An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Overview of Digital Relays ISO Training John S. Levine, P.E. Levine Lectronics & Lectric John@L-3.com www.L-3.com

  2. ISO Training July 22, 2008Outline • Introduction • Overview of Digital Relays • Tools • Enervista Launchpad • PowerPoint presentations at • GE Digital Relays • Protection Basics • SR489 • GE Multilin G30 Training • Post Glover NGR Training • ANSI Symbols handout • Conversion of Electro-Mechanical to Electronic sheet • GE Multilin Training CD’s

  3. Trends • 75% of Installed Base of Relays are Electromechanical • 90% of New Relays Purchased are Digital/Electronic • Lingering Issue of “Putting All Eggs In One Basket” • “No Backup” • “Like to See Disk Move” • Solve with Backup (such as DIAC as backup to SR760 or F60) • Gain Excellent Accuracy and No Setting Drift • Manufacturers have Created Relay Families, thus reducing maintenance, O&M costs and training.

  4. Microprocessor-Relay Benefits • Multi-Function Protection Cost Effectiveness • Configurable/Programmable Logic • User Configurable Time Current Curves • Self-Testing of Relay’s Algorithms with Alarm Contact • Reduce Periodic Testing • Every 1-2 years for Electromechanical • Every 5-10 years for Digital (or More!) • Improved System Data • Fault Location & Reporting - Waveform Capturing • Internal Operation Data - Metering • Breaker Health Monitoring - Demand Interval Records • Sequence of Event Reporting

  5. Microprocessor-Relay Benefits • Flexible Settings • Multiple Setting Levels • Communication Capabilities • Local via Keypad • Remote via Computer and Modem • Networks can be created • Reduced Panel Space & Wiring • Compact Packaging • Tested at Factory • Eliminate Component Panel Metering

  6. Digital Relays - Areas Of Use • Distribution Feeder Protection • Reclosing • Down Conductor Detection • Breaker Failure Protection • Generator Protection • Transmission Line Protection • Transformer Protection • Bus Protection • Motor Protection

  7. NEW OLD

  8. Programmability • Digital Relays Have: • Programmable Inputs • Programmable Outputs (ALARM & TRIP) • Programmable Logic • Boolean Logic - AND, OR, NOT Logic • Programmable Time Current Curves

  9. Waveform Capturing Including Bar Plotting of Unit Operation

  10. Metering • 0.25 - 5% Accuracy on I & V • Typical Values • Can Be Accessed Locally or Remotely • Some Relays Have Analog Outputs Proportional to Metering Values (i.e. 0-1mA) • Min & Max Values with Date & Time Stamp • Harmonic Values of I • Symmetrical Components • Operation Counters • Breaker Position • Current • Voltage • Watts, Vars, PF • Frequency • kWh, kVarh • Phase Angles

  11. Metering

  12. Other Monitoring • Breaker Health Monitoring • Cumulative I2T or IT • Activate Alarm At Set Level • Demand Interval Reporting • 15, 30, 60 Minute Intervals over Several Days • I, Watts, Vars, VA, PF • Peak Values Recorded • Date & Time Stamped • Trip & Close Coil Monitor • Fault Location & Fault Reporting

  13. Sequence Of Events Recording • Events Stored with Date & Time: • Alarms • Contact Operations • Logins & Logouts • Waveform Captures • Remote Operations • Resets • Setting Changes • Last 100-1000 Events Stored

  14. Settings • Easier Than Electromechanical/Static • Flexible settings • Relays Have Multiple Setting Groups • Can be Switched with Input Contacts or Remotely • Settings Are Stored in Files and Down Loaded to Relay with PC • Easy to Copy Existing Setting Files and Modify • Accurate Implementation of Settings • No Overtravel • No Large Drifts in Set Points • Selection of Reset Times • Fast (Digital) or Slow (Electromechanical)

  15. Phase A Phase B Phase C Alarm 87 Local Communications • Thru Keypad, Up, Down Arrows, Enter/Select Keys or RS232 Port on Relay • Local LED Display • Reset Key/Button • LED Targets • Password Protection Phase TOC1 OP DN UP ENTER

  16. Communications

  17. DSL or Telephone Modem RELAY Modem Remote Communications • Thru Rear RS232 or RS485 Port Using Standard Modem Software or Relay Manufacturer’s Communication Software • Password Protection • 10Mbps Ethernet Connections - Wire or Fiber • Multiple Protocol Support (DNP3.0, Modbus RTU, Devicenet, Profibus, and IEC 61850)

  18. Substation Communications - LAN & WAN

  19. Communications

  20. Memory Map Example Group Address Description Current 0300 Phase A Current 0301 Phase B Current 0302 Phase C Current 030D Phase A Differential 030E Phase B Differential 030F Phase C Differential

  21. Reset Data Min/Max, Demand, etc. Reset Targets Operate Output Contacts Trip & Close Trigger Waveform Capture Set Date & Time Force Input Contact Operation Block Relay Functions Perform Setting Changes Available Control by Digital Relaysvia Communications & Protocols

  22. Maintenance Benefits • Self-Test Capabilities • Remote Communications • Easy Setting Changes • One Model Could Be Used for Several Applications • No Setting Drift of Digital Relay • Reduced Wiring • Flash Memory • Upgradeable Firmware

  23. Today’s Feeder and Transformer Digital Relays

  24. DIAC,DIFC,DSFC Single Phase Overcurrent Protection • Digital Overcurrent Relay Platform w/ True RMS Overcurrent Measurement (50/51) • Replace IAC, IFC and SFC relays. . . • Self Powered (no DC Battery Required) • Same case size, no metal modifications • Simply add surge ground lead • User Selection of 16 curve characteristics • Exact Duplication of IAC51, IAC53 & IAC77 Characteristics • Instantaneous Overcurrent Delay Setting • Reset Characteristic Selection (Fast or E/M) • Draw-out Case with Test Facilities • Retrofit existing IAC, IFC and SFC Cases • Very Low Burden (1.8VA) • No Communications

  25. SR760 - Feeder Protection • 16 Samples/Cycle • 3 Phase & Ground Overcurrent Protection • Programmable Time Current Curves • Over/Under Voltage • Over/Under Frequency • Synch Check • 4 Shot Reclosing • Fault Location • 4 Setting Groups • Analog Outputs/Input (8/1) • Metering I, V, W, Var, VA, PF, Hz, Wh, Varh • Waveform Capturing • RS485 Communications • DNP3.0 and Modbus RTU Protocols • Flash Memory for Upgrades • Drawout Construction • Programmable Display • Simulation Test Mode • IRIG-B Time Sync

  26. SR489 Generator Management Relay Product Overview • Ideal Protection for Induction and Synchronous Generators at 25, 50 and 60Hz • Complete Generator Protection including: • Generator Stator Differential • 2 Zone Distance Backup • 100% Stator Ground • High speed sampling, 12 samples per cycle • Drawout Case Installation • Powerful Fault Recording: Waveform, Sequence of Events • Ethernet and Serial Communications • EnerVista Suite of Software supported • Metering of all important parameters

  27. SR489 Protection Functions • Protection Functions Include: • Generator Stator Differential • Backup Distance Protection • 100% Stator Ground • Generator Unbalance • Loss of Excitation • Accidental Energization • Breaker Fail • Phase Overcurrent – Voltage Restraint • Neutral Inst. / Timed Overcurrent • Neg. Sequence Overcurrent • Under / Over Voltage • Under / Over Frequency • Generator Thermal Model • RTD Temperature • Overexcitation – Volts/Hertz

  28. SR745 - Transformer Protection • 64 Samples/Cycle • 3 Phase Differential Protection • 3 Phase & Ground Overcurrent per Winding • Adaptive Time Overcurrent • Programmable Time Current Curves • Loss of Life Monitoring (Opt.) • 4 Setting Groups • Harmonic Analysis (up to 25st) • Angle & Zero Sequence Compensation • Analog Outputs/Input (Opt.) • 2 & 3 Winding Models • Configurable Logic • Waveform Capturing & Playback • Simulation Test Mode • Flash Memory for Upgrades • RS485 Communications • Modbus RTU and DNP3.0 Protocols • Programmable Display • Dynamic CT Ratio Correction • IRIG-B Time Sync SR745 Transformer Management Relay

  29. The UR Family - One Common Architecture TRANSMISSION DISTRIBUTION • L60 (Transmission Line: Phase Comparison) • L90 (Transmission Line: Current Differential) • D30, D60, abd D90 (Transmission Line: Distance) • B30 and B90 (Busbar: 6 to 24 Feeder) • F35 (Feeder: Multiple Feeders - Basic Protection) • F60 (Feeder: Comprehensive w Hi-Z) • T60 (Transformer: Comprehensive) • C30 (Control IED) • C60 (Breaker Management IED) GENERATION / MOTOR • G30 and G60 (Generator: Comprehensive) • T60 and T35 (Transformer: Basic up to 6 Windings) • B30 and B90 (Busbar: Comprehensive up to 24 Feeders) • M60 (Motor) “The Engine for Substation / Plant Automation”

  30. Modular Hardware Family

  31. Physical Realization 19’’ Chassis (4RU high) or Vertical Unit Modules Power Supply COMMUNICATIONS DSP & Magnetics DSP processor + CT/VTs DIGITAL I/O Status Inputs / Control Outputs ANALOG I/O Analog Transducer I/O CPU Main Processor Modular HMI (Hinged & Removeable) High-Speed Data Bus

  32. ‘Upgradeability’/Serviceability ‘Plug n Play’ Easy Module Draw-out Module Keying Field Wiring Undisturbed CT Shorting ‘Clips’ CPU Automatically Recognizes New Hardware upon Initialization

  33. Example: Busbar with 5 Feeders 79 79 79 79 79

  34. Example: Inputs in to UR Relay CT2 CT1 CT4 CT5 CT3 VT1

  35. Example: UR Relay using Sources 79 79 79 79 79 Universal Relay 50-Inst, 51-Time, 81-Freq, 79- Reclose

  36. F60 Feeder Protection • Single Feeder Protection with Bus Voltage • Phase, Neutral & Ground Time Overcurrent (51P, 51N, 51G) • Phase, Neutral & Ground Inst.Overcurrent (50P, 50N, 50G) • Negative Sequence Time Overcurrent (51_2) • Negative Sequence Inst.Overcurrent (50_2) • Fast or EM Reset Characteristic for TOC Elements • Phase, Neutral and Negative Sequence Directional Control • Phase Undervoltage & Overvoltage • Negative Sequence Overvoltage • Underfrequency (6 elements) • Overfrequency • 4 Shot Autoreclosing with Sequence Coordination • VT Fuse Failure • Programmable Fast & Slow Operations • Breaker Failure (50BF) • Synchrocheck (25) • Cold Load Pickup • Breaker Arcing Current (I2t) • Data Logger & Fault Location • Transducer I/O • FlexLogic with gates and timers • Programmable LED Panels • Metering • Harmonic Metering (up to 25th) • Oscillography • Event Recorder & Fault Records • Demand Recording • DNP, Modbus RTU & UCA Protocols • 8 Setting Groups • Down Conductor Detection (Optional)

  37. F35 Multiple Feeder Protection • 5 Feeder Protection with Bus Voltage • 6 Feeder Protection w/o Bus Voltage • Programmable LED Panels • (6) Phase TOC elements • (12) Phase IOC elements • (6) Neutral TOC elements • (12) Neutral IOC elements • (6) Ground TOC elements • (12) Ground IOC elements • (1) Phase Undervoltage element • (6) Underfrequency elements • (6) Autoreclosing elements • FlexLogic with gates and timers • Transducer I/O • Data Logger • Metering • Oscillography • Event Recorder • Demand Recording • DNP, Modbus RTU & UCA Protocols • 8 Setting Groups

  38. LED Programmability

  39. T60 Transformer Protection • Up to 4 Restraint Inputs • 2 & 3 Restraint with Three Phase Voltage Inputs • 4 Restraint without Voltage Inputs • Dual Slope Percent Differential Protection (87T) • Harmonic Inhibit Feature • Overexitation Inhibit Feature • Instantaneous Differential Element (50/87) • Overcurrent Protection Per Winding (50/51) • Phase, Neutral & Ground Time Overcurrent • Phase, Neutral & Ground Inst.Overcurrent • Fast or EM Reset Characteristic for TOC Elements • Phase Undervoltage • Phase Overvoltage • Phase & Neutral Directional OC • Volts/Hz • Restricted Ground Fault • RTD and dcmA Inputs Available • Underfrequency (6 elements) • Data Logger • FlexLogic with gates and timers • Programmable LED Panels • Metering per Winding (I, V, W, Var, VA, PF) • Harmonic Metering (up to 25th) • Differential and Restraint Currents • Oscillography & Event Recorder • Demand Recording • DNP, Modbus RTU & UCA Protocols • 8 Setting Groups

  40. UR Applications Option 1 T60 - Transformer Protection F60 - Main Feeder Protection F35 - Backup Feeder Protection

  41. UR Applications Option 2 T60 - Transformer Protection F35 - Main Feeder Protection F35 - Backup Feeder Protection

  42. Tools

  43. Free PC Software and Firmware • Windows based • Access all: • Actual Values • Setpoints • Status • Event records • Oscillography • Graphical trending • Setpoint programming • Setpoint files • Download updated firmware to Flash memory

  44. Enervista Launchpad: http://www.geindustrial.com/multilin/enervista/launchpad/

  45. Demo Relays at L-3

  46. ANSI Symbols