An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ASHRAE GPC 26 In-Situ Filter Testing

  2. In-Situ • In Original Position • In Place • As Installed

  3. Full Name of Guideline Guideline for Field Testing of General Ventilation Filtration Devices and Systems for Removal Efficiency In-Situ by Particle Size and Resistance to Airflow

  4. Easy and User Friendly

  5. Purpose • Provide test procedure for evaluating in-situ performance of: • Removal Efficiency of Filter Devices • Removal Efficiency of Filtration Systems • Resistance to Airflow

  6. Scope • For General Ventilation Air Cleaning Devices in their End Use Installed Configuration • Site Conditions must meet Minimum Criteria • Not Intended for : • HEPA or ULPA Filters • Portable Air Cleaners

  7. Test Equipment • Particle Counter • 3 Range Minimum • .3 to 5 Micron Size Range • Pump • Sampling Probes and Lines • Valve • Air Velocity Instrument • Relative Humidity Instrument • Temperature Measuring Instrument • Pressure Drop Gauges

  8. Equipment Setup

  9. Procedure • Record Conditions • Velocity • Humidity • Temperature • Pressure Drop • Visual Inspection • Take Fractional Efficiency Data

  10. Fractional Particle Efficiency Data • Filter Efficiency • Upstream probe within 24” • Downstream probe centered within 12” • Filtration System Efficiency • Upstream same as above • Downstream probe – in front of next component • Other “System” Test – across desired components –(pre, coils, fan, final)

  11. Sampling Probe Setup

  12. Sampling Method • Zero Particle Counter • Concentration Limit – Dilute if over 50% of instrument limit • Isokinetic Flow – within 20% • Prescreen Particle Concentration for Variability – 2 sets of 5 samples within 25% • Take Samples

  13. Samples • Alternating Upstream/Downstream • Purge between counts • Number of Samples • Minimum of 4 upstream and 3 downstream for each range • More to lower uncertainty • Sample Volume • Greater of 20 seconds or 1 liter

  14. Calculations of Fractional Efficiency

  15. Reporting Results • General Information • Which Filter Tested • Number and Type of Filters • Dimensions of Duct • Schematic Drawing showing Location of Sample Points • Equipment Used • When Filters were Last Changed • Other Observations

  16. Reporting Results (Cont.) • Airflow • Relative Humidity • Temperature • Pressure Drop • Fractional Efficiency

  17. Challenges • Isokinetic Flow • Turbulent Flow • Repeatability of Test • Operator Error or Inconsistencies

  18. Timeline • Final Draft by ASHRAE – Quebec • Review ?????