40 likes | 512 Views
The World Cup Soccer and Harmonic Distortion Paulo F Ribeiro. Measurement Point. Harmonic Distortion on the CHESF Transmission Grid Caused by: TV Receivers).
E N D
The World Cup Soccer and Harmonic DistortionPaulo F Ribeiro Measurement Point • Harmonic Distortion on the CHESF Transmission Grid • Caused by: • TV Receivers) Harmonic Distortion Measurements - 230kV Substation - During World Cup Soccer Game Fortaleza, Brazil, June 12, 1986Brazil 3 X 0 Ireland
Summary of the Measurements5th Harmonic Voltage – 230kV Bus Match Time
Voltage at the 230kV - Detail of 13.2kV Residential Feeder Disconnection (before the beginning of the match) 7th Harmonic Led to Flexibility and Higher Tolerance Clearly indicates the origin the harmonic source / contribution to the 5th harmonic distortion on the 230kV bus.