Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system

Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system. ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E. & Jae-Weon Jeong, Ph.D. Architectural Engineering Department Penn State University, @ Univ. Park, PA.

gerda
Download Presentation

Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005Stanley A. Mumma, Ph.D., P.E. &Jae-Weon Jeong, Ph.D.Architectural Engineering DepartmentPenn State University, @ Univ. Park, PA sam11@psu.edu; jqj102@psu.eduhttp:// doas-radiant.psu.edu

  2. Presentation Outline • First thoughts when considering DOAS-CRCP control. • DOAS-CRCP design philosophy. • Summary of the design issues you may wish to consider. • Field experience with single zone controls. • Extension to multi-zone applications designed with a DOAS supply air temperature equal to the required design SA DPT. Why you ask!

  3. First Thoughts about control? Points list Nyquist Plots Stability and dynamic response Schematics Z and Laplace Transforms Sequence of operation Bodi Plots BACnet

  4. High Induction Diffuser 20-70% less OA, Cool/Dry Supply DOAS Unit W/ Energy Recovery Building With Sensible and Latent cooling decoupled Parallel Sen. Radiant Cooling System DOAS-CRCP Design Concept

  5. Issues that impact Control • Thermal comfort, temperature and humidity control. • DOAS SAT, neutral or cold. • Envelope, Internal generation (high or low occ. Density), & Geo. Loc. • Std. 62, and IAQ. • ADPI with low to very low air flow. • Condensation control. • Instrumentation for control and monitoring. • Controlled devices. • Desire for BACnet compatibility & Web Access. • Control hardware and software.

  6. Schematic & Control Points: Single Zone DOAS-CRCP System

  7. 2. Occupied-Unoccupied Control

  8. 3. Enthalpy Wheel Control

  9. 4. Chiller Control

  10. 5. Cooling Coil Control

  11. 6. CRCP Control

  12. 7. Thermodynamic Calculations

  13. Extension to Multi-Zone Facility • Case 1, Low Occupancy Density Facilities such as Offices. • Maintain low SAT, i.e. EW with CC. • Modulate the panel inlet water Temperature rather than flow as in the single zone. • Space DPT sensing not required, provided DOAS supply conditions maintained, but condensation sensing is still needed in some perimeter spaces. • If movable sash facility, sash position sensing is required.

  14. Extension to Multi-Zone Facility • Case 2, High Occupancy Density Facilities such as schools. • Maintain low design SAT with capability of central “free” reheat, i.e. EW-CC-SW. • A critical space reset control will be discussed next. The intent is to minimize terminal reheat energy use.

  15. Paper Figure 3 ReHt EW--CC-- SW CRCP Is Terminal Reheat allowed? Yes!!! See ASHRAE Std. 90.1- 2004; Sec. 6.5.2.1 “If the air reheated does not exceed that required to meet ASHRAE Std. 62.1” Space 1 of nDBT, %RH

  16. OA h ReHt RA h, EW--CC-- SW CRCP Operate the EW whenOA h > RA h, otherwise off SpaceDBT, %RH

  17. CC CV ReHt EW--CC-- SW CRCP Modulate the CC CV so no space %RH > 55%orno space DBT > 75 SpaceDBT, %RH

  18. CRCP CV ReHt EW--CC-- SW CRCP Modulate the SW speed to hold at least one CRCPCV wide open SpaceDBT, %RH

  19. ReHt CV CRCP CV ReHt EW--CC-- SW CRCP Modulate the CRCP CV & the ReHt CV in sequence to maintain the Space DBT @ 75F SpaceDBT, %RH

  20. Conclusions • The single zone DOAS-CRCP system has been operating superbly now for over 3 years with the controls presented here. • Without a single incidence of condensation. • Maintenance free. • Based upon that experience, the control was extended to a multi-zone building utilizing low SAT. A CRITICAL ZONE DBT AND DPT RESET SCHEME • The many interacting local control loops in the reset control will require care (slow response) to avoid hunting.

  21. Questions