200 likes | 405 Views
A LOW CARBON DEFROST SYSTEM . Tom DAVIES , Robin CAMPBELL, Varun THANGAMANI. Frigesco Ltd., Innovation Centre, University of Exeter. Tom@frigesco.com. 15 th Intnl Refrigeration and Air Conditioning Conference, Purdue, 2014. EXISTING DEFROST METHODS. Electric Hot gas Cool gas Warm liquid
E N D
A LOW CARBON DEFROST SYSTEM Tom DAVIES , Robin CAMPBELL, Varun THANGAMANI Frigesco Ltd., Innovation Centre, University of Exeter Tom@frigesco.com 15thIntnl Refrigeration and Air Conditioning Conference, Purdue, 2014
EXISTING DEFROST METHODS • Electric • Hot gas • Cool gas • Warm liquid • Reverse cycle • ALL USE EXTRA ENERGY TO MELT ICE AND THEN TO RE-CHILL • Some use thermal storage
FLASH DEFROST • REQUIRES A HEAT STORE INSERTED IN THE LIQUID LINE LEAVING THE CONDENSER • REQUIRES 3 SOLENOID VALVES + PIPEWORK • DOES NOT USE EXTRA ENERGY
POSSIBLE COLD CHAIN APPLICATIONS LARGE SYSTEMS – WAREHOUSES TRANSPORT SYSTEMS SUPERMARKETS AND CONVENIENCE STORES – WALK-INS RETAIL DISPLAY CABINETS (RDCs) DOMESTIC FREEZERS ______________________________________________ PLUS AIR SOURCE HEAT PUMPS
TESTS ON: Supermarket retail display cabinets - 4.8m worldwide. Cold Rooms - over 2.5m worldwide, 900k in large supermarkets, 300k in fast food (MacDonalds, Starbucks, etc) plus hospitals, schools, restaurants. Air source heat pumps, rapidly growing market. Over 2m units sold in Europe in 2010.
RDCTESTS 2.6m HALF GLASS DOOR PLUS OPEN WELL (R404A) BOTH REFRIGERATION CIRCUITS MODIFIED TO TAKE HEAT STORE MODULES COULD BE RUN WITH EITHER ELECTRIC DEFROST OR FLASH DEFROST 24hr TESTS TO COMPARE ENERGY CONSUMPTION TO EN23953:2005 STANDARD AT CC3. FLASH DEFROST REDUCED ENERGY CONSUMPTION BY 40% WITH 6 DEFROSTS PER DAY.
WALK-IN TESTS 8m3 STOREROOM WITH SIMULATED LOADS REFRIGERATION CIRCUIT MODIFIED TO TAKE HEAT STORE MODULE (R404A) COULD BE RUN WITH EITHER ELECTRIC DEFROST OF FLASH DEFROST 24hr TESTS TO COMPARE ENERGY CONSUMPTION FLASH DEFROST REDUCED ENERGY CONSUMPTION BY 20%
BENEFITS OF FLASH DEFROST Flash defrost eliminates the use of electrical power for melting ice Flash defrost limits the temperature rise in the air coil Flash defrost reduces temperature rises in the product Flash defrost reduces energy consumption in post-defrost re-chilling phase Flash defrost creates the opportunity to operate at higher evaporator temperatures Flash defrost allows more frequent defrosts