1 / 11

BREEAM HIGHER EDUCATION AND LABORATORIES

BREEAM HIGHER EDUCATION AND LABORATORIES. Peter James Higher Education Environmental Performance Improvement (HEEPI) www.heepi.org.uk. BREEAM CHANGES.

lamond
Download Presentation

BREEAM HIGHER EDUCATION AND LABORATORIES

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. BREEAM HIGHER EDUCATION AND LABORATORIES Peter James Higher Education Environmental Performance Improvement (HEEPI) www.heepi.org.uk

  2. BREEAM CHANGES • BREEAM 2008 general changes- Credit updating, e.g. Energy & EPCs- Revised weightings- Minimum requirements- Innovation and exemplary credits- Post Construction Review • BREEAM HE campus changes • BREEAM HE lab related changes

  3. NEW/MODIFIED CREDITS • HEALTH17- Use of BS CEN 14175 on fume cupboard safety- Explicit H&S sign off • MANAGEMENT1 – Commissioning • MANAGEMENT4 – Building User Guide + 2cnd credit for Laboratory User • MANAGEMENT – Early stage design process

  4. LAB ENERGY CREDITS • Choice from a ‘menu’- up to 5 for larger labs, 3 for medium • Based on expert consultation process • Fume cupboard credits (1.5)- First credit mandatory for labs with fume cupboards • 10 additional half credits

  5. FAN POWER (Watts/Litre/Second) • General laboratory supply air AHUs with heating and cooling - 1.5 • General laboratory extract systems - 1.2 • Laboratory local extract (ducted) – 1.0 • Containment area (no HEPA) - 1.5 • Containment area (HEPA) – 2.5 • Fume cupboard extract – 1.5

  6. CONTINUOUS IMPROVEMENT SHARING EXPERIENCE -User group -User evaluation BUILDING CAPACITY -HE specific training -Sector assessors -Referral service? DRIVING IMPROVEMENT -Innovation credits -Benchmarking-Linking with DECS BREEAM HIGHER EDUCATION EFFECTIVE IMPLEMENTATION -Post occupancy evaluation -BREEAM in Use

  7. VENTILATION CREDITS • Grouping/isolation of high filtration/ventilation activities • Low pressure drop design- optimised duct runs; use of 3D modelling • Specification and achievement of best practice fan power

  8. HEAT AND COOLING CREDITS • Heat recovery- e.g. exhaust air (where no risk of cross-contamination) • Cooling recovery • Grouping of cooling loads • Specification of free cooling coils

  9. SYSTEM INTEGRATION CREDITS • Design integration- a documented process of dialogue and challenge between key suppliers (especially architects and engineers) and users to achieve right sizing; eliminate unecessary contingencies etc. • Load responsiveness- modularity; variable speed drives and pumps etc.

  10. FUME CUPBOARD CREDITS • Credit 1 – Exhaust volume air flow of below 0.16m3/second • Credit 2 – Below 0.12m3/s • Achieved – GSK; Newcastle • Comparison – Traditional CAV 0.25m3/s • Comparison – Cambridge 0.175m3/s • Prerequisite – HEALTH17 (BS 14175) + design team assurance on safety

  11. KEY QUESTIONS • Defining laboratories • Avoiding perverse incentives- fume cupboards and air change rates • Precise credit definitions- design integration- laboratory user guide- low pressure drop design