E N D
1. SR750Feeder Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators.
5. Complete time & inst overcurrent
Directional overcurrent control
Undervoltage and overvoltage
Negative sequence voltage
Undervoltage automatic restoration
Bus underfrequency
Autoreclosing (760 only)
Underfrequency automatic restoration
Breaker failure, breaker operation & trip failure, VT fuse failure
Cold load pickup
Syncrocheck
Bus transfer
Fault locator, event recorder and waveform capture
4 setting groups
Power factor - two independent stages
Analog input - level and rate
Total breaker arcing current
Metering: V I Hz W var VA PF
Demand: Ia , Ib , Ic , MW, Mvar, MVA
Reverse power (optional mod 008)
RS232 and RS485 ports
Modbus & DNP3 protocols
Drawout construction
7. 3 phase CTs
1 ground CT
Zero sequence
Residual Mention Dot orientation on CT’s and Pt’s.
Mention that you will discuss differential in next slide.Mention Dot orientation on CT’s and Pt’s.
Mention that you will discuss differential in next slide.
8. If you do not have a ground fault Ct the residual ground wiring works well.If you do not have a ground fault Ct the residual ground wiring works well.
9. 15 Digital Inputs
Setpoint Access (Fixed)
Wet or Dry Connections
14 Assignable
Breaker Functions
Control Functions
User Inputs with Alarm & Trip Capability & Delay
Block Functions
Block OC Functions
Transfer Functions
Misc Functions
Wet or Dry Type
Virtual Input Selections
If you have a Synchronous Motor use must us a 52B contact to let us know the motor is still running. If the current goes below 5% we think the unit has turned off. This is why you will see so many starts in the statistical data.If you have a Synchronous Motor use must us a 52B contact to let us know the motor is still running. If the current goes below 5% we think the unit has turned off. This is why you will see so many starts in the statistical data.
10. Trip and Close
Form A
20A Continuous & 40A make/carry (0.2s)
5 Auxiliary
Form C
10A & 30A make/carry (0.2s)
1 Solid State
15A @ 250Vdc for 500ms
Self-Test Alarm Contact
Form C
8 Analog Outputs
Assignable to any metered parameter
mA Range Specified in Model No.
1 Analog Input
Settable Trip & Alarm with Delay or Rate of Change
Settable to 0-1, 0-5, 4-20, 0-20 or0-10mA range If using the remote RTD unit on the 369 you wire this to one of the three 485 ports.If using the remote RTD unit on the 369 you wire this to one of the three 485 ports.
11. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
12. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
13. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
14. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
15. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
16. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
17. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
18. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
19. If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.If you have to go into the service factor we now cut off the lower end of curve. Do not shift the curve. Example 100 amp FLA, Used at 110 amps, 6 times is 600 verses 660. Voltage dependant will discuss on future slide
Trip coil supervision to monitor that coil is not open so that it will close when we tell it to close.
20. Individual Voltages & Currents (mag & angle)
Sequence Currents and Voltages (mag & angle)
Real, Reactive & Apparent Power
Real & Reactive Power Costs & Usage
Frequency & Power Factor
Running & Maximum Demand Levels
Current, W, Var, VA
Synchronizing Voltage & Frequency
21. Event Recorder (Last 100 Events)
Trace Memory
Up to 10 Faults at 16 Cycle Each
Selectable Prefault Cycles
Fault Locator
Breaker Trip & Close Coil Monitoring
VT Failure
Vo without significant Io
Total Breaker Arcing Current (I2t)
Monitor Single Analog Input
Threshold & Rate of Change
Data Logger
Any Measured Parameter
For Example: Demand I at 15min for 42 Days
22. Use enerVista 750 Setup Software to Retrieve and View Oscillography Files Mention Learned parametersMention Learned parameters
23. Mention Learned parametersMention Learned parameters
25. Flash Memory for Future Upgrades Free Upgrades on Web Site
Fully Programmable Keypad
40 Character Display
Selectable Message Scrolling
Self Testing
Draw out Case (no external hardware)
Mountable in Breaker Cabinet
Extensive IEC & ANSI Testing
Complete Burn-in and Testing on Relays
Front Door with Gasket and Lock Provision
Heavy Duty Terminals
ISO 9002 Certified, UL, CSA
Optional Conformal Coating Option for Harsh Environment (H)
26. Enhanced Version
Status LEDs
Fully Programmable Keypad
Target Reset Key
Menu Key
40 Character Display
Selectable Message Scrolling
27. Basic Version
Status LEDs
Fully Programmable Keypad
Target Reset Key
40 Character Display
Selectable Message Scrolling
29. enerVista 750 Setup Program
View Multiple Relays on Screen
Actual Values
Setpoints
Status
Event records
Oscillography
Data Logger trending
Setpoint programming
Setpoint files
Download updated firmware to Flash memory
1 Front RS232 Port
2 Rear RS485 Ports that support Modbus RTU or DNP3.0 Protocols
Optional 10BaseT Port
31. Converts Modbus RTU over RS485 into Modbus TCP/IP over Ethernet
Supports both 10BaseT and 10BaseF fiber connections
Industrially hardened product meant for harsh environments
Connect up to 32 RS485 serial devices to an Ethernet network
Modbus TCP/IP provides multiple SCADA masters allowing simultaneous communications to the same IED
Easy to use set up software
44. Questions?