An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NPDgamma Liquid Hydrogen Target Safety Review Warning Alarms and Interlocks At LANL November 29-30, 2005

  2. A Plan is to have three-tiered hierarchy of status indicators for the system:Normal: The system operating as designed with all interlocks and sensors active and within set ranges.Warning: - Some sensor(s) are at values between low and high trip points. Local indication (target computer gives warning). - Target operator attention is required but automatic shutdown action is not needed.Alarm: - Some sensor(s) have exceeded their high trip levels. - Automatic safety and/or shutdown systems take over. - Local indications; horn and flashing light on FP12, area alarm at ER2/ER1, CCR has alarm and CCR gives alarm announcement at Lujan- All personnel should leave ER1/ER2.