Transformer heat run test: The loading back method

Transformer heat run test: The loading back method. IEEE transformer Committee meeting, March 2008 By Marcel Fortin, eng., Consultant. Standard Requirement: C57.12.90 clause 11. Tests shall be made by one of the following methods: a) Actual loading b) Simulated loading

iokina
Download Presentation

Transformer heat run test: The loading back method

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Transformer heat run test: The loading back method IEEE transformer Committee meeting, March 2008 By Marcel Fortin, eng., Consultant

  2. Standard Requirement: C57.12.90 clause 11 • Tests shall be made by one of the following methods: • a) Actual loading • b) Simulated loading • 1) The short-circuit method, in which appropriate total losses are produced by the effect of short-circuit current • 2) The loading back (opposition) method, in which rated voltage and current are induced in the transformer under test

  3. Duplicate (not nessary) transformers may be tested by connecting their respective high-voltage and low-voltage windings in parallel (see Figure 27 and Figure 28). Transformers shall be tested with the combination of connections and taps that give the highest average winding temperature rise. This will generally involve those connections and taps resulting in the highest losses. Standard Requirement: C57.12.90 clause 11

  4. Loading back method

  5. Loading back method • Transformer 1: transformer under test • Transformer 2: « source » transformer • S1: variable source, provides essentially the total iron losses • S2: variable source, provides essentially the copper losses

  6. Loading back method Tranformer 1 • P1 : nomiral kVA • Ip1: nominal primary current • Is1: nominal secondary current • Up1: nominal primary voltage • Us1: nominal secondary voltage • Iz1: percentage impedance • N1: Up1/ Us1

  7. Loading back method Tranformer 2 requirements • P2  P1 • Ip2  Ip1 • Is2  Is1 • Up2  Up1 • Us2  Us1 • Iz2: percentage impedance • n2 = n1  (Iz1+Iz2) (base power: P1)

  8. Loading back method Source 1 requirement • Variable source • Voltage range: 0 to Us1 • Nominal current: enough to feed the total magnetizing current.

  9. Loading back method Source 2 requirement • Variable source • Voltage range: 0 to  total Iz voltage drop • Nominal current  Ip1