An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. POWER GRID CORPORATION OF INDIA LIMITED Presentation on ‘FREE GOVERNOR OPERATION”

  2. FREE GOVERNOR OPERATION FREQ COMPARISION MAY-02 & MAY-03 ROLE WHY ABT & GOVERNOR BEFORE GOVERNOR GOVERNOR RESPONSE IN NER BLOCKED GOVERNOR CHARACTERISTICS GOVERNOR TYPES GOVERNOR GOVERNOR TIME LAG DEAD BAND TIME DELAY BACKLASH DROOP FREQUENCY DECAY RATE TYPES OF CONTROLS DROOP RESPONSE IN SR ADVANTAGES PROBLEMS LIST OF GENERATORS FREQUENCY BASED DISPATCH FREQUENCY BASED DISPATCH SUPPRESSED GOVERNOR ACTION PID CONTROL PTI TAPE ORDERS

  3. ORDERS IEGC 1.6 IEGC 6.2 (e) & 6.2(f) IEGC 6.2 (g) IEGC 6.2 (h) NLY PETITION WEST BENGAL

  4. ROLE OF SYSTEM OPERATOR • LOAD GENERATION BALANCE 50

  5. WHY DOES FREQUENCY DROP ? Sudden addition of load causes a drop in frequency. An increased load is supplied through an increase in the load angle by which the rotor lags the stator field. It means a loss of Kinetic Energy of the rotating M/c and a slower speed of rotation i.e. a lower frequency. f = (P/2) X (N/60) Where f = frequency of the system P = no of poles of the M/c. N = rpm of the M/c. Next

  6. PRIMARY CONTROLS • Load Frequency control • Free Governor Opertaion • Under Frequency Operation

  7. ABT AND GOVERNOR POST ABT FREQUENCY WITHIN 49 TO 50.5HZ ACHIEVED BY STAGGERING OF LOADS FLUCTUATION IN FREQUENCY INCREASED Show Me

  8. 2003 2002

  9. HUMAN GOVERNOR OPERATION SYSTEM TG ~ X GOVERNOR

  10. GOVERNOR SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY WHEN THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY) WHEN THERE IS A CHANGE IN SYSTEM FREQUENCY GOVERNOR RESPONSE BY CAUSING VALVES/GATES TO OPEN/CLOSE TO INCREASE/DECREASE THE INPUT TO THE PRIME MOVER Next BTG

  11. MISCONCEPTION Governors attempt to restore frequency to normal. In reality, Governors attempt to restore load generation balance, using frequency change as a signal. Next

  12. Next

  13. BACK

  14. 1. Respond promptly to a small change in speed. 2. Adjust the throttle valve with a minimum of overshoot. 3. Have sufficient power to overcome friction losses and unbalance forces in the throttle valve. 4. Permit very little speed fluctuation under constant load and steam conditions. CHARACTERISTICS

  15. Mechanical shaft Direct acting orifice Oil relay Precision oil relay Electronic governor TYPES OF GOVERNORS

  16. DEAD BAND DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH THERE IS NO ACTION BY GOVERNOR. IEC - 45

  17. DROOP CHARACTERISTICS THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY TO CAUSE THE MAIN PRIME MOVER CONTROL MECHANISM TO MOVE FROM FULLY CLOSED TO FULLY OPEN. NORMAL RANGE - 3 TO 5% THE MINIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE LESS THAN 0.4 TIMES OF ITS DROOP. THE MAXIMUM RATE OF CHANGE OF SPEED SHOULD NOT BE MORE THAN 3 TIMES OF ITS DROOP. Next

  18. Next

  19. Next

  20. Next

  21. Next

  22. GOVERNOR TIME LAG TIME TAKEN BY GOVERNOR TO JUST BEGIN CHANGING POWER OUTPUT TO STABILISE FREQUENCY. OR TIME BETWEEN A CHANGE IN GENERATOR SPEED & CHANGE IN TURBINE POWER.

  23. TIME DELAY IN GOVERNOR OPERATION • Dead band 0.25 sec • Valve opening 0.5 sec • Steam flow 4 seconds • During transient state Governor is of little help. • Effect is felt during steady state

  24. BLOCKED GOVERNOR • BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN FIXED GENERATOR OUTPUT. • DISADVANTAGES:- • SYSTEM INSTABILITY • RESTORATION OF SYSTEM FREQUENCY TO NORMAL TAKES MORE TIME AFTER A DISTURBANCE.

  25. FREQUENCY DECAY RATE Approximate Freq 5 X Lost Generation Decay Rate = -------------------------------------- In Hz / sec Remaining Generation Example:- 2200MW 200MW Generation Lost Freq decay rate = (5 X 200) / 2000 = 0.5 Hz /second

  26. Next

  27. Next

  28. Next

  29. Next

  30. Next

  31. 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 POINT C POINT D POINT B POINT A POINT A - GENERATION LOSS POINT B – GOVERNOR ACTION STARTED POINT C - FREQUENCY AFTER GOVERNER ACTION POINT D – FREQUENCY AFTER OPERATOR ACTION

  32. BACKLASH The distance through which one part of connected machinery, as a wheel, piston, or screw, can be moved without moving the connected parts.

  33. BOILER CONTROLS • BOILER FOLLOWING SYSTEM • TURBINE FOLLOWING SYSTEM • INTEGRATED CONTROL SYSTEM SHOW SYSTEM

  34. BACK NEXT

  35. Next

  36. 50

  37. ADVANTAGES • Reduce the random change of frequency • Mitigate effect of load generation mismatch • Prevents wastage of fuel during low load condition • Faster restoration from grid disturbance

  38. Steam deposits on the valve stem . Lubrication deposits (i.e., soaps, dirt, detergents, etc.) in the top works of the valve exposed to the elements. Mechanical failures of the valve resulting from bent stems, either in the valve proper or the upper works, damaged split couplings, etc., all within about a 6" area near the center of the valve mechanism. Galling of the piston in the hydraulic latch cylinder. Jamming of the screw spindle in the larger cylinder-type valve design due to forcing by operations personnel PROBLEMS

  39. FREE GOVERNOR OPERATION • Mother of all Controls • Self healing mechanism • Collectively Control • Most equitable • Reduces risk of collapse • Makes restoration easy • World wide mandatory practice

  40. NEXT

  41. STEADY STATE OPERATION AT 50 HZ GEN= 190MW NEXT

  42. OVER GENERATED BY 5% FREQUENCY DIPPED TO 49.8 HZ GENERATION INCREASED BY 10 MW NEXT

  43. OVER GENERATED BY 5% NEXT

  44. STEADY STATE OPERATION AT 50 HZ GEN= 190MW NEXT

  45. INITIAL FREQUENCY RISE UPTO 50.2 HZ GENERATION DECREASED BY 17MW UI PRICE = 84 Ps NEXT

  46. INITIAL FREQUENCY RISE UPTO 50.2 HZ GENERATION DECREASED BY 17MW UI PRICE = 84 Ps NEXT

  47. SINCE VARIABLE COST OF STATION A > STATION B FINAL GENERATION FURTHER REDUCED BY 17MW NEXT