ASHRAE GPC 26. In-Situ Filter Testing. In-Situ. In Original Position In Place As Installed. Full Name of Guideline. Guideline for Field Testing of General Ventilation Filtration Devices and Systems for Removal Efficiency In-Situ by Particle Size and Resistance to Airflow.
E N D
ASHRAE GPC 26 In-Situ Filter Testing
In-Situ • In Original Position • In Place • As Installed
Full Name of Guideline Guideline for Field Testing of General Ventilation Filtration Devices and Systems for Removal Efficiency In-Situ by Particle Size and Resistance to Airflow
Purpose • Provide test procedure for evaluating in-situ performance of: • Removal Efficiency of Filter Devices • Removal Efficiency of Filtration Systems • Resistance to Airflow
Scope • For General Ventilation Air Cleaning Devices in their End Use Installed Configuration • Site Conditions must meet Minimum Criteria • Not Intended for : • HEPA or ULPA Filters • Portable Air Cleaners
Test Equipment • Particle Counter • 3 Range Minimum • .3 to 5 Micron Size Range • Pump • Sampling Probes and Lines • Valve • Air Velocity Instrument • Relative Humidity Instrument • Temperature Measuring Instrument • Pressure Drop Gauges
Procedure • Record Conditions • Velocity • Humidity • Temperature • Pressure Drop • Visual Inspection • Take Fractional Efficiency Data
Fractional Particle Efficiency Data • Filter Efficiency • Upstream probe within 24” • Downstream probe centered within 12” • Filtration System Efficiency • Upstream same as above • Downstream probe – in front of next component • Other “System” Test – across desired components –(pre, coils, fan, final)
Sampling Method • Zero Particle Counter • Concentration Limit – Dilute if over 50% of instrument limit • Isokinetic Flow – within 20% • Prescreen Particle Concentration for Variability – 2 sets of 5 samples within 25% • Take Samples
Samples • Alternating Upstream/Downstream • Purge between counts • Number of Samples • Minimum of 4 upstream and 3 downstream for each range • More to lower uncertainty • Sample Volume • Greater of 20 seconds or 1 liter
Reporting Results • General Information • Which Filter Tested • Number and Type of Filters • Dimensions of Duct • Schematic Drawing showing Location of Sample Points • Equipment Used • When Filters were Last Changed • Other Observations
Reporting Results (Cont.) • Airflow • Relative Humidity • Temperature • Pressure Drop • Fractional Efficiency
Challenges • Isokinetic Flow • Turbulent Flow • Repeatability of Test • Operator Error or Inconsistencies
Timeline • Final Draft by ASHRAE – Quebec • Review ?????