210 likes | 534 Views
TESYS U COMMANDE PAR MODBUS TSX MICRO. MARSEILLE LE 17 NOVEMBRE 2004. 02/2004. SCA62. SCA62. Liaisons série : Modbus. Pré-câblage bobine. Module MODBUS. Té MODBUS. Cordon blindé. TSX37 22. TESYS U. MAQUETTE LYCEE. CHARGE. SHEMA CABLAGE. CONFIGURATION CARTE TSX MICRO.
E N D
TESYS U COMMANDE PAR MODBUS TSX MICRO MARSEILLE LE 17 NOVEMBRE 2004 02/2004
SCA62 SCA62 Liaisons série : Modbus Pré-câblage bobine Module MODBUS Té MODBUS Cordon blindé
TSX37 22 TESYS U MAQUETTE LYCEE CHARGE
MODULE LUCMX6BL MULTIFONCTION MARCHE AVANT ECRITURE REGISTRE
ECRITURE 1 MOT REGISTRE 704 DANS TESYS_U A PARTIR DU MOT MW200 DU TSX
MODULE LUCMX12BL 100% = 3A LECTURE LECTURE REGISTRES
LECTURE 12 MOTS CONSECUTIFS A PARTIR DU REGISTRE 455 DE TESYS_U RANGES A PARTIR DU MOT MW100 DANS LE TSX
EVALUATION DU TEMPS DE TRANSMISSION. A/ THEORIQUE. CALCULS DE TRAMES, NOMBRE OCTETS,TEMPS, ETC... B/ PAR PROGRAMMATION. MESURE PAR PROGRAMME , LIMITES... C/ PAR OSCILLOSCOPE. MESURES REELLES SUR LA LIGNE DE TRANSMISSION OU SUR ACTIONNEURS.
A/ Théorique ( Lecture 12 mots ) Évènement Compte rendu 13,5ms (9ms*1,5) 13,5ms TSX 37 TC1 TC1 TC1 TC1 Temps de cycle équipement 1 LIGNE RS485 9600Bds TCB Temps de cycle bus Modbus 9,2ms TCB 33,2ms COM TESYS_U Temps de cycle équipement 2 TC2 TC2 70ms CONTACTEUR Action Temps total # 140ms
B/Programme Tâche rapide
C/Oscilloscope Total : # 150 ms