40 likes | 60 Views
This document outlines the step-by-step procedure for replacing the Variable Frequency Drive (VFD) in response to EVENT45752. It includes diagnostic observations, error messages, and proposed next steps for resolving the issue and improving procedures.
E N D
EVENT45752: QURCB P18, TimeLine INTERVENTION SCHEDULE
Variable Frequency Drive EDMS procedure #1134814 Magnetic Bearing Controller EDMS procedure #1257230
EVENT45752: QURCB P18, Intervention description 1- INITIAL DIAGNOSTIC: QURCB P18, VFD & watchdog AMB faults 1.1 - VFD replacement 1.2 - Customer's Interface board 3A2 replacement OBSERVATION 1:All CCs MB diagnostic signals lost DI fuse replacement 2- SECOND DIAGNOSTIC: message error ID 54 & 51 on new VFD 2.1: Code licence lost BACK to initial VFD OBSERVATION 2: protection Zener diode blows 33Q1 (VFD 24V PS) & 32Q4 (AO quantum card) down NOT ENOUGH TIME TO SOLVE PROBLEM => CC1 VFD still not operational
EVENT45752: QURCB P18, next steps • 1- POST EVENT ANALYSIS FROM CE EXPERT: • 24VDC Short circuit should occur with internal profibus PCB slot manipulation PROPOSAL: replace VFD spare, including licence update • all spares equipment left in SM18 (VDF, S2M, relay & interface card) • 2- FEEDBACK: This event was instructive to • - Update piquet procedures (already Done-OK) • - Define new task for Watchdog fault (in progress) • - Improve Spare management, Tools and access definitions