An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CLIC CES Webex 12 Nov. 2008 • Summary: • Set of fire safety measures defined in CERN Safety Report • Proposed Structure for CLIC/ILC Fire Safety Report Fabio Corsanego Fire Safety CERN-SC

  2. Structure of the safety report The Safety Report is subdivided in several parts.. • Description of the hazards (non mitigated yet) • Measures to mitigate the hazard: • Prevention • A Design • B Organization • Protection • C Design • D Organization

  3. Basic Assumptions “Low fire load” in the tunnels Fire radiologic risk localized in few specific points (collimators, experiments)

  4. A) Prevention-design (1) • Subdivision into ventilation sectors • Possibility to increase ventilation flow in the tunnel ( to 2 m/s) 2 m/s

  5. A) Prevention –Design (2) • Pressurized access shafts P>0 Fire Rated 2 hrs

  6. A) Prevention-design (3) • All zones with “periodic access” have multiple way out • Evacuation system • Automatic Fire detection in areas with relevant fire load

  7. A) Prevention- design (4) • Electric Vehicles for Fire Brigade • Areas with large fire loads have internal hydrants • Warm magnets are interlocked with thermal detection

  8. B) Prevention-organization (1) • Temporary storage of combustibles forbidden • Regular maintenance of the automatic detection system • Fire Brigade has materials and resources adapted to the hazards.. • Hot work permits • No smoking facility

  9. C) Protection -design • Fire retardant no halogen cables and plastics • Emergency call points every 60m with evacuation buttons and phones • Emergency light and signs • Foam system in the cavern

  10. D) Protection - Organization • Fire brigade has intervention procedures including smoke extraction • Manual fire fight means (extinguishers, hydrants, are localized where there is large fire load) • Training for workers • Self rescue breathing devices

  11. Resume’ • The combustible amount is low, exception made for about 90 locations. • A large fraction of this combustibles burn with difficulty • The fire risk has been judged moderate • Experiments have foam deluge systems Residual risk: • If a fire happens underground people will have to reach an exit located, at worst, at 2.5 km distance • Breathing device to assist for 30 minutes in the smoke • Potentially a relevant fire damage to equipment • In case of fire, fire brigade will try to reach the spot (can take 60* minutes) an initiate fire fightwith manual extinguishers or, in few locations, with hydrants • The ventilation can be increased to help to reach the spot

  12. T=0: fire and smoke starts travelling in tunnel • t-=~ 20 min: smoke is detected; Fire Brig. Alerted • T=~25 min: the machine stopped; Fire truck on the way • T=~35mins: Smoke could reach outside if not filtered • T=~40mins Fire truck on surface • T=~50mins Fire twin underground (if RP ok) • T=~65 mins Fire Twins reaches the fire (if air is still sufficient) • T=~70 fire twins air is maybe over and have to be changed • And so on

  13. Proposed strategy for ILC-CLIC • No reference codes yet, but we should have at least 2 objectives: • Protect life= reach a safe area leading outside in less that 2-3 minutes • Protect property= damage contained to less that ?x (value should be indicated here)? in case of accident

  14. Proposed Structure for Fire Safety Report INTRODUCTIVE NOTES • ReferenceCodes for FirePrevention • Description of the facilityfrom the fireSafety Point of View DESIGN CONDITIONS: • Characteristicsof the Occupants • Abilityand Resources of the Fire Service • SpecialHazards in case of Fire, and Emergency Plan • FireLoad MEASURES TO PREVENT THE INSURGENCY OF A FIRE • Propertiesof the Combustible Materials • Protection againstElectric Faults • LightningProtection • WorksiteOrganization (firepermitsetc, work coordination)

  15. ESCAPE IN THE EVENT OF A FIRE • Escape Strategy • Type of Stairways and Access Ways • Internalevacuationpathways • TravelDistance to Reach an Exit • Doors • Access Control Locking • Guidance Signs for escape • Emergency Lighting • Evacuation Alarm • Communication Devices PROTECTION AGAINST THE SPREAD OF FIRE BETWEEN COMPARTMENTS • Subdivision intoFireCompartments • Fire Resistance Class of Structural and Non-structural ElementsSeparating the FireCompartments: • Technicalrooms on surface

  16. FACILITIES FOR FIREFIGHT: • Access routes for the rescue service: • Firegasventilation; • Equipment for ManualFireFighting: • Communication Systems; HEATING, VENTILATION AND AIR CONDITIONING (HVAC), and SMOKE EXTRACTION • General aspects common to the wholefacility • Commands(stop and activation) for the ventilation and smoke extraction system • Fireprotection construction of plant rooms and shafts • Protected Access Shaft • TUNNEL and Transfer line VENTILATION • Exepriment Hall Ventilation and SmokeExtraction

  17. FIRE PROTECTION INSTALLATIONS • Automaticfiredetection • Evacuation alarm system • AutomaticFire suppression Systems