An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Belimo Energy Valve™Delta T Manager™ Energy Valve Delta T Manager

  2. Presentation Agenda Energy Valve Delta T Manager • Low Delta T at the Coil • Some of Low Delta T Causes • Low Delta T • Cost of Overflowing Coil • Cost of Chiller Staging • Cost of Over Pumping • Occupant Comfort • Does it Really Work? • Benefits

  3. Low Delta Tat the Coil • Low Coil Delta T = Inefficient • Heat Transfer • Increase GPM >> No Increase in • Energy output • More Pump HP >> Reduction in • Plant Efficiency Energy Valve Delta T Manager

  4. Low Delta TSome of Low Delta T Causes Energy Valve Delta T Manager Low Control Set Point Fouled Coils Low Valve Authority

  5. Low Delta TCoil Power vs Delta T Behavior Energy Valve Delta T Manager

  6. Low Delta TCost of Overflowing the Coil… 1 335000 330000 2 Coil Power Curve 12°F Delta T Curve 10.5°F 55 GPM 65 GPM Energy Valve Delta T Manager

  7. Low Delta TCost of Overflowing the Coil… ? Energy Valve Delta T Manager

  8. Delta T Manager™Cost of Chiller Staging Design Condition • Design ΔT=12oF (54oF - 42oF) • 360 GPM • 1 Chiller, 90% Load (180 Ton) 360 GPM Loop flow Energy Valve Delta T Manager Chiller Plant Efficiency

  9. Delta T Manager™Cost of Chiller Staging Low ΔT • ΔT=10.4oF(52.4oF - 42oF) • 415 GPM • 2 Chillers, 45% Load (180 Ton) 415 GPM Loop flow No change to the load, but a 2nd Pump and 2nd Chiller are started. Energy Valve Delta T Manager Chiller Plant Efficiency

  10. Low Delta TCost of Over Pumping Delta T Manager Signal Wasted Pumping DDC Signal Delta T Manager On Delta T Manager On Energy Valve Delta T Manager

  11. Delta T Manager™Occupant Comfort “How can I let the Delta T Manager limit flow if it doesn’t measure discharge air temperature? What about occupant comfort?!?”

  12. Delta T Manager™Occupant Comfort Delta T Manager adjusts the valve if the ΔT drops below the set point in order to maintain peak coil efficiency Virtually No Power Reduction 335000 325000 Delta T Curve Power Saturation Power Curve Delta T Set Point 55 GPM 65 GPM Energy Valve Delta T Manager

  13. Delta T Manager™ Does it really work? Energy Valve Delta T Manager

  14. Case StudyLarge Tech Company in North Carolina DT Management 96 GPM Flow Control 144 GPM 240 GPM Position Control Energy Valve Delta T Manager

  15. Case StudyMIT University Hayden Library - Boston, MA Energy Valve Delta T Manager Building and Project Details • 150,000 sq. ft. on 3 floors • 6 AHU provide majority of the cooling Results • Aug 9 - Oct 9, 2010 DT = 6.15°F • Aug 9 - Oct 9, 2011 DT = 12.14°F

  16. Case StudyUniversity of Miami Hospital Building and Project Details • Rosenstiel Building • 11 AHUs • 2600 Tons of Cooling • Over 10,000 GPM Results • Delta T raised from 5.5°F to 10.5°F • Flow ~ 5600 GPM • Estimated $66,000/yr savings • Estimated 2.9 year payback Energy Valve Delta T Manager

  17. Delta T Manager™Benefits • Coil • ΔT Managing for peak coil efficiency • Optimization in retro-fit applications • Chiller Plant • Improved chilled water plant efficiency • Released chiller capacity • Pump • Reduced pump energy • Occupant Comfort • No reduction in supplied energy Belimo Americas Danbury, Connecticut

  18. Thank You !Visit (www.EnergyValve.com)or Contact Belimo(800) 543-9038 Thank You Energy Valve Delta T Manager