RMM Systems, LLC By Sam Rietta

RMM Systems, LLC By Sam Rietta. RMM Systems, LLC is a manufacturer's representative firm focused on providing value added sales solutions by providing customer service, technical support and application assistance to our customers, design engineering firms and specification authorities.

holmes-hull
Download Presentation

RMM Systems, LLC By Sam Rietta

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RMM Systems, LLCBy Sam Rietta RMM Systems, LLC is a manufacturer's representative firm focused on providing value added sales solutions by providing customer service, technical support and application assistance to our customers, design engineering firms and specification authorities. It is our goal to provide a high degree of professionalism to complement the image and objectives of the leading manufacturer's of electrical equipment we represent.

  2. Have you ever lost a motor? • Caused a loss of production? • After a storm? • Same motor over and over again? • While you were away from the plant? • Something happened on the power company side. • Didn’t know why?

  3. Why Do Motors Fail? Common Causes of Motor Failures

  4. Costs Associated with Motor Failures • Equipment downtime $$$$ • Loss of production • Collateral equipment damage • Equipment replacement • Work in process damage • Overtime for repair crews

  5. Motor Windings Breakdown • Thermal • Mechanical • Environmental

  6. Thermal Breakdown • Rule of thumb: A 10o C temperature rise above rated temperature will half the life of a motor • Motor operating temperature is based on: • 40o C ambient temperature • Class B Insulation limit is 130o C • Class F Insulation limit is 155o C

  7. Thermal Breakdown Causes: • Overload • Voltage Variations • Single Phasing • Short Cycle • Lightning and Surges • Improper Ventilation • Dirt & Dust Accumulation

  8. Mechanical Breakdown Causes: • Bearing failure resulting in rotor or stator rubbing insulation off • Vibration • Improper Alignment

  9. Bearing Failure Causes • Improper lubrication • Excessive belt tension • Mis-alignment

  10. Environmental Breakdown Causes: • Moisture / Water • Corrosion/ Chemicals • Rodents & Insects • Age

  11. Causes of Motor Failures 44 % of all motors failures are due to overloads and single-phasing.

  12. Bearing Rotor Failures Failures 5% Overload 13% 30% Contaminants Single Phasing 19% Misc 14% Old Age 9% 10% Why Motors Fail... * Based on 9,000 failure events researched by the Electric Motor Manual which was written by Robert Lawrie in conjunction with the staff at Electric Construction and Maintenance Magazine.

  13. Overload 30% Number One Motor Failure…Overload!

  14. Overloads “ It is practically impossible to burn out a motor from overload when it is protected by properly sized and maintained motor protection devices”. William P. Maples, P.E.

  15. Motor Service Factor Motor service factor of 1.15 means that the temperature rise of a motor will not exceed design temperature even if the motor is carrying a continuous overload of 15%

  16. U.L and IEC Test Procedures • U.L. 508 Determines test procedures for motor starters. • U.L. Short Circuit test procedures • Starter door cannot be blown open • Contacts must not disintegrate • Overload burnout is allowed with breaker tests.

  17. Short Circuit Protection of Motor Controllers

  18. IEC Standards • IEC Publication 947 “Low Voltage Switchgear and Control”

  19. IEC Levels of Motor Starter Protection • Type 1 Protection. • No discharge of parts beyond the enclosure is allowed • Damage to the contactor and overload relay is acceptable

  20. IEC Levels of Motor Starter Protection • Type 2 Protection. • No damage is allowed to either the contactor or overload relay • Light contact welding is allowed, but must be easily separable

  21. Voltage • Voltage Variations • Phase imbalance • Phase loss (Single Phasing)

  22. Voltage Variation Nema Standards states that motors shall operate successfully at rated load under the following conditions: • +/- 10% variation of rated voltage at rated frequency • Any voltage drop below 10% will reduce starting torque which can be serious because starting times may increase beyond allowable limits. • Winding failure from extreme voltage variations are identical to those of overloads because the input current is uniformily excessive.

  23. Low Voltage… Cause • Demand for power is greater than the supply • Long cable runs • Overloaded transformers • Distribution system

  24. Low Voltage… Effect Reduced efficiency Reduced life expectancy Increased temperatures Increased current Lower torque

  25. High Voltage… Definition Operating a motor above 110% of nameplate voltage

  26. High Voltage… Cause • Poor line regulation • Incorrect transformer tap • Utility demand down

  27. High Voltage… Effect • Reduced efficiency • Reduced power factor • Increased power consumption • Increased current • Increased temperature

  28. Voltage Unbalance Percent voltage unbalance = 100 xMaximum voltage deviation from average voltage average voltage

  29. Voltage Unbalance example: Assume voltages to a motor are 228 V to Phase A, 220V to Phase B and 236 V to Phase C. The average voltage is 228 V. The voltage unbalance is as follows: Voltage imbalance = 236-228x 100 = 3.5% 228

  30. Effect of Voltage Unbalance on Motor Longevity

  31. Effects of Voltage Unbalance Horsepower Derating

  32. Another Rule of Thumb…………. A 3.5% voltage unbalance will cause a 25% temperature rise. An increase in temperature rise in the phase with the highest current is 2 times the square of the voltage imbalance

  33. Causes of Voltage Unbalance: • Unequal loading of a three phase system • Unequal tap settings on transformers • Loose connections in the power system • Damaged starter contacts • Open delta transformer systems • Storms (wind, fallen trees, lightning) • Poor regulation by utility

  34. Example of heat rise due to voltage variations 50 HP Motor Heat rise 60oC Ambient Temperature 40oC 8% Unbalance Effect: 76oC (8x8=64 x 2= 128% x 60oC= 76oC) 176oC Result: Motor Failure

  35. Single Phasing 14% 14% of All Motor Failures - Single Phasing

  36. Secondary Single Phasing

  37. Secondary Single Phasing

  38. Causes of Secondary Single Phasing • Damaged motor starter contact • Burned open overload relay • Damaged switch or circuit breaker • Blown fuse • Open cable or bus on transformer secondary • Open motor winding • Open transformer winding

  39. Primary Single Phasing

  40. Primary Single Phasing

  41. Causes of Primary Single Phasing • Open line on primary • Storm (wind, ice, fallen trees, lightning) • Vehicle striking utility pole • Construction mishaps • Blown Primary fuse • Open contact on utility contactor or re-closer • Open winding on transformer

  42. RMM Systems In conclusion: • Motors will last a long time if operated within their design parameters. ( Voltage, current & temperature) • Identify the cause of your motor failure • When replacing motors also consider changing overloads and motor start contacts • For critical motors incorporate the latest motor monitoring products.

  43. Thank you! From RMMSystems