ID3000 2 to 8 Loop Intelligent Fire Alarm Panel. Applications. Medium To Large Single/Multiple Building Systems Retrofit And New Construction Standalone Systems Networked Systems. Hardware Overview. Modular Design. Basic Equipment Kit. Cover(s). Extension Chassis (if required).
E N D
Applications • Medium To Large Single/Multiple Building Systems • Retrofit And New Construction • Standalone Systems • Networked Systems
Modular Design BasicEquipment Kit Cover(s) Extension Chassis (if required) Backbox(es) Optional Expansion Modules (if required) Power Supply
Key Components Backbox Power Supply Basic Equipment Kit Covers & Batteries & Extension Chassis
Basic Equipment Kit Expansion Cards Base Card ProcessorPCB Main Chassis Display PCB
Basic Equipment Kit Extension Options • Up to 3 Standard Loop Cards (LIB) • Up to 3 Enhanced Loop Cards (E-LIB) • One RS-232 Card • One RS-485 Card • One ID-Net Card
BEK - Inputs & Outputs • Outputs • A/B/C/D - Sounder or Relay programmable • Sounder - rated @ 1A/30V each • Dry contact relay - rated @ 1A/30V • Fault and Fire Relays VF rated @ 1A/30V each • Auxiliary 26-28Vdc outputs 1 and 2 both rated @ 1A • Battery charger max 8.6A (130Ah batteries) when used remotely.
BEK - Inputs & Outputs • Inputs • Mains - 230Vac ± 15% 50/60 Hz • Two addressable loops - 500mA/Loop • Tamper switch input (VF dry contact) • Communications • RS232 Port 1 • PC Programming, internal printer option • RS232 Port 2 (optional module) • RS485 Port (optional module)
Extension Chassis with 64 Zone Display Module Kit (with or without Printer) Extension Cover Blanking Plate Extension Chassis with PRN2000 Printer Module Kit Extension Chassis Options Double Extension Chassis with 255 Zone Display Module Kit
Optional Expansion Modules ID-Net Network Card Printer Module Kit Dual Loop Module Kit Enhanced Dual Loop Module Kit Isolated RS232 Module Kit Isolated RS485 Module Kit
RS232 Card Option Isolated port Third party interface External printer UniNet (NION) connection Pager interface VDU for terminal emulation RS485 Card Option Isolated Master/Slave network Repeaters Mimics Communication Modules
LIB Handles communication only System CPU scans loops In case of main CPU failure all detection is lost Max. 512 devices per panel (EN54) E-LIB Powerful microprocessor Degrade mode In case of main CPU failure the E-LIB will still activate sounder circuits 1-4 and the Fire Relay when an alarm is received from the loop Full 1584 device count on the panel (EN54) Standard LIB Vs E-LIB
Power Supply Selection Remote Battery/Charger Enclosure Kit Power Supply Unit Kit 2.5 Amp + Universal PSU Kit 4.5A or 7.0A (External enclosure or deep boxes only) PSU DTP Booster Kit (4.5 or 7.0A PSU only)
Power Supply Options 4.5A PSU mounts into the deep (extended) back box 2.5A PSU mounts on the side of the BEK DTP Booster mounts on the side of the BEK 7A PSU mounts into the external charger/ battery enclosure
Back box Options Flush Mounting Bezels Standard Back Box Kit Backbox Extension Kit (available in ‘standard’ and ‘deep’) Double Extended Backbox Kit (available in ‘standard’ and ‘deep’) Extended Back Box Kit (available in ‘standard’ and ‘deep’)
Backbox Options Standarddepth 12Ah 17Ah 17 Ah 38Ah 38Ah 78Ah Deep Boxes Standard Extended Double Extended External Box
Cover/Door Kits Security Door Kits (available for main & extension covers) Main Cover Kit (High Security option) Extension Cover Blanking Plate Extension Cover Kit (High Security option) Double Extension Cover Kit
19” Rack Mounting Option • 19” Rack Mounting Assembly for Basic Equipment Kit • 6U x 19” Rack Mounting Assembly for 7A PSU • 6U x 19” Rack Mounting Assembly for 64 Zone LED Extension Chassis & Printer Kit • 6U x 19” Rack Mounting Assembly for 256 Zone LED Extension Chassis Kit • 6U x 19” Rack Mounting Assembly for Printer • 3U x 19” Rack Blank Cover with Mains Termination Kit • 6U x 19” Rack Blank Cover with Mains Termination Kit • 3U x 19” Rack Mounting Assembly for Mimic Driver Kit • 6U x 19” Rack Blank Cover • 3U x 19” Rack Blank Cover
Main User Interface 6 Line x 40 Character Graphic LCD Navigation Keypad Numeric Data Entry & Enter/Cancel Main Control Switches Key switchAccess Level 2 System Status Indicators
Main User Interface • Fully EN54 compliant • Simple tabbed menu navigation • Prioritised event display (Automatically displays highest priority event) • User in control… has choice of what is displayed • Simple lights and switches for common controls • Top level info displayed
Graphic Display • Large 240 x 64 pixel LCD 6 lines x40 characters • Short-cuts for test & disablement • Selection by direct addressing • Displays: • Time and Date • Active Point Count for each event • Event type, index and actions • Panel, Zone and Device descriptors
Graphic Display System Information on Windows Style Tabbed Screens
Virtual Keyboard Panel and Zone Text up to 32 Characters via Keyboard to Navigate and to Select
Fire Alarm Display Example-3 Zones in Alarm: 2 Devices Alarmed in Zone 2 1 Device Alarmed in Zone 1 1 other zone in Alarm - Press “Zones in Alarm” to view others Use Navigation keys46 to scroll through zones and display other devices, date/time of event and device % value, etc. Short-cut key selects either device or zone disablement.
Fault Display 3 Zones are in FAULT with 4 events in the system. Use to scroll through zones and to display device, type, value, etc.
Disablement Display 142 Devices Disabled in 3 input zones. 12 devices are disabled in Zone 2 (all input devices). No outputs are disabled. Useto scroll through zone list and to see device details.
Main Features • Meets EN54 Parts 2 and 4 • Degraded mode of operation • Enhanced LIB (parallel CPUs) • Menu driven point/data access • Multi-level operator password control • Multiple language options
Key Functions • 9 sensitivity levels for Fire & Pre-alarm • Adjustable alarm & fault verification delay • Two-stage alarm operation • Alarm silence/re-sound • Sound general alarm (Evacuate) • Day and Night modes • Fire output(s) inhibit • Internal and external printer options
Key Functions • Powerful Control-by-Event (CBE) • Auto-Learn or PC programming • Duplicate address detection • One-man Walk Test with counter • Output device test • Daily high test • 2 pulse rates for outputs • Time of day functions
System CapacityStand-Alone • Up to 8 loops • 198 (99+99) devices per loop • Up to 1584 devices • Up to 255 zones • Up to 7A PSU • Up to 31 repeaters or mimics • Up to 512 LEDs per controller • 600 event history log
System CapacityStand-Alone • Four sounder circuits (NACs) • Rated @ 1A each • Two programmable as VF relaysrated @ 30Vdc/1A • Two 24Vdc auxiliary outputs • Rated at 1A each • Two programmable inputs • Fault and Fire relays • VF rated @ 30Vdc/1A • Two loops as standard • One isolated RS232 port (optional) • One isolated RS485 port (optional)
System CapacityInterlinked • Master/Slave interlink • Up to 32 network nodes • Maximum 8 panels • Remainder repeaters and mimics • Up to 64 loops in total • Up to 12,672 devices in total • Up to 2040 zones in total • Up to 56A PSU in total • Max. RS485 bus length of 3000m
Configuration Tool • Windows Operating Systems • Standard Windows features (cut, copy, paste, etc) • On-line error checking • Software protection • EN54 Network functions • Easy report printouts • Multi-lingual operation
On-Site Configuration • Multi-level password/key-switch access • Level 2: Code 1/Keyswitch - Panel controls & menus • Level 3: Code 2 - Level 2 + Configuration menus • Level 3A: Code 3 - Level 3 + Advanced Configuration • Panel settings • Auto-learn facility • Loop/Device configuration • Text Editor (Virtual keyboard) • Control matrix editor (512 lines) • Network configuration