320 likes | 686 Views
Power Factor Correction. KW KVA KVAR. Power Factor is the ratio between Power and Apparent Power Motors. Reasons behind P.F corrections. P.F = watts/va Or P.F = P/S. Formula P.F. Power Factor Improvement. Over Correction Individual power factor correction. Power Factor Improvement.
E N D
Power Factor Correction KW KVA KVAR
Power Factor is the ratio between Power and Apparent Power Motors Reasons behind P.F corrections
P.F = watts/va Or P.F = P/S Formula P.F
Power Factor Improvement • Over Correction • Individual power factor correction
Power Factor Improvement • Group power factor correction
centralized automatic power factor correction Utility P.F Correction
Shunt Reactors Series Reactors Reactors
Edmonton downtown network Calgary downtown network Underground Networks
Reduce electrical costs. Reduce load losses of the distribution system. I²R Loss Increase the system's capacity. Maintain a better voltage regulation on the system. Improves P.F. Benefits of Power Factor Correction
Capacitors hold charges High Quality Capacitors Capacitors in transit Safety
Rules for P.F Calculations • Power input in a load is what the utility see as load • P= KW or W
Power is constant KW or Watts Output power is what the customer sees KW or Watts Rules
Cal. All Power Values @ original P.F 1st SmPmQm Cal. All Power Values @ New P.F (corrected p.f) Using Pm – constant Scor and Qcor or Delivered Rules
Find the Qreq or the Q of the cap required to correct the P.F Qcap = Qm - Qcor Cal Size of Cap’s Xc value Xc = E²/Qcap Rules
Cal the Cap size to μF C=1 x 106 / 2п f Xc Assume 60 Hz Rules
Size the cap for total bank size if required per individual cap divide by 3 Remember Power is always constant Rules Qt = √S² - P²