laws • LL85/09 – NYC Energy Conservation Code • Plan review team in place • All new buildings, including Pro-Cert applications, and ramping up to include major alterations • Randomly selected minor alterations, post-approval • Inspector visiting residential & commercial buildings during construction, will issue violations

  22. Greener, Greater Buildings Laws • Updated Energy Code (IECC 2012/ASHRAE 90.1/NYS Additions/NYC Local Laws) to become effective later in 2014 • New code requires: • Blower door testing on all residential buildings, • Energy modeling will have to be 15% better than code, • 30% max fenestration unless daylight dimming (then 40%) • Skylights required in certain areas/ building types • ERV/DCV/economizer required in more applications • Occupancy sensors in many more locations • Overall lighting/HVAC more efficient and higher R-values

  23. Greener, Greater Buildings Laws • LL88/09 – Lighting Upgrades & Sub-Meters • Affects non-residential (commercial) buildings • Aimed at making tenants aware of electrical consumption • Same criteria of applicability as LL87/09 (buildings over 50,000 sf, etc.)

  24. Greener, Greater Buildings Laws • Required Upgrade of Lighting Systems • Has to comply with the standards required for new systems, including: • Lighting controls (interior lighting controls, light reduction controls and automatic lighting shutoff) • Tandem wiring • Exit signs • Interior lighting power requirements • Exterior lighting

  25. Greener, Greater Buildings Laws • Compliance documentation has to be submitted on or prior to January 1, 2025 • DOB will begin rolling out the program so that buildings can comply earlier (stay tuned) • Rule pending

  26. Greener, Greater Buildings Laws • Lighting and/or Sub-metering Report to be filed by: • Registered Design Professional, or • Licensed Master or Special Electrician • Certifying that such upgrade has been completed and that the work is in compliance with the technical standards of the New York city electrical code. • Certifying that sub-meters have been installed in all covered tenant spaces in such building as required

  27. Greener, Greater Buildings Laws • Exceptions: • An element of a lighting system that is in compliance with the standards of the New York city energy conservation code and/or applicable standards referenced in such code as in effect for new systems installed on or after July 1, 2010 • Lighting power densities in any space bounded by permanent floor-to-ceiling partitions and/or closeable doors that are in compliance with the standards of the New York city energy conservation code and/or applicable standards referenced in such code as in effect for new systems installed on or after July 1, 2010

  28. Greener, Greater Buildings Laws • Exceptions: • Lighting systems within dwelling units classified in occupancy group R-2 or R-3 or spaces serving such dwelling units, including but not limited to, hallways, laundry rooms, or boiler rooms • Lighting systems within a space classified in occupancy group A-3 that is within a house of worship

  29. Greener, Greater Buildings Laws Sub-meters • Covered tenant space • Larger than 10,000 gross square feet on one or more floors of a covered building let or sublet to the same person • A floor of a covered building larger than 10,000 gross square feet consisting of tenant spaces let or sublet to two or more different persons