LUMEN METHOD. Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation.
E N D
LUMEN METHOD • Utilization factor-- Ratio of flux received by reference plane to total rated lamp flux in the installation. • Utilization factor of a lighting installation depends only on polar curve of the luminaire, the room geometry (represented by room index) and reflectances of the ceiling, wall and floor. ELEC 3105
Maintenance factor – -- LSF -- LLMF -- LMF -- RSMF ELEC 3105
LUMEN METHOD • E= N x n x ø x UF x MF A • where MF = LLMF x LSF x LMF x RSMF • E =Maintained illuminance, lux • A = Area, m2 • Ø = Initial lamp flux, lumen ELEC 3105
LLMF & LSF ELEC 3105
(Taken from Table 3.4 of CIBSE Code for Lighting, 2002) ELEC 3105
LMF ELEC 3105
LMF (Taken from Table 3.5 and 3.6 of CIBSE Code for Lighting, 2002) ELEC 3105
RSMF ELEC 3105
RSMF (Taken from Table 3.7 of CIBSE Code for Lighting, 2002) ELEC 3105